Technical Data |
|
|
|
|
|
|
| 01.03 | ||
|
|
|
|
|
|
|
|
|
| |
| R/R unit |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| |
| Rated voltage, rated frequency, rated current |
|
|
|
|
|
| |||
| Rated voltage |
| V |
|
|
|
|
|
|
|
| Rectifier connection |
| 3 AC 660 to 690V ±15% |
| ||||||
| Regenerating connection |
| using an (auto) transformer |
| ||||||
|
|
|
| 1.2 times the voltage of the rectifier connection |
| |||||
| DC link voltage |
|
| DC 890 to 930V ±15% |
|
| ||||
| Rated frequency fn | Hz |
|
|
|
|
|
|
| |
| Input |
|
| 46 to 64 (automatic frequency matching) |
| |||||
| Output |
|
|
|
| D.C. |
|
|
|
|
| Rated current |
| A |
|
|
|
|
|
|
|
| (rms value) |
|
|
|
|
|
|
|
|
|
| With autotransformer |
|
|
|
|
|
|
|
| |
| Regenerating, line side |
| 1215 |
| 1825 |
|
| 2485 |
| |
| Regenerating, unit side |
| 1015 |
| 1520 |
|
| 2075 |
| |
| Rectifier operation |
| 1125 |
| 1690 |
|
| 2310 |
| |
| Without autotransformer |
|
|
|
|
|
|
|
| |
| Regenerating, unit side |
| 1015 |
| 1520 |
|
| 2075 |
| |
| Rectifier operation |
| 1125 |
| 1690 |
|
| 2310 |
| |
| Load class I to EN |
|
| |||||||
| in rectifier operation; currents reduced to 92% in regenerating operation |
| ||||||||
| Rated current |
| A | 1300 |
| 1950 |
|
| 2660 |
|
| (average) |
|
|
|
|
|
|
|
|
|
| DC link connection |
|
|
|
|
|
|
|
| |
| Rectifier operation |
|
|
|
|
|
|
|
| |
| Load class II to EN |
|
| |||||||
| in rectifier operation; currents reduced to 92% in regenerating operation |
| ||||||||
| Rated current |
| A | 1195 |
| 1795 |
|
| 2450 |
|
| Base load duration | s |
| 240 |
|
|
|
| ||
| Excess current |
| A | 1770 |
| 2650 |
|
| 3620 |
|
| Excess current duration | s |
| 60 |
|
|
|
| ||
| Losses, cooling |
|
|
|
|
|
|
|
|
|
| Power dissipation | kW | 4.60 |
| 6.08 |
|
| 8.52 |
| |
| - Maximum |
|
|
|
|
|
|
|
|
|
| Cooling air requirement | l/min |
|
| 54 2) |
|
|
|
| |
| coolant pressure drop ∆p | bar |
| 1) |
|
|
|
| ||
|
|
| 0.75 |
|
|
|
| |||
| Dimensions, weight |
|
|
|
|
|
|
|
| |
| Width |
| mm |
| 504 | 3) |
|
|
| |
| Height |
| mm |
| 740 |
|
|
| ||
| Height |
| mm |
| 550 |
|
|
|
| |
| Weight app. |
| kg |
| 142 | 3) |
|
|
|
„Parallel units“
The permissible output current in parallel mode is reduced (due to current division between the power sections) by 10 % as compared to the sum of the rated currents of the separate power sections.
1)For units from product status A2 and onwards (labelling on the unit at the coolant connection).
2)If the cooling circuits of the two converters are connected in parallel.
3)A rectifier/regenerating unit consists of two converters in separate housings.
| ENGLISH | Siemens AG |
| Common rectifier and rectifier/regenerating units with water cooling | Supplement to the operating instructions |