Siemens 6SE7086-4AH85-1BA0 Protective surge arresters, Surge arresters can be ordered from

Page 16

Connection

01.03

3.1Protective surge arresters

WARNING

We recommend the provision of protective surge arresters (supplied by DEHN, type VAV 1000) on the system side. One surge arrester per phase is connected to ground at the input of the common rectifier or rectifier/regenerating unit (use short-circuit-proof lead, fuse protection < 100 A – read data sheet supplied by surge arrester manufacturer!). These are particularly effective in isolated-neutral systems in preventing sparkovers and damage caused by voltage surges in the system. Experience shows that these surge voltages can be several kilovolts in magnitude. They can generate high-intensity secondary arcs when sparkovers occur, causing damage, possibly irreparable, to the device or installation concerned. The arc heat may also damage plastic components resulting in leakage of cooling water.

These surge voltages occur, for example, in the case of phase-to-ground faults or potential differences in the system, or as a result of system impedances in connection with the high switching gradients of e.g. IGBT semiconductor switches. Apart from sparkovers, these surges may also cause damage to parts insulated to ground (e.g. decomposition or electrical corrosion).

The surge arresters recommended above feature a defect display. It is advisable to perform a visual check on the devices at regular intervals.

Circuit-breaker

Circuit-breaker

Surge arrester

Common rectifier or

rectifier/regenerating unit

Inverter

M

Surge arresters can be ordered from:

Order-No.: 901000 / Type VAV1000

DEHN+SÖHNE Hans-Dehn-Straße 1 D-92318 Neumarkt/Opf.

eMail: info@dehn.de

3-2

ENGLISH

Siemens AG 6SE7086-4AH85-1BA0

 

Common rectifier and rectifier/regenerating units with water cooling

Supplement to the operating instructions

Image 16 Contents
Simovert Master Drives Conformity  Siemens AG 1997 All rights reservedEnglish Contents 01.03 Description Description 01.03 Assembly Unit Wall penetration Outgoing pipe Incoming pipe Use CoolantDefinition of cooling water BarFollowing table is a guideline coolant temperature 20 C Protection against moisture condensation Zinc breaks down all inhibitors which have a glycol basisCabinet design and connecting system Dimension drawing EnglishDimension drawing, regenerating unit Connection Protective surge arresters Surge arresters can be ordered fromPower connections FusesBuilt-in brunch fuses for common rectifier AG1BA04AH85Siemens6SE7086ENGLISH Parallel unit PMU Operating instructions 6SE7086-4AH85-1BA0 Parallel unit Parallel unit Power Siemens AG 6SE7086-4AH85 Common rectifierEnglish Common rectifier Maintenance Thyristor replacementLocation of the burden resistors and fuses Dimensioning of the burden resistorsChanging fuses Spare parts Equipment Designation Order number Used IdentifierSpare-parts 01.03 10-3 10-4 Technical Data 95,0% 92% 90,0% 85,0% 85% 80,0%III 14-2Losses, cooling, power factor Dimensions, weightLoad class II to EN 14-314-4 Losses, cooling 14-514-6 Page Data edizione Siemens Aktiengesellschaft
Related manuals
Manual 40 pages 33.66 Kb