Error Codes

The L100 series inverters will trip on over-current, over-voltage, and under-voltage to protect the inverter. The motor output turns OFF, allowing the motor to free-run to a stop. Press the Stop/Reset key to reset the inverter and clear the error.

Basic Error Codes

Error

Name

Probable Cause(s)

Code

 

 

 

 

 

 

 

 

E01

Over current event while

• Inverter output was short-circuited

at constant speed

• Motor shaft is locked

 

 

• Load is too heavy

E02

Over current event during

• A dual-voltage motor is wired

deceleration

incorrectly

 

 

Note: The L100 will over current trip

E03

Over current event during

at nominally 200% of rated current

 

acceleration

 

E04

Over current event for

• DC braking power(A_54) set too

other conditions

high

 

 

• Current transformer / noise error

 

 

 

E05

Overload protection

• Motor overload is detected by the

 

 

electronic thermal function

E07

Over voltage protection

• DC bus voltage exceeds a threshold,

 

 

due to regenerative energy from motor

E08

EEPROM error

Built-in EEPROM memory experi-

 

 

enced noise, high temperature, etc.

E09

Under-voltage error

• DC bus voltage decreased enough to

 

 

cause a control circuit fault

E11

CPU error

Built-in CPU had internal error

 

 

E22

 

 

 

 

 

E12

External trip

• [EXT] input signal detected

 

 

E13

USP (Unattended Start

• When (USP) was enabled, an error

Protection)

occurred when power was applied

 

 

while a Run signal was present

 

 

 

E14

Ground fault

• A ground fault was detected

 

between the inverter output and the

 

 

motor. This feature protects the

 

 

inverter, and does not protect humans.

 

 

 

E15

Input over-voltage

• Input voltage was higher than the

 

specified value, 60 sec. after powerup

 

 

 

 

 

E21

Inverter thermal trip

• Inverter internal temperature is

 

above the threshold

 

 

 

 

 