Pelco DD53TC16-X Ack Action, Activate Aux, Current Reading, Reset Alert, Quick Programming Guide

Page 33
ACK ACTION

SPECTRA III

LANGUAGEENGLISH

<SYSTEM INFORMATION> <DISPLAY SETUP> <DOME SETTINGS>

ACK ALERT

RESET CAMERA

CYCLE CAMERA POWER

REBOOT SYSTEM

EXIT

ACK ACTION

Acknowledge action programs the alert label behavior after the alert condition has been acknowledged. The following settings are available for ACK ACTION:

ALWAYS ON

The alert label is displayed until alert conditions are cleared.

OFF 8 HRS

The alert label is turned off for 8 hours. Label returns after 8 hours

 

if the alert condition persists.

OFF 24 HRS

The alert label is turned off for 24 hours. Label returns after 24

 

hours if the alert condition persists.

OFF 48 HRS

The alert label is turned off for 48 hours. Label returns after 48

 

hours if the alert condition persists.

DOME SETTINGS

<CAMERA>

<MOTION> <POWER UP> <LINE SYNC> <PRESETS> <PATTERNS> <ZONES>

<TITLE TEXT> <ALERT> <CLEAR> <PASSWORD>

BACK

EXIT

ALERT

 

REPEAT

CONSTANT

ACK ACTION

ALWAYS ON

ACTIVATE AUX

NO

<CURRENT READING>

 

RESET ALERT

 

BACK

 

EXIT

 

CURRENT READING

TEMPERATURE

0°C

 

0°F

DEWPOINT

0°C

 

0°F

PRESSURE

0.0 PSIG

 

0.0 BAR

REFRESH

2

BACK

 

EXIT

 

ACTIVATE AUX

This setting activates an auxiliary when an alert condition exists. ACTIVATE AUX settings include the following:

NO (default)

Not activated.

1

An alert condition will close AUX 1.

2

An alert condition will close AUX 2.

CURRENT READING

The Current Reading menu displays the existing status of temperature, pressure, and dew point inside the dome system. An arrow displayed to the left of a menu item denotes that an alert condition exists.

An up arrow indicates the reading is over the threshold. A down arrow indicates the reading is below the threshold.

The high temperature alert occurs if the temperature is above 140°F (60°C). The low temperature alert occurs if the temperature is below -40°F (-40°C). The high pressure alert occurs if the pressure is above 11 PSIG.

The low pressure alert occurs if the pressure is below 1 PSIG.

The dew point (high humidity) alert occurs if the difference between the temperature and the dew point is less than or equal to 3°C.

NOTE: The normal operating temperature inside the unit will be greater than the temperature outside the back box due to the heat emitted by the system’s electronics.

RESET ALERT

Reset alert clears the alert condition and removes the alert label from the monitor. The system automatically checks internal conditions 60 seconds after reset. If conditions are still unaccept- able, the alert label reappears on the screen indicating further corrective action is required.

Quick Programming Guide

(See page 11)

C2446M-E (11/05)

33

Image 33
Contents Models DD53TC16 & DD53TC16-X Spectra III SeriesO P E R AT I O N / P R O G R A M M I N G C2446M-E11/05Page OPERATION/PROGRAMMING MANUAL MODELS DD53TC16 & DD53TC16-X16X LowLight COLOR TECHNOLOGY C2446M-E11/05 CONTENTS POWER UP Getting Started WELCOMEHow to Control HOW TO OPERATE YOUR DOME SYSTEMPresets AlarmsCM6700/CM6800 Accessing Main Menu PresetKBD200A/KBD300A Direct Mode Only CM9500MPT9500 KBD4000/KBD4002NET300/NET350/NET4001A WS5050QUICK START GUIDE - SYSTEM SETUP Preset FunctionPresets Press Iris Close to cancel selectionC2446M-E11/05 Quick Programming Guide LANGUAGESYSTEM INFORMATION Quick Programming Guide DISPLAY SETUPLabel Position Camera DOME SETTINGSAUTO FOCUS ZOOM LIMITAdvanced Camera Settings SHUTTER SPEEDAGC LIMIT Auto Iris Level AUTO IRISAuto Iris Peak Quick Programming GuideAUTO WHITE BALANCE AUTO SHARPNESSThere are two settings ON defaultVIDEO LEVEL BACKLIGHT COMPENSATION BLCQuick Programming Guide Backlight compensation is not activatedMotion Settings AUTO FLIPPROPORTIONAL PAN Park Action PARK TIMEDome goes to preset Quick Programming GuideLIMIT STOPS SCAN SPEEDTo program azimuth zero AZIMUTH ZERO2.Press Iris Open 3.Follow the directions displayed on the monitorPOWER UP ACTION Power UpQuick Programming Guide Line SyncPresets PresetAction Quick Programming Guide Patterns Zones Quick Programming Guide Title TextREPEAT AlertSystem Condition Alert MessageACK ACTION RESET ALERTACTIVATE AUX CURRENT READINGACK ALERT RESET CAMERA CYCLE CAMERA POWER ClearREBOOT SYSTEM EXIT DOME SETTINGS CAMERA BACK EXIT CLEAR RESTORE FACTORY DEFAULTS BACKQuick Programming Guide PasswordRESET CAMERA RESET, CYCLE POWER, REBOOTCYCLE CAMERA POWER REBOOT SYSTEMSOFTWARE/LANGUAGE FILE UPLOAD UPLOAD ICONUpload Icon SPECIFICATIONS DD53TC16DD53TC16-X REGULATORY NOTICES RADIO AND TELEVISION INTERFERENCEREVISION HISTORY Page Page Clovis, California 93612 USA USA & Canada World Headquarters 3500 Pelco WayTel 800/289-9100 Fax 800/289-9150 International Tel: 1-559/292-1981 Fax: 1-559/348-1120
Related manuals
Manual 42 pages 54.13 Kb