Siemens 6SE7086-4AH85-1BA0 operating instructions Maintenance, Thyristor replacement

Page 27

01.03

Maintenance

8 Maintenance

WARNING

The warning notes for "air-cooled units" apply.

Installation and maintenance work relating to the water-equipment is only to be done when the installation is off load.

8.1Thyristor replacement

d

s

a

f g f

1.) Remove reference spacer a (accuracy: ± 0.1 mm)

2.) Loosen lock nut (SW 46) s .

3.) Unscrew adjusting screw (SW 22) d max. four turns.

4.) Carefully press apart the contact rails f of the corresponding thyristor.

5.) Remove thyristor disc g.

6.) Using a spatula, apply a thin layer of contact grease (Elektrolube 2A-X) to the new thyristor disc.

7.) Insert new thyristor disc. Make sure it is positioned correctly (polarity and terminals)! Connect firing cables.

8.) Screw in adjusting screw (M30x1.5) d until the reference gauge a has been reached.

9.) Firmly tighten s lock nut.

The position of the thyristor and its diameter may not be the same as in the diagram! After a thyristor defect, check the fuse indicators at the least.

For further information and warnings, see the operating instructions for air-cooled rectifier or rectifier/regenerating units.

Siemens AG 6SE7086-4AH85-1BA0

ENGLISH

8-1

Common rectifier and rectifier/regenerating units with water cooling

Supplement to the operating instructions

 

Image 27 Contents
Simovert Master Drives  Siemens AG 1997 All rights reserved ConformityEnglish Contents 01.03 Description Description 01.03 Assembly Unit Wall penetration Outgoing pipe Incoming pipe Bar UseCoolant Definition of cooling waterFollowing table is a guideline coolant temperature 20 C Zinc breaks down all inhibitors which have a glycol basis Protection against moisture condensationCabinet design and connecting system English Dimension drawingDimension drawing, regenerating unit Connection Surge arresters can be ordered from Protective surge arrestersFuses Power connectionsBuilt-in brunch fuses for common rectifier AG1BA04AH85Siemens6SE7086ENGLISH Parallel unit PMU Operating instructions 6SE7086-4AH85-1BA0 Parallel unit Parallel unit Siemens AG 6SE7086-4AH85 Common rectifier PowerEnglish Common rectifier Thyristor replacement MaintenanceDimensioning of the burden resistors Location of the burden resistors and fusesChanging fuses Equipment Designation Order number Used Identifier Spare partsSpare-parts 01.03 10-3 10-4 95,0% 92% 90,0% 85,0% 85% 80,0% Technical Data14-2 III14-3 Losses, cooling, power factorDimensions, weight Load class II to EN14-4 14-5 Losses, cooling14-6 Page Siemens Aktiengesellschaft Data edizione
Related manuals
Manual 40 pages 33.66 Kb