b. Electric Models Only
MLE-75 (ELECTRIC)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME . When ordering, specify exact voltage.
NOTES: A. Fuse ratings are dual element, time delay, current limiting, class RK1 or RK5 ONLY.
B.Circuit breakers are thermal/magnetic (industrial) motor curve type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.
C.Circuit breakers for
APPLIED VOLTAGE/PHASE
KW
20
24
30
33
36
40
APPROX. AMP DRAW
208/1ø (60 Hz) | 240/1ø (60 Hz) | 208/3ø (60 Hz) | 240/3ø (50/60 Hz) | 380/3ø (50 Hz) | 416/3ø (50 Hz) | 460/3ø (60 Hz) |
104 | 90 | 33 | ||||
|
|
|
|
|
|
|
72 | 63 | 36 | 33 | |||
|
|
|
|
|
|
|
88 | 77 | 45 | 41 | |||
|
|
|
|
|
|
|
53 | ||||||
|
|
|
|
|
|
|
105 | 92 | 53 | 48 | |||
59 | ||||||
|
|
|
|
|
|
|
IMPORTANT: Figures shown are for
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the left side panel/wall area behind the control door. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.
IMPORTANT: The wire size must be properly sized to handle the related current.
WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.
IMPORTANT: