Siemens 6DS2-510-0xx00-0xa0 manual Parameter of configuration file BRSYS.INI

Page 13

Product Information

 

February, 1999

BRIDGE CS-L2

 

 

6.1 Parameter of configuration file BR_SYS.INI

Parameter ADR=xxxx

Address of the Dual-Port-RAM of the TPM 478

 

C600 = standard system setting (hexadecimal)

Parameter DPR=xx

Address of the register of the TPM 478

 

C8 = standard system setting (hexadecimal)

Parameter RANGE=xx

Address range of all PROFIBUS-TM stations, which are

 

coupled over the BRIDGE CS-L2

 

Permissible range: 1-20 (hexadecimal)

 

Standard system setting: 20 (hexadecimal)

Parameter BATA=xxxx

Definition of the CS address of the BRIDGE in

 

hexadecimal representation

 

High byte:

Bus No. BA (hexadecimal)

 

Low byte:

Station No. TA on CS275 bus resp.

 

 

PROFIBUS-TM (hexadezimal)

Parameter REDUNDANZ=x

Redundancy operating mode of CS275 bus

 

x = 1: Redundancy on CS275 long-distance bus

(Standard)

x = 0: No redundancy on CS275 long-distance bus

Examples of standard system settings:

TA = 32, BA= 0, Range = 32, TPM478 Slot = 6, REDUNDANZ = 1

____________________________________________________

ADR=C600

DPR=C8

RANGE=20

BATA=0020

REDUNDANZ=1

____________________________________________________

Note:

The BATA must be set individually for each application. BRIDGE cannot start up with the default factory setting.

The range is set to its maximum size, i.e. 20h.

The parameters ADR and DPR correspond to the standard settings of BRIDGE CS-L2. In case you change these parameter, knowledge about the slot addresses of SIMATIC M7 is required since incorrect entries can lead to serious system errors.

If the ‘REDUNDANZ’ parameter is missing in the configuration file, the CS275 bus will operate redundantly.

Copyright © SIEMENS AG 1996-1999. All Rights Reserved.

S79220-A0978-A-05-7637

Page 13 of 20

Image 13
Contents Var Bridge CS-L2Scope Startup by Commissioning Terminal CommissioningBridge CS-L2 Esccopytm IBSBEDI.386 Removed Errors from V02.00 to Update by Programming Device PG740Removed Errors already with Replacing the CP5412-A1 with an IF964-DP interface module Extended Functions Installing the new M7 CPUSlot Module Interface Use for Configuration Box File Instructions on installing the CPU Limited operating performance L2AMPRO.INI Configuration of the bus connectionsExamples of standard system settings Parameter of configuration file BRSYS.INIL2ts = Parameter of configuration file DOSCONF.DAT for CP5412-A1L2hsa = L2ttr =# File for Installing TF/IHI Driver Example of a configuration file DOSCONF.DATBRSYS.INI . If different addresses are entered, Example of a configuration file L2AMPRO.INI Diomaskeein =255 Diomaskeaus =255 Schl Parameter of configuration file SYSPAR.INIFunction Assignment of the Outputs Connector Pin Assignment IF961-DIOFunction Assignment of the Inputs Operational modes switch key switch Status display and error messages