Siemens 6DS2-510-0xx00-0xa0 manual Startup by Commissioning Terminal

Page 3

Product Information

February, 1999

BRIDGE CS-L2

 

2 Commissioning

The Memory Card contains the entire system software for the Bridge (version V02.01) .

To perform an upgrade or update from diskette, a BRIDGE CS-L2 memory card must be available.

The upgrade procedure is performed offline with a PC or a programming device having a compatible MC interface (e.g. PG740).

The update procedure is performed either from the IBS terminal (online) or from a programming device having a compatible MC interface (e.g. PG740).

A description of the upgrade procedure is provided under heading 2.2 in this document, of the update procedure under heading 2.3 .

Caution: The file RM3_PC1.SYS on the memory card must never be deleted, moved or overwritten, as this would mean that the memory card would no longer be bootable!

2.1 Startup by Commissioning Terminal

Additional the IBS-Tool diskette contains your local tool in the directory ASBEDIEN. Install this on your PC to be used for commissioning of the BRIDGE CS-L2 according to the installation instructions in the document file ASBEDI_E.DOC in the directory ASBEDIEN, and connect your PC to the serial commissioning interface of your BRIDGE CS-L2 via a serial interface.

For operation under Windows 3.1, a PIF file is delivered with the software. This contains the following settings: run in full screen mode, exclusive foreground execution, foreground priority very high.

For operation under Windows 95, the following setting should be specified: idle time activity very low; no screen saver.

Using your "Commissioning terminal" installed in this manner and the commands of the ASBEDIEN input program you can access all data on the memory card inserted in the BRIDGE CS-L2.

Read the parameter files which have to be processed to enable parameterization from the memory card into a file on your PC using the command "COPY_PC ...". You can modify this file on your PC according to your system configuration using the ASCII editors which can be executed under DOS, and then write them back onto your memory card using the ASBEDIEN command "COPY_TM ...".

Note:

Before starting the UPGRADE/UPDATE activities, please ensure that a current backup of any files that are to be modified exists. This will allow the previous software version to be restored in the even of unforeseen circumstances. The files on the memory card are not write protected, so care should be taken when accessing the memory card.

To back up the files from the memory card to your archive, use the ASBEDIEN command "COPY_PC ...".

Copyright © SIEMENS AG 1996-1999. All Rights Reserved.

S79220-A0978-A-05-7637

Page 3 of 20

Image 3
Contents Var Bridge CS-L2Scope Startup by Commissioning Terminal CommissioningBridge CS-L2 Esccopytm IBSBEDI.386 Removed Errors from V02.00 to Update by Programming Device PG740Removed Errors already with Replacing the CP5412-A1 with an IF964-DP interface module Extended Functions Installing the new M7 CPUSlot Module Interface Use for Configuration Box File Instructions on installing the CPU Limited operating performance L2AMPRO.INI Configuration of the bus connectionsExamples of standard system settings Parameter of configuration file BRSYS.INIL2ttr = Parameter of configuration file DOSCONF.DAT for CP5412-A1L2ts = L2hsa =# File for Installing TF/IHI Driver Example of a configuration file DOSCONF.DATBRSYS.INI . If different addresses are entered, Example of a configuration file L2AMPRO.INI Diomaskeein =255 Diomaskeaus =255 Schl Parameter of configuration file SYSPAR.INIConnector Pin Assignment IF961-DIO Function Assignment of the OutputsFunction Assignment of the Inputs Operational modes switch key switch Status display and error messages