Siemens 6SE7086-4AH85-1BA0 operating instructions Iii, 14-2

Page 34

Technical Data

01.03

Storage temperature Transport temperature Coolant intake temperature

−25 °C to +70 °C

−25 °C to +70 °C

+5 °C to + 38 °C (max + 46°C with current reduction)

Operating pressure

 

< 2,5 bar

 

 

 

Environmental class

3K3

DIN IEC 721-3-3 / 04.90

Soiling

2

DIN VDE 0110

Part 1 / 01.89

 

 

 

 

moisture not permitted

Overvoltage category (power section)

III

DIN VDE 0110

Part 2 / 01.89

Overvoltage resistance class

1

DIN VDE 0160

/ 04.91

 

(with converter connected)

 

 

 

 

 

Type of protection

IP00

DIN VDE 0470

Part 1 / 11.92 =^ EN 60529

Interference immunity

 

IEC 801-2, IEC 801-4

Mechanical strength

 

DIN IEC 68-2-6 / 06.90

 

 

Frequency range

Constant amplitude of

 

 

 

 

 

deflection

acceleration

 

 

 

 

Hz

mm

 

m/s2 (g)

 

−

stationary use

 

10 to 58

0,075

 

 

 

 

 

 

 

 

 

more than 58 to 500

 

 

9,8 (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−

during transport

 

 

3,5

 

 

 

 

 

 

 

 

 

 

 

 

 

9,8 (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The units can also be operated in load class II. The permissible values must be taken from the following tables.

I (A)

Load class

II

136%

 

 

 

 

Load class I

100%

 

 

91%

 

 

60s

240s

t/(s)

Figure 14.1 Power output according to load class II

14-2

ENGLISH

Siemens AG 6SE7086-4AH85-1BA0

 

Common rectifier and rectifier/regenerating units with water cooling

Supplement to the operating instructions

Image 34
Contents Simovert Master Drives Conformity  Siemens AG 1997 All rights reservedEnglish Contents 01.03 Description Description 01.03 Assembly Unit Wall penetration Outgoing pipe Incoming pipe Definition of cooling water UseCoolant BarFollowing table is a guideline coolant temperature 20 C Protection against moisture condensation Zinc breaks down all inhibitors which have a glycol basisCabinet design and connecting system Dimension drawing EnglishDimension drawing, regenerating unit Connection Protective surge arresters Surge arresters can be ordered fromPower connections FusesBuilt-in brunch fuses for common rectifier AG1BA04AH85Siemens6SE7086ENGLISH Parallel unit PMU Operating instructions 6SE7086-4AH85-1BA0 Parallel unit Parallel unit Power Siemens AG 6SE7086-4AH85 Common rectifierEnglish Common rectifier Maintenance Thyristor replacementLocation of the burden resistors and fuses Dimensioning of the burden resistorsChanging fuses Spare parts Equipment Designation Order number Used IdentifierSpare-parts 01.03 10-3 10-4 Technical Data 95,0% 92% 90,0% 85,0% 85% 80,0%III 14-2Load class II to EN Losses, cooling, power factorDimensions, weight 14-314-4 Losses, cooling 14-514-6 Page Data edizione Siemens Aktiengesellschaft