Siemens 6DS2-510-0xx00-0xa0 Parameter of configuration file DOSCONF.DAT for CP5412-A1, L2ts =

Page 14

Product Information

February, 1999

BRIDGE CS-L2

 

6.2 Parameter of configuration file DOS_CONF.DAT for CP5412-A1

The configuration file DOS_CONF.DAT includes the PROFIBUS-TM bus parameters. A specification of slot coordinates is not necessary.

Bus parameters:

Parameter

l2_ts =

Station No. on PROFIBUS-TM (decimal representation)

 

 

Default setting: 32

 

 

Must be identical to the station address in BATA from

 

 

BR_SYS.INI. If different addresses are entered, the

 

 

parameter 'l2_ts' from DOS_CONF.DAT is used.

 

 

Note: The station addresses should be assigned without gaps

 

 

if possible. This may increase the performance.

Parameter

l2_hsa =

Highest station address on PROFIBUS-TM

 

 

(decimal representation)

 

 

Default setting: 32

 

 

Note: If the actual highest station address is entered exactly,

 

 

this may increase the performance. However, to retain

 

 

a reserve, it is also advisable when configuring to set a

 

 

higher station address than that actually present.

Parameter

l2_ttr =

Token rotation time (decimal representation)

 

 

Default setting: 90000

 

 

The default setting applies to a maximum of 10 active stations

 

 

on the PROFIBUS-TM bus. If more than 10 stations are present

 

 

on the PROFIBUS-TM bus, the parameter must be calculated

 

 

according to the following equation and entered:

 

 

l2_ttr = 9000 * [number of active PROFIBUS-TM stations].

 

 

Note: The factor 9000 in the equation only applies to a baud

 

 

rate of 1.5 MBaud.

All bus parameters are matched to a transmission rate of 1.5 MBaud.

Optimization requires detailed knowledge of the PROFIBUS standard, Part 1, DIN 19245. Selection of a different transmission rate is illegal, and may result in faulty functioning. The bus parameters are described in the SINEC Manual

TF5412/MS-DOS, WINDOWS (C79000-G8976-C031).

Attention: Apart from the bus parameters, the configuration file DOS_CONF.DAT also contains system parameters for handling BRIDGE CS-L2 communication tasks. Unauthorized modifications to these usually result in major faults in the BRIDGE CS-L2.

Note:

The BUS address (BA) cannot be configured in DOS_CONF.DAT .

Copyright © SIEMENS AG 1996-1999. All Rights Reserved.

S79220-A0978-A-05-7637

Page 14 of 20

Image 14
Contents Bridge CS-L2 VarScope Commissioning Startup by Commissioning TerminalBridge CS-L2 Esccopytm IBSBEDI.386 Update by Programming Device PG740 Removed Errors from V02.00 toRemoved Errors already with Extended Functions Installing the new M7 CPU Replacing the CP5412-A1 with an IF964-DP interface moduleSlot Module Interface Use for Configuration Box File Instructions on installing the CPU Limited operating performance Configuration of the bus connections L2AMPRO.INIParameter of configuration file BRSYS.INI Examples of standard system settingsL2hsa = Parameter of configuration file DOSCONF.DAT for CP5412-A1L2ts = L2ttr =Example of a configuration file DOSCONF.DAT # File for Installing TF/IHI DriverBRSYS.INI . If different addresses are entered, Example of a configuration file L2AMPRO.INI Parameter of configuration file SYSPAR.INI Diomaskeein =255 Diomaskeaus =255 SchlFunction Assignment of the Inputs Connector Pin Assignment IF961-DIOFunction Assignment of the Outputs Status display and error messages Operational modes switch key switch