2.3 Procedure for Update V01.05 to V01.06

2.3.1 Update by Commissioning Terminal

You will find the files listed below in the directory A:\UPDATE.106 on the UPDATE diskette delivered to you. Copy these files to the directory ‘C:\ASBEDIEN’ on your Commissioning Terminal PC or into the current working directory (e.g. C:\TEMP is specified in ASBEDIEN.PIF).

On the Commissioning Terminal PC connected to the BRIDGE CS-L2, start the program ASBEDIEN.exe (via ASBEDIEN.PIF under Windows, so that the program runs in full screen mode and without a screen saver).

Now, in command mode, copy the files previously backed up to the PC to the memory card in the BRIDGE CS-L2 in the following sequence:

<ESC>COPY_TM IBS_BEDI.386

resp. <ESC>COPY_TM C:\ASBEDIEN\IBS_BEDI.386

<ESC>COPY_TM STARTER.386

resp. <ESC>COPY_TM C:\TEMP\STARTER.386

<ESC>COPY_TM BRI_BEDI.386

...

<ESC>COPY_TM BRIDGE.386

 

<ESC>COPY_TM ITASK.EXE

 

<ESC>COPY_TM RMOS.INI

 

<ESC>COPY_TM L2AMPRO.INX

 

<ESC>COPY_TM VERSION.TXT

 

If necessary, the following file should be modified in accordance with this product information.

BR_SYS.INI settings for non-redundant operation of the CS 275 bus

After a successful transfer, exit ASBEDIEN (with Alt-X).

Now perform the following two steps:

1)Initiate a reboot of the BRIDGE CS-L2 (reset or off/on)

2)Install the new terminal program ASBEDIEN V1.06 to your PC from the diskette included with your delivery (IBS tools).

Attention: The data transfer was only successful if the command COPY_TM ends without error messages, and without any manual intervention (e.g. termination with ESC). In the case of errors, the copy procedure must be repeated.

If problems occur during the data transfer (frequent terminations), we recommend the following procedure:

If the first file (IBS_BEDI.386) was transferred without errors, the BRIDGE CS-L2 can be rebooted with the new emergency utility disk (press MRES during switch-on). Together with the new ASBEDIEN V1.06, an error free transfer can be expected.

Before the next RESET, the files IBS_BEDI.386 and STARTER.386 must be successfully transferred.

Copyright © SIEMENS AG 1996-1999. All Rights Reserved.

S79220-A0978-A-05-7637

Page 5 of 20

Image 5
Contents Var Bridge CS-L2Scope Startup by Commissioning Terminal CommissioningBridge CS-L2 Esccopytm IBSBEDI.386 Removed Errors from V02.00 to Update by Programming Device PG740Removed Errors already with Replacing the CP5412-A1 with an IF964-DP interface module Extended Functions Installing the new M7 CPUSlot Module Interface Use for Configuration Box File Instructions on installing the CPU Limited operating performance L2AMPRO.INI Configuration of the bus connectionsExamples of standard system settings Parameter of configuration file BRSYS.INIL2ts = Parameter of configuration file DOSCONF.DAT for CP5412-A1L2hsa = L2ttr =# File for Installing TF/IHI Driver Example of a configuration file DOSCONF.DATBRSYS.INI . If different addresses are entered, Example of a configuration file L2AMPRO.INI Diomaskeein =255 Diomaskeaus =255 Schl Parameter of configuration file SYSPAR.INIFunction Assignment of the Inputs Connector Pin Assignment IF961-DIOFunction Assignment of the Outputs Operational modes switch key switch Status display and error messages