Maytag W10131619A If using a power supply cord, If your outlet looks like this

Page 6

A 4-wire power supply connection must be used when the appliance is installed in a location where grounding through the neutral conductor is prohibited. Grounding through the neutral is prohibited for (1) new branch-circuit installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where local codes prohibit grounding through the neutral conductors.

If using a power supply cord:

Use a UL listed power supply cord kit marked for use with clothes dryers. The kit should contain:

A UL listed 30-amp power supply cord, rated 240 volt minimum. The cord should be type SRD or SRDT and be at least 4 ft (1.22 m) long. The wires that connect to the dryer must end in ring terminals or spade terminals with upturned ends.

A UL listed strain relief.

If your outlet looks like this:

At least 5 ft (1.52 m) long.

4-wire receptacle (14-30R)

Then choose a 4-wire power supply cord with ring or spade terminals and UL listed strain relief. The 4-wire power supply cord, at least 4 ft (1.22 m) long, must have four 10-gauge copper wires and match a 4-wire receptacle of NEMA Type 14-30R. The ground wire (ground conductor) may be either green or bare. The neutral conductor must be identified by a white cover.

If your outlet looks like this:

3-wire receptacle (10-30R)

Then choose a 3-wire power supply cord with ring or spade terminals and UL listed strain relief. The 3-wire power supply cord, at least 4 ft (1.22 m) long, must have three 10-gauge copper wires and match a 3-wire receptacle of NEMA Type 10-30R.

If connecting by direct wire:

Power supply cable must match power supply (4-wire or 3-wire) and be:

Flexible armored cable or nonmetallic sheathed copper cable (with ground wire), protected with flexible metallic conduit. All current-carrying wires must be insulated.

10-gauge solid copper wire (do not use aluminum).

6

Image 6
Contents Electric Dryer W10131619ATable of Contents Dryer SafetyImportant Safety Instructions Installation Instructions Tools and PartsLocation Requirements It is your responsibility Mobile Home Additional Installation RequirementsElectrical Requirements Electrical ConnectionGauge solid copper wire do not use aluminum If using a power supply cordIf connecting by direct wire If your outlet looks like thisInstall strain relief Power Supply Cord Direct WireStyle 1 Power supply cord strain relief Electrical ConnectionStyle 2 Direct wire strain relief Wire connection Power Supply Cord Wire connection Direct Wire CG F Loosen or remove center silver-colored terminal block screwOptional 3-wire connection Tighten strain relief screwIf using an existing vent system Venting RequirementsIf this is a new vent system Vent material Recommended hood styles are shown here Plan Vent SystemExhaust Angled hood style shown here is acceptableSpecial provisions for mobile home installations Install Vent SystemAlternate installations for close clearances Vent system chartLevel Dryer Install Leveling LegsConnect Vent Reverse Door Swing OptionalComplete Installation If the dryer will not start, check the followingHow Automatic Drying Works Dryer USEStarting Your Dryer Stopping and RestartingDryer Care Cleaning the Dryer LocationCleaning the Lint Screen Drying Rack OptionCleaning the Dryer Interior Removing Accumulated LintVacation and Moving Care Troubleshooting Dryer OperationDryer Results Loads are wrinkled Lint on loadStains on load or drum Cycle time too shortEnhance your dryer with these premium accessories Assistance or ServiceAccessories Part Number AccessoryW10131619A