Product Information

February, 1999

BRIDGE CS-L2

 

The parameter assignments 'int_vector=12' and 'dpram_adr=0xD0000', with which the interrupt and DPRAM address range are set, agree with the default settings of the bridges and the DIP switches on the interface module CP5412-A1 which are already factory-set when delivered.

Caution:

If the L2AMPRO.INI configuration file is also saved on the memory card, this configuration takes precedence, i.e. a parameter file DOS_CONF.DAT existing in parallel and a bus circuit CP5412-A1 are ignored.

6.3 Parameter of configuration file L2AMPRO.INI for module IF964-DP

1) 1) Parameters for slot addressing

Parameter slot = Slot No. according to incrementing of SIMATIC M7-400 System setting: 5

Parameter modulbox = Module slot No. according to incrementing of SIMATIC M7-400 System setting: 1

The settings which correspond to the standard system configuration have been preselected for the coordinates of the IF964-DP and should therefore be used unchanged. Any changes to these parameters require knowledge of the slot addressing for SIMATIC M7, and incorrect entries may result in major system faults.

2) Bus parameters

 

Parameter

l2_ts =

Station No. on PROFIBUS-TM (decimal representation)

 

 

Must be identical to the station address in BATA from

 

 

BR_SYS.INI . If different addresses are entered, the

 

 

parameter 'l2_ts' from L2AMPRO.INI is used.

 

 

Note: The station addresses should be assigned without gaps

 

 

if possible. This may increase the performance.

Parameter

l2_hsa =

Highest station address on PROFIBUS-TM

 

 

Default setting: 32

 

 

Note: If the actual highest station address is entered exactly,

 

 

this may increase the performance. However, to retain

 

 

a reserve, it is also advisable when configuring to set a

 

 

higher station address than that actually present.

Parameter

l2_ttr =

Token rotation time (decimal representation)

 

 

Default setting: 90000

 

 

The default setting applies to a maximum of 10 active stations

on the PROFIBUS-TM bus. If more than 10 stations are present on the PROFIBUS-TM bus, the parameter must be calculated

Copyright © SIEMENS AG 1996-1999. All Rights Reserved.

S79220-A0978-A-05-7637

Page 16 of 20

Image 16
Contents Bridge CS-L2 VarScope Commissioning Startup by Commissioning TerminalBridge CS-L2 Esccopytm IBSBEDI.386 Update by Programming Device PG740 Removed Errors from V02.00 toRemoved Errors already with Extended Functions Installing the new M7 CPU Replacing the CP5412-A1 with an IF964-DP interface moduleSlot Module Interface Use for Configuration Box File Instructions on installing the CPU Limited operating performance Configuration of the bus connections L2AMPRO.INIParameter of configuration file BRSYS.INI Examples of standard system settingsParameter of configuration file DOSCONF.DAT for CP5412-A1 L2ts =L2hsa = L2ttr =Example of a configuration file DOSCONF.DAT # File for Installing TF/IHI DriverBRSYS.INI . If different addresses are entered, Example of a configuration file L2AMPRO.INI Parameter of configuration file SYSPAR.INI Diomaskeein =255 Diomaskeaus =255 SchlFunction Assignment of the Outputs Connector Pin Assignment IF961-DIOFunction Assignment of the Inputs Status display and error messages Operational modes switch key switch