Siemens 6DS2-510-0xx00-0xa0 manual Example of a configuration file L2AMPRO.INI

Page 17

Product Information

February, 1999

BRIDGE CS-L2

 

 

according to the following equation and entered:

 

l2_ttr = 9000 * [number of active PROFIBUS-TM stations].

 

Note: The factor 9000 in the equation only applies to a baud

 

rate of 1.5 MBaud.

All bus parameters are matched to a transmission rate of 1.5 MBaud.

Optimization requires detailed knowledge of the PROFIBUS standard, Part 1, DIN 19245. Selection of a different transmission rate is illegal, and may result in faulty functioning.

Example of a configuration file L2AMPRO.INI:

# ****************** Start L2AMPRO - INI file ********************

# ---> for Bridge CS-L2 (PROFIBUS) <---

# ****************** IF964 parameters ****************************

boardtyp

= IF964

slot

=

5

modulbox

=

1

# ****************** L2 bus parameters ***************************

l2_ts

= 32

l2_hsa

= 32

l2_baud_rate

= 7

l2_tsl

= 3000

l2_tqui

= 0

l2_tset

= 240

l2_max_tsdr

= 980

l2_min_tsdr

= 150

l2_ttr

= 90000

l2_g

= 30

# ****************** End L2AMPRO - INI file **********************

Caution:

If the bus circuit CP5412-A1 is connected in parallel to the IF964-DP module, the duplicate interrupts can lead to serious system errors.

Copyright © SIEMENS AG 1996-1999. All Rights Reserved.

S79220-A0978-A-05-7637

Page 17 of 20

Image 17
Contents Var Bridge CS-L2Scope Startup by Commissioning Terminal CommissioningBridge CS-L2 Esccopytm IBSBEDI.386 Removed Errors from V02.00 to Update by Programming Device PG740Removed Errors already with Replacing the CP5412-A1 with an IF964-DP interface module Extended Functions Installing the new M7 CPUSlot Module Interface Use for Configuration Box File Instructions on installing the CPU Limited operating performance L2AMPRO.INI Configuration of the bus connectionsExamples of standard system settings Parameter of configuration file BRSYS.INI L2ts = Parameter of configuration file DOSCONF.DAT for CP5412-A1 L2hsa = L2ttr =# File for Installing TF/IHI Driver Example of a configuration file DOSCONF.DATBRSYS.INI . If different addresses are entered, Example of a configuration file L2AMPRO.INI Diomaskeein =255 Diomaskeaus =255 Schl Parameter of configuration file SYSPAR.INIFunction Assignment of the Inputs Connector Pin Assignment IF961-DIOFunction Assignment of the Outputs Operational modes switch key switch Status display and error messages