| Default |
|
Func. |
| Name / Description | Value | Set | |
Code |
| Value | |||
|
|
| |||
|
|
|
|
| |
|
|
|
| ||
|
|
|
| ||
B_12 | Level of electronic thermal setting | Rated |
| ||
|
|
|
| current of |
|
|
|
|
| each inverter |
|
|
|
|
| ||
B_13 | Electronic thermal characteristic | 01 / 01 / 00 |
| ||
| • 00 Reduced torque | • 01 Const. torque |
|
| |
|
|
|
| ||
B_21 | Overload restriction operation mode | 01 |
| ||
| • 00 Disabled |
|
|
| |
| • 01 Enabled for accel and constant |
|
| ||
| speed |
|
|
| |
| • 02 Enabled for constant speed only |
|
| ||
|
|
|
| ||
B_22 | Overload restriction setting | Rated |
| ||
|
|
|
| current |
|
|
|
|
| x 1.25 |
|
|
|
|
| ||
B_23 | Deceleration rate at overload restriction | 1.0 |
| ||
|
|
|
| ||
B_31 | Software lock mode selection | 01 |
| ||
| • 00 |
|
| ||
| edits |
|
|
| |
| • 01 |
|
| ||
| edits (except F_01 and |
|
| ||
| parameters) |
|
|
| |
| • 02 No access to edits |
|
| ||
| • 03 No access to edits except F_01 and |
|
| ||
|
|
| |||
|
|
|
| ||
B_32 | Reactive current setting | 58% rated |
| ||
| Note: For Japanese | current |
| ||
|
|
| |||
|
|
| |||
|
|
|
| ||
B_81 | [FM] terminal analog meter adjustment | 80 |
| ||
|
|
|
| ||
B_82 | Start frequency adjustment | 0.5 |
| ||
|
|
|
| ||
B_83 | Carrier frequency setting | 5.0 / 5.0 / |
| ||
|
|
|
| 12.0 |
|
|
|
|
| ||
B_84 | Initialization mode (parameters or trip | 00 |
| ||
| history) |
|
|
| |
| • | 00 Trip history clear |
|
|
|
| • | 01 Parameter initialization |
|
| |
|
|
|
| ||
B_85 | Country code for initialization | 01 / 02 / 00 |
| ||
| • 00 Japan version | • 01 Europe |
|
| |
| version |
|
|
| |
| • 02 US version |
|
|
| |
|
|
|
| ||
B_86 | Frequency scaling conversion factor | 1.0 |
| ||
|
|
|
|
| |
B_87 | STOP key enable |
| 00 |
| |
| • 00 Enable | • 01 Disable |
|
| |
|
|
|
|
|
|
18