Honeywell XYR 5000 LINE manual Transmitter Device Type Holding Registers, Value Device Type

Page 39

00005 + (RF ID * 10)

Primary Sensor Value

32-Bit IEEE

00006 + (RF ID * 10)

Primary Sensor Value

Floating Point

00007 + (RF ID * 10)

Secondary Sensor Value

32-Bit IEEE

00008 + (RF ID * 10)

Secondary Sensor Value

Floating Point

00009 + (RF ID * 10)

Tertiary Sensor Value

32-Bit IEEE

00010 + (RF ID * 10)

Tertiary Sensor Value

Floating Point

Note If you have purchased any Wireless Differential Pressure Transmitters, please see the User Guide for specific Modbus holding register differences from those listed in the following sections.

6.5.3 Transmitter Device Type Holding Registers

The following are possible values for the Device Type holding registers. Note that the register is a 32-bit floating point value for Transmitters.

Value

Device Type

0

Acoustic Monitor Transmitter

1

RTD Transmitter

2

Pressure Transmitter

3

Dual 0-10V Input Transmitter

4

Dual 4-20mA Input Transmitter

5

Thermocouple Transmitter

6

Reserved

7

Level Sensor Transmitter

8

Split RTD Transmitter

9

Split Pressure Transmitter

10

Split Dual Thermocouple Transmitter

11

Differential Pressure Transmitter (100 IN. H20)

12

Split Differential Pressure Transmitter (100 IN. H20)

13

Differential Pressure Transmitter (300 IN. H20)

14

Split Differential Pressure Transmitter (300 IN. H20)

15

Differential Pressure Transmitter (25 PSID)

16

Split Differential Pressure Transmitter (25 PSID)

17

Differential Pressure Transmitter (100 PSID)

18

Split Differential Pressure Transmitter (100 PSID)

19

Differential Pressure Transmitter (300 PSID)

20

Split Differential Pressure Transmitter (300 PSID)

21

Reserved

22

Reserved

23

Gauge and Submersible Level Transmitters

24

Split Gauge and Submersible Level Transmitters

25

Advanced Development

26

Switch Input Transmitter

27

Switch Input Transmitter with Output Options

32

Image 39
Contents XYR 5000 Line 34-XY-25-05 Rev 08/06 Base Radio User GuidePage FCC Certification Base RadioRevision Notes ContactsTelephone Table of Contents Quare R OOT F Unction Table of Figures Overall Wiring SchematicUsing this Manual IntroductionAbout the Device Software Compatibility UnpackingQuick Start Overall Wiring SchematicPage Installation Mechanical InstallationBase Radio Positioning General Layout Electrical Specifications Electrical InstallationTerminal Block Labels Wiring RS-485 to the Base Radio Wiring Power to the Base RadioWiring RS-485 to the Base Radio Wiring the RS-485/232 Converter to the Base RadioUSB Driver Installation Wiring the RS-485/USB Converter to the Base RadioUSB Driver Un-installation Daisy-Chaining Multiple Base Radios to Single RS-485/PowerWiring the DB-9 RS-485 Cable to the Base Radio USB Converter’s Male DB-9 ConnectorDaisy-Chaining RS-485 to Multiple Base Radios Daisy-Chaining Power to Multiple Base RadiosDaisy-Chaining RS-485 to Multiple Base Radios Terminating Communications Wiring to the Base RadioHigh Gain Antenna Grounding the Base RadioGeneral Configuration Base Radio Displayed MessagesRead Only Sequence Read Only Sequence Overall Configuration Menu MapMenu Map to Password Setting Setting the User PasswordRF Channel Selection Configuring the RF CommunicationsRF Baud Rate Selection Menu Map to RF Baud Rate SettingHigh Rfid Setting High RF ID SettingModbus Baud Rate Setting Base Radio SetupMenu Map to Modbus Baud Rate Setting Modbus Device ID SettingPage Modbus Mapping Mode Setting Modbus Parity SettingRegmode Modbus Communication ProtocolModbus Commands Command 03-Read Holding RegistersCommand 08- Diagnostic Command 11- Get Com Event Counter Command 12- Get Com Event LogCommand 17- Report Slave ID Register Address Description Command 43- Read Device ID Base Radio Holding Registers Register Address Description Register TypeValue Base Radio Device Status Base Radio Device Type RegistersBase Radio Device Status Registers Base Radio On/Offline Transmitter RegistersRegister Address Device ID Mapping ModeRegister Mapping Mode Transmitter Holding RegistersValue Device Type Transmitter Device Type Holding RegistersValue Transmitter Device Status Alarm Condition WN571 onlySquare Root Function Transmitter Device Status RegistersTechnical Specifications Overall Base Radio Dimensions Appendix a Navigating the Menus Figure A- 1 Base Radio Menu Map Appendix B Base Radio Menu MapAppendix C Modbus Register Definitions Page Page Page Honeywell