32 en Input and Output Ports | Conettix Communications Receiver/ | |
Gateway | ||
| ||
|
| |
|
|
Warning!
!Operating the input as an analog input between 0.5 V and 5 V might cause abnormal results. This input state is not defined and might change expected results.
i | Notice! | |
Reverse configuration is not for use in UL Listed applications. | ||
|
10.1.2Automation Link Monitoring (COM3) through CPU Programmable Output
Ports
The output connections on the I/O port have an open collector transistor output that can activate an external sounder or light if the automation system fails.
i | Notice! |
|
Configure external devices using the specifications listed in the table below. Outputs are not | ||
| verified by UL. |
|
|
|
|
|
|
|
| Radionics D6615 CPU Terminator Card | Bosch D6615 CPU Terminator C |
|
|
|
| Solid state output provides a current sink to | Solid State output provides a current sink to |
| common | common |
|
|
|
| Maximum load is 20 mA | Maximum load is 75 mA |
|
|
|
| Vsat @ 1 mA = 0.5 VDC | Vsat @ 10 mA = 0.5 VDC |
|
|
|
| Vsat @ 10 mA = 3.0 VDC | Vsat @ 25 mA = 1.0 VDC |
|
|
|
| Maximum voltage = 30 VDC | Vsat @ 50 mA = 2.5 VDC |
|
|
|
|
| Maximum voltage = 30 VDC |
|
|
|
| Table 10.1: Terminator Card Configuration |
|
2012.11 08 4998122704 | Installation and Operation Guide | Bosch Security Systems, Inc. |