Allstar Products Group ANSI/UL 325 owner manual Wiring Radio Receivers to the Terminal Strip

Page 15

CLOSE/OPEN PHOTO/EDGE (#s 9, 10, 12, & 13) can be continuous commands as noted on page 18. Labels identify the function of each of the terminals on the strip. See the TERMINAL STRIP Reference Chart on pages 17-19 related to each terminal number for an explanation of each of the inputs.

The transformer mounted in the GS4000 Control Box can be used power an accessory equipment item such as a radio receiver. This is a Class II transformer and is equipped with an internal fusible link. If this link is "blown" the transformer must be replaced. The transformer is powered whenever the GS4000 main power switch is ON. The maximum power that can be supplied by the transformer for an accessory equipment item is 20 VA or about 1 Ampere at 24VAC. This is usually sufficient to supply an accessory equipment item such as a radio receiver. Check the equipment for its power specifications.

THE MAXIMUM POWER DRAW FOR ALL AUXILIARY EQUIPMENT SHOULD NOT EXCEED 20 VA IF POWER IS SUPPLIED FROM THE GS4000 CONTROL BOARD. FAILURE TO OBSERVE THIS RESTRICTION WILL DAMAGE THE GS4000 CONTROL BOARD AND VOID ANY WARRANTY.

All auxiliary equipment devices must be of the type that require both sides of the transformer supplying power be "floating" and not grounded. The GS4000 auxiliary equipment low voltage power, terminals 1 & 2, is not referenced to ground. FAILURE

TO OBSERVE THIS RESTRICTION WILL DAMAGE THE GS4000 CONTROL BOARD AND VOID ANY WARRANTY.

C:INSTALLING THE OPERATOR

WIRING RADIO RECEIVERS TO THE TERMINAL STRIP

Radio Receivers MUST be of the 4 wire connection hook-up type (where the power input for the receiver is separate from the receiver’s output connection). The 4 wire version is necessary as the GS4000 control board 24 VAC output is not referenced to ground. See Figure 16 and the following text for proper connection.

FOUR WIRE RECEIVERS

Four wire receivers replace the "spade" terminals on the RECEIVER with 4 wires. These wires are typically color coded. The instructions with the receiver must be carefully followed to properly connect the receiver. For any 4 wire receiver, two of the wires will be for power input and two will be for the relay contacts. Connect the two wires for the power input to terminals 1 and 2 (24 VAC). Connect one of the two wires for the relay to terminal #4 (RADIO OPEN) or terminal #3 (ALTERNATE) depending on the function desired (see descriptions on the chart on pages 17 - 19) and the other wire to terminal #16 (COMMON) on the GS4000 terminal strip. See Figure 16 for connecting 4 wire receivers to the GS4000.

NOTE: IF THE 4 WIRE RECEIVER INSTRUCTIONS SHOW THAT TWO OF THE WIRES ARE OF THE SAME COLOR AND ARE COMMON CONNECTIONS INSIDE THE RECEIVER, YOU WILL NOT BE ABLE TO UTILIZE THIS RECEIVER AS WIRED WITH THE GS4000 CONTROL BOX. THE POWER SUPPLY CONNECTIONS MUST BE SEPARATE FROM THE RECEIVER OUTPUT CONNECTIONS WITH NO COMMON REFERENCES INSIDE THE RECEIVER.

Figure 16: Wiring 4-Wire Receiver

TERMINAL

 

STRIP

110120

 

WIRING A 3-BUTTON STATION

NOTE: THE GS4000 WILL OPERATE ONLY WITH A NORMALLY OPEN STOP BUTTON. THREE BUTTON STATIONS MAY BE ORDERED FROM ALLSTAR WITH THE STOP BUTTON CONFIGURED AS NORMALLY OPEN. See Figure 17 for instructions on wiring a Three Button Station.

16 COMMON

Figure 17: Wiring 3-Button Station

TERMINAL

STRIP

DRY CONTACT

RELAY OUTPUT

24VAC POWER FOR RECEIVER

WIRING FOUR-WIRE RECEIVER

6

5

4

3

2

1

OPEN

FREE EXIT

CONNECT TO:

RADIO OPEN

OR

ALTERNATE

24VAC

24VAC

OPEN

CLOSE

STOP

16 COMMON

8 STOP

7 CLOSE

6 OPEN

110121

WIRING 3-BUTTON STATION

WITH NORMALLY OPEN STOP

15

Image 15
Contents Gate Star WA R N I N G H I G H V O LTA G E Table of ContentsConnections for External Entrapment Prevention Sensors PRE-INSTALLATION NotesPinch Points Entrapment Zone Electric Gate Edge Gate System Design and Installation Safety Check ListDeath Gate System Design InstallationAS the Installer YOU are Responsible for Moving GatePreparing the Site Concrete PADPlacing the Vehicle Detector Loops Vehicle Detector Loop Blanking for Swing Gates Loop DiagramsElectrical Power Requirements Other Voltages and 3 Phase SystemsService Conduit Tools Required Installing the OperatorPlacing the GS4000 Mechanical Unit Installing the GS4000 ARMElectrical Hook UP Installing the GS4000 Control BOXAdditional Lightning Protection Connecting the AC Wiring Volt InstallationsWiring the Mechanical Unit to the Control BOX Right Hand and Left Hand InstallationBI-PARTING Wiring Accessory Equipment HOOK-UPBi-Parting Installation Limit & Motor Wiring Diagram Wiring Radio Receivers to the Terminal Strip Four Wire ReceiversWiring a 3-BUTTON Station Vehicle Detector Power Wiring a KEYPAD, Card Reader or Telephone Entry SystemConnecting the Vehicle Detector Wiring Vehicle DetectorsConnecting the Loop Wires Presetting the Motor Overload Sensitivity PotentiometersClose Photo SwitchClose Shadow LoopOPEN/CLOSE Push Button ENABLE/ Disable Patent no ,611,205 Setting the Limit SwitchesSetting the Switch Selectable Options NO-LOAD Test ModeTimer to Close Setting Applying Power to the GS4000Indicator Lamps Final Setting of the Close Timer Starting the Operator Final SettingsPRE Running Checklist Smart Setting Maximum RUN TimerFinal Setting of the Motor Overload Sensitivity Installation Notes for Auxiliary EquipmentTo the Owner/End User of Allstar’s GS4000 Precautions for Pedestrian Traffic or Residential AreasBasic Operational Guide Entrapment ZonePinch Points Entrapment Zone GS4000 Mechanical Unit Exploded View Mechanical Unit Exploded ViewARM KIT & Control BOX Exploded View & Parts Mechanical Unit Parts ListPhysical Drive Technical Specifications

ANSI/UL 325 specifications

Allstar Products Group is a prominent manufacturer in the realm of access control and safety products, and its commitment to quality is evidenced by its compliance with ANSI/UL 325 standards. These standards are essential for ensuring the safety and reliability of automatic gates and their related components, focusing on minimizing risks associated with entrapment and injury.

One of the key features of Allstar's ANSI/UL 325 compliant products is their advanced safety mechanisms. These include integrated sensing technology that detects the presence of objects or obstacles in the path of the gate, effectively preventing accidents. This safety technology often encompasses features such as photo eyes and edge sensors that can immediately halt or reverse the movement of a gate if an obstruction is detected.

Additionally, Allstar’s product range is notable for its robust design and durability. Built to withstand various environmental conditions, these products use high-quality materials that ensure longevity and reliability, meeting the stringent demands of both residential and commercial applications. The designs are also forward-thinking, incorporating user-friendly features that allow for easy installation and maintenance.

Another characteristic that sets Allstar apart is their integration of advanced technologies. Many of their products support smart technology, enabling users to control their gates through mobile applications or remote access systems. This integration allows for convenience and enhanced security, providing real-time alerts and status updates.

Allstar Products Group also emphasizes compliance to facilitate peace of mind for users. All their ANSI/UL 325 certified products undergo rigorous testing procedures to ensure they meet the stringent safety and performance requirements set forth by the American National Standards Institute and Underwriters Laboratories. This adherence to such standards not only assures consumers of reliability but also aligns with the industry’s best practices.

In conclusion, Allstar Products Group’s ANSI/UL 325 compliant products exemplify cutting-edge safety features, robust construction, and advanced technology integration. Their commitment to quality and safety ensures that customers can enjoy the benefits of automatic gate systems with confidence, knowing that they adhere to the highest safety standards in the industry.