a. Gas and Steam Models Only
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.
B.Circuit breakers are
C.Circuit breakers for
SERVICE |
| WIRE | APPROX. | MINIMUM | FUSING | CIRCUIT | ||
PHASE | AMP DRAW |
| ||||||
Dual Element | ||||||||
VOLTAGE | SERVICE | WIRE SIZE | BREAKER | |||||
|
|
| 60 Hz | 50 Hz |
| Time Delay |
| |
120 | 1 ø | 2 | 13.0 | — | * | 20 | 2 0 | |
208 | 1 ø | 2 | 7.6 | — | * | 1 5 | 15 | |
220 | 1 ø | 2 | 7.3 | 8.6 | * | 1 5 | 15 | |
230 | 1 ø | 2 | — | 8.0 | * | 1 5 | 15 | |
240 | 1 ø | 2 | 7.0 | — | * | 1 5 | 15 | |
208 | 3ø | 3 | 4.7 | — | * | 1 5 | 15 | |
230 | 3ø | 3 | — | 4.7 | * | 1 5 | 15 | |
240 | 3ø | 3 | 4.9 | — | * | 1 5 | 15 | |
380 | 3ø | 3 | 2.9 | — | * | 1 5 | 15 | |
380 | 3ø | 4** | — | 3.1 | * | 15 | 15 | |
400 | 3ø | 4** | — | 3.2 | * | 15 | 15 | |
416 | 3ø | 4** | — | 3.1 | * | 15 | 15 | |
460/480 | 3ø | 3 | 2.8 | — | * | 15 | 15 | |
* AWG Stranded Wire Type - size wire as per National Electrical Code or local codes. | ||||||||
** |
|
|
|
|
| 5/26/05 |
b. Electric Models Only
ALL electrically heated dryers must be connected to the electric service shown on the dryer’s data label. The connecting wires must be properly sized to handle the rated current.
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.
B.Circuit breakers are
C.Circuit breakers for
SERVICE VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
60 Hz | 50 Hz |
|
|
MINIMUM WIRE SIZE
FUSING
Dual Element Time Delay
CIRCUIT BREAKER
|
|
| 30 kW |
|
|
| |
208 | 3ø | 3 | 9 1 | — | * | 125 | 125 |
230 | 3ø | 3 | — | 8 3 | * | 125 | 125 |
240 | 3ø | 3 | 7 9 | — | * | 100 | 100 |
380 | 3ø | 3 | 48 | — | * | 60 | 6 0 |
380 | 3ø | 4** | — | 54 | * | 70 | 70 |
400 | 3ø | 4** | — | 51 | * | 70 | 70 |
416 | 3ø | 4** | — | 50 | * | 70 | 70 |
460 | 3ø | 3 | 40 | — | * | 50 | 50 |
480 | 3ø | 3 | 39 | — | * | 50 | 50 |
575 | 3ø | 3 | 33 | — | * | 50 | 50 |
|
|
| 36 kW |
|
|
| |
208 | 3ø | 3 | 108 | — | * | 150 | 150 |
230 | 3ø | 3 | — | 98 | * | 125 | 125 |
240 | 3ø | 3 | 94 | — | * | 125 | 125 |
380 | 3ø | 3 | 58 | — | * | 80 | 80 |
380 | 3ø | 4** | — | 63 | * | 80 | 80 |
400 | 3ø | 4** | — | 60 | * | 80 | 80 |
416 | 3ø | 4** | — | 58 | * | 80 | 80 |
460 | 3ø | 3 | 48 | — | * | 60 | 60 |
480 | 3ø | 3 | 46 | — | * | 60 | 60 |
* AWG Stranded Wire Type - size wire as per National Electrical Code or local codes. | |||||||
** |
|
|
|
|