GE HE500TIU103, IC300TIU201, IC300TIU101, HE500TIU100, HE500TIU050 manual Getting Started, Self-Test

Page 34

CH. 7: GETTING STARTED

06 Apr 2000

PAGE 35

 

 

GFK-1819

 

CHAPTER 7: GETTING STARTED

7.1Self-Test

Power up the unit with the UP and ENTER keys pressed at the same time. The unit enters a self-test mode. The self-test consists of the following four checks:

7.1.1Contrast Band

This test allows the user to set the lower and upper limits of contrast. Adjust the lower limit using the UP or DOWN key and press Enter when done. Do the same for the upper limit.

WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max FE).

7.1.2Display Test

The display test continuously blinks all pixels on (black) to off. Look for any pixels stuck on or off. Exit this test by pressing and holding any key for approximately two seconds.

7.1.3Keyboard Test

As each key is pressed, an indication *** appears above that key. In the case of units with a numeric keypad, press the key and a message appears indicating the key press. Check for keys indicating multiple presses or not reporting presses. Exit this test by pressing and holding any key for approximately two seconds.

7.1.4RAM Test

Test either segment 0000 or segment 1000 (on the TIU100/110) of the RAM. The segment 1000 test performs a base 3 repeating test. This test detects shorted address lines and damaged memory bits. The segment 0000 test performs a Read-Modify-Write test on each byte of RAM, detecting damaged memory bits. Exit this test by selecting DONE.

7.1.5Serial Loop-back Tests

Tests the PC port and the Serial Port in each of it’s three modes for serial loop-back. Pre-made plugs are required to link the pins of a particular port. This takes the following form:

Table 7.1 Loop-back Test Plugs

Port Tested

Product

Type of Connector

Pins to Short

PC (J2)

TIU100/110

Pin male D link connector

pin 2 to pin 3

RS-232 (J3)

TIU100/110

13-pin phoenix connection

pin 6 to pin 8

RS-422/485 (J3)

TIU100/110

13-pin phoenix connection

pin 2 to pin 4 and pin 3

 

 

 

to pin 5.

Current Loop

TIU100/110

13-pin phoenix connection

pin 1 to 9, pin 10 to 11

 

 

 

and pin 12 to 7

PC

TIU050/101/102/1

Pin male D link connector

pin 2 to pin 3

 

03/112/113/20X

 

 

RS-232

TIU050/101/102/1

8-pin phoenix connection

Pin 5 to pin 7

 

03/112/113/20X

 

 

RS-422/485

TIU050/101/102/1

8-pin phoenix connection

Pin 1 to pin 3, Pin 2 to

 

03/112/113/20X

 

pin 4

NOTE: current loop in not installed on standard models, as such a standard model will fail the current loop-back test. Current Loop is not an option on the TIU050/20X.

After starting the test, the OK counter begins to count up. Exit this test by selecting DONE.

Image 34
Contents Operator Station Hardware Manual Preface Declaration of EMC Conformity About Programming Examples06 Apr Table of Contents Networks Scope IntroductionOperator Station OS Product Line Fanuc Channels CH Introduction Equipment Needed CH Introduction 06 Apr GFK-1819 Technical Specifications Parameter Conditions Min Typical Max UnitsFirmware Upgrade GFK-1819 Upgrade Revision Software & FirmwareSoftware Upgrade Scope06 Apr GFK-1819 CH Introduction TIU050 TIU050 Contrast AdjustmentCH.2 TIU050 06 Apr GFK-1819 Configuration Bank 1 TIU050 Configuration of the RS-485 Port06 Apr CH TIU050 GFK-1819 TIU050 Ports TIU050 Dimensions TIU050 Cutout06 Apr CH TIU050 GFK-1819 TIU10X Contrast Adjustment CH TIU100/101/102/103 06 Apr GFK-181906 Apr CH.3 TIU100/101/102/103 GFK-1819 Tiux Rear View Rear View of TIU100/101/102 TIU100 Ports1 TIU10X Configuration of the RS-485 Port Automation Equipment Port Receive Transmit LEDsTIU10X Dimensions 06 Apr CH.3 TIU100/101/102/103 GFK-1819TIU11X Contrast Adjustment CH TIU110/111/112/113 06 Apr GFK-181906 Apr CH TIU110/111/112/113 GFK-1819 TIU11X Rear View Rear View of TIU11X TIU110 PortsSerial P ort TIU11X Dimensions 1 TIU11X Configuration of the RS-485 Port06 Apr CH TIU110/111/112/113 GFK-1819 CH TIU200/201/202/203 06 Apr GFK-1819 Front View of TIU20X TIU20X Button Selection ActionsRear View of TIU20X TIU20X Ports Automated Equipment Serial PortLED’s flash when the TIU20X Is communicating with the AE TIU20X Dimensions 1 TIU20X Configuration of the RS-485 Port06 Apr CH TIU200/201/202/203 GFK-1819 Recommended Automation Equipment Communication Cables CommunicationsPC to Operator Station Communications RS-232 ConnectionGFK-1819 RS-422/485 Four-Wire TIU110/10006 Apr GFK-1819 RS-485 Two-Wire GFK-1819 Current Loop + SRGetting Started Self-TestGFK-1819 Updating the Protocol Select Update TIU Protocol from the File menuProtocol Name Software Revision Terminal Type Scope Controller Area Network can Overview NetworksCsCAN Network Overview DeviceNet Features DeviceNet OverviewDeviceNet Protocol DeviceNet OperationGFK-1819 Can Wiring Rules Can Network CablingProfibus Wiring 06 Apr GFK-1819 ProfibusE term in atio n H m Smartstack  Installing and Removing a SmartStack ModuleInstalling SmartStack Modules Removing SmartStack ModulesCH Smartstack