Honeywell XYR 5000 LINE Transmitter Holding Registers, Device ID Mapping Mode, Register Address

Page 38

total from the subtraction and subtract the next largest number possible and so on until the result is zero. Each value that was used in the subtraction indicates that the Transmitter is online.

For example: The On/Offline Status holding register contains the value 15. In this case the largest value we can subtract is 8, which leaves a result of 7. Now we can subtract 4 from 7 and get 3. Now subtract 2 from 3 and we get 1. Finally we subtract 1 from 1 and get 0, so we are done. Which Transmitters are online? We subtracted 8,4,2 and 1, and these numbers correspond to Transmitters’ with RF IDs 1,2,3 and 4.

Note An alternate method to determining which Transmitter(s) are online is to look at the Base Radio Holding Register as a binary number with the rightmost bit representing Transmitter 1 and the leftmost bit representing Transmitter 16. For example, the binary representation for Transmitters 1-4 online is as follows:

0000000000001111

In another example, say the On/Offline Status holding register contains the value 6. We can subtract 4 to get 2. Then we can subtract 2 to get 0. Thus Transmitter 2 and 3 are online, but Transmitters 1 and 4 are offline.

6.5Transmitter Holding Registers

The following are the Transmitter holding registers when used in the Device ID Mapping Mode (First Table) and the Register Mapping Mode (Second Table).

6.5.1 Device ID Mapping Mode

 

Transmitter Holding

 

Device ID =

 

 

Registers

 

Base Radio Modbus ID + RF ID

 

 

(DEVMODE Only)

 

 

 

 

Register Address

 

Description

Register Type

 

00001

 

Device Type

32-Bit IEEE

 

00002

 

Device Type

Floating Point

 

00003

 

Device Status

32-Bit IEEE

 

00004

 

Device Status

Floating Point

 

00005

 

Primary Sensor Value

32-Bit IEEE

 

00006

 

Primary Sensor Value

Floating Point

 

00007

 

Secondary Sensor Value

32-Bit IEEE

 

00008

 

Secondary Sensor Value

Floating Point

 

00009

 

Tertiary Sensor Value

32-Bit IEEE

 

00010

 

Tertiary Sensor Value

Floating Point

6.5.2 Register Mapping Mode

 

 

 

 

 

 

 

Transmitter Holding

 

Device ID =

 

 

Registers

 

Base Radio Modbus ID

 

 

(REGMODE Only)

 

 

 

 

Register Address

 

Description

Register Type

 

00001 + (RF ID * 10)

 

Device Type

32-Bit IEEE

 

00002 + (RF ID * 10)

 

Device Type

Floating Point

 

00003 + (RF ID * 10)

 

Device Status

32-Bit IEEE

 

00004 + (RF ID * 10)

 

Device Status

Floating Point

31

 

 

 

 

Image 38
Contents Base Radio User Guide XYR 5000 Line 34-XY-25-05 Rev 08/06Page Base Radio FCC CertificationTelephone Revision NotesContacts Table of Contents Quare R OOT F Unction Overall Wiring Schematic Table of FiguresAbout the Device Using this ManualIntroduction Unpacking Software CompatibilityOverall Wiring Schematic Quick StartPage Base Radio Positioning InstallationMechanical Installation General Layout Electrical Installation Electrical SpecificationsTerminal Block Labels Wiring Power to the Base Radio Wiring RS-485 to the Base RadioWiring the RS-485/232 Converter to the Base Radio Wiring RS-485 to the Base RadioWiring the RS-485/USB Converter to the Base Radio USB Driver InstallationUSB Converter’s Male DB-9 Connector Daisy-Chaining Multiple Base Radios to Single RS-485/PowerWiring the DB-9 RS-485 Cable to the Base Radio USB Driver Un-installationDaisy-Chaining Power to Multiple Base Radios Daisy-Chaining RS-485 to Multiple Base RadiosTerminating Communications Wiring to the Base Radio Daisy-Chaining RS-485 to Multiple Base RadiosGrounding the Base Radio High Gain AntennaRead Only Sequence General ConfigurationBase Radio Displayed Messages Overall Configuration Menu Map Read Only SequenceSetting the User Password Menu Map to Password SettingConfiguring the RF Communications RF Channel SelectionMenu Map to RF Baud Rate Setting RF Baud Rate SelectionHigh RF ID Setting High Rfid SettingBase Radio Setup Modbus Baud Rate SettingModbus Device ID Setting Menu Map to Modbus Baud Rate SettingPage Modbus Parity Setting Modbus Mapping Mode SettingModbus Communication Protocol RegmodeCommand 08- Diagnostic Modbus CommandsCommand 03-Read Holding Registers Command 17- Report Slave ID Command 11- Get Com Event CounterCommand 12- Get Com Event Log Register Address Description Register Type Command 43- Read Device IDBase Radio Holding Registers Register Address DescriptionBase Radio On/Offline Transmitter Registers Base Radio Device Type RegistersBase Radio Device Status Registers Value Base Radio Device StatusTransmitter Holding Registers Device ID Mapping ModeRegister Mapping Mode Register AddressTransmitter Device Type Holding Registers Value Device TypeTransmitter Device Status Registers Alarm Condition WN571 onlySquare Root Function Value Transmitter Device StatusTechnical Specifications Overall Base Radio Dimensions Appendix a Navigating the Menus Appendix B Base Radio Menu Map Figure A- 1 Base Radio Menu MapAppendix C Modbus Register Definitions Page Page Page Honeywell