American Dryer Corp ID-120 installation manual Steam Information

Page 31

H. STEAM INFORMATION

It is your responsibility to have ALL plumbing connections made by a qualified professional to assure that the gas plumbing installation is adequate and conforms to local and state regulations or codes.

IMPORTANT: Failure to comply with the requirements stipulated in this manual can result in component failure, which will VOID THE WARRANTY.

NOTE: This dryer is manufactured with a pneumatic (piston) damper system, which requires an external supply of clean, dry, regulated air of 0.75 CFH @ 80 PSI +/- 10 PSI (5.51 bars +/-

0.69bars). Refer to Steam DamperAir System Connections, item 4 (page 29).

1.Steam Coil PH Level

The normal PH level for copper type steam coils must be maintained between a value of 8.5 to 9.5. For steel type steam coils the PH level must be maintained between a value of 9.5 to 10.5. These limits are set to limit the acid attack of the steam coils.

IMPORTANT: Coil failure due to improper PH level will VOID THE WARRANTY.

2.Steam Requirements - High Pressure

Inlet -------- 1-1/4” supply line connection -- qty. one (1) at top manifold. Return ----- 1-1/4” return line connection --- qty. one (1) at bottom manifold.

OPERATING STEAM PRESSURE

MAXIMUM

125 psig

862 kPa

MINIMUM

100 psig*

689 kPa

HEAT INPUT (NORMAL LOAD)

13 Bhp

 

 

 

CONSUMPTION (APPROXIMATE)

450 lbs/hr

204 kg/hr

 

 

 

Shaded areas are stated in metric equivalents

Minimum operating pressure for optimum results.

3.Installation Instructions

To insure an adequate supply of steam is provided, be sure that the steam lines and steam return lines are sized and laid out as stipulated in this manual. Inadequate steam lines and steam return lines or improper steam plumbing will result in poor performance and can cause component failure. Clean, dry steam must be provided to the dryer.

IMPORTANT: Steam coil failure due to water hammer by wet steam will VOID THE WARRANTY.

27

Image 31
Contents ID-120 Retain This Manual In a Safe Place For Future Reference Foryour Safety Page Table of Contents Section Procedure for Functional Check of Replacement Receiving and Handling Important InformationWhat to do if YOU Smell GAS Safety PrecautionsStandards Specifications GAS and Steam SPECIFICATIONS/COMPONENT IdentificationSpecifications IDG-120 Gas IDS-120 Steam Component Identification Dryer Rear View Illus. No Location Requirements Installation ProceduresUNPACKING/SETTING UP Lift the console module off the dryer base C Dryer Enclosure Requirements Fresh AIR Supply Requirements General Exhaust Ductwork Information Exhaust RequirementsPage Ducting Horizontal and Vertical Page Page Electrical Requirements Electrical InformationID-120 Gas and Steam Only Electrical Connections GAS Information Type of GAS Page Page Bars. Refer to Steam DamperAir System Connections, item 4 Steam InformationPage COM Pressed AIR Pressure AIR Supply Page Preparation for OPERATION/START-UP Compressed AIRPreoperational Tests Page Basket Tumbler Coating Operating Instructions Shut Down Instructions Service SERVICE/PARTS InformationParts Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyPage Cleaning Routine MaintenanceSteam Dryers Lubrication AdjustmentsSectionvii Reversing Timer SPIN/DWELLADJUSTMENTSProcedure for Functional Check Replacement Components Page Data Label Datalabel InformationSerial Number P O R T a N T For Phase 7 ModelsFor Dual Timer Models ADC113330 1 08/31/01-25