6.2 Parameter of configuration file DOS_CONF.DAT for CP5412-A1
The configuration file DOS_CONF.DAT includes the
Bus parameters:
Parameter | l2_ts = | Station No. on |
|
| Default setting: 32 |
|
| Must be identical to the station address in BATA from |
|
| BR_SYS.INI. If different addresses are entered, the |
|
| parameter 'l2_ts' from DOS_CONF.DAT is used. |
|
| Note: The station addresses should be assigned without gaps |
|
| if possible. This may increase the performance. |
Parameter | l2_hsa = | Highest station address on |
|
| (decimal representation) |
|
| Default setting: 32 |
|
| Note: If the actual highest station address is entered exactly, |
|
| this may increase the performance. However, to retain |
|
| a reserve, it is also advisable when configuring to set a |
|
| higher station address than that actually present. |
Parameter | l2_ttr = | Token rotation time (decimal representation) |
|
| Default setting: 90000 |
|
| The default setting applies to a maximum of 10 active stations |
|
| on the |
|
| on the |
|
| according to the following equation and entered: |
|
| l2_ttr = 9000 * [number of active |
|
| Note: The factor 9000 in the equation only applies to a baud |
|
| rate of 1.5 MBaud. |
All bus parameters are matched to a transmission rate of 1.5 MBaud.
Optimization requires detailed knowledge of the PROFIBUS standard, Part 1, DIN 19245. Selection of a different transmission rate is illegal, and may result in faulty functioning. The bus parameters are described in the SINEC Manual
Attention: Apart from the bus parameters, the configuration file DOS_CONF.DAT also contains system parameters for handling BRIDGE
Note: | The BUS address (BA) cannot be configured in DOS_CONF.DAT . |