INSTALLATION
MINIMUM FIREPLACE
DIMENSIONS
The minimum fireplace dimensions for the Re- gency gas space heater are shown in the following diagrams:
GAS CONNECTION
GAS CONNECTION WARNING: Only persons licensed to work with gas piping may make the neces- sary gas connections to this appli- ance.
1)If the appliance is to be installed into an existing chimney system, thoroughly clean the masonry or factory built fireplace.
2)The gas connection is 12" BSP.
Mantel Clearances with Bay and Flush Louvres in Masonry Installation
MINIMUM
CLEARANCES TO COMBUSTIBLES
The minimum fireplace clearances for the Re- gency gas space heater are shown in the following diagrams:
| From Unit |
|
Sides | A | 255 mm |
Ceiling | B | 1205 mm |
Mantle | C | see Mantel |
|
| Clearances |
From Surround (660 mm x 1016 mm)
Max. Mantle Depth | G | 305 mm |
Hearth Height | H | 0 mm |
Hearth Depth | I | 405 mm |
Hearth Width | J | 1015 mm |
Min. Alcove Width | K | 1220 mm |
Max. Alcove Depth | L | 915 mm |
NOTE: Mantel clearances for Installation into a Zero Clearance Kit are differ- ent. Please refer to the Zero Clear- ance Kit Manual for details.
Note: A
3)Locate the center point where the flue will pass through the chimney above the appli- ance. Move the appliance into the exact location where it is to be installed. Ensure that the Insert is level.
4)The installer must provide a valve with a plugged tapping, accessible for test gauge connection, immediately upstream of the gas supply connection to the appliance.
CAUTION: If the glass is removed or opened for servicing, it must be re- placed and closed prior to operating the appliance. The glass must be fixed in the door when operating.
SPECIFICATIONS
| NG | LPG |
|
|
|
INJECTOR | #37 | #52 |
SIZE | 2.65mm | 1.6mm |
|
|
|
INPUT | Min. 17 mj/h | Min. 17 mj/h |
RATING | Max. 31 mj/h | Max. 31 mj/h |
MANIFOLD |
|
|
PRESSURE | Max. 0.9 kPa | Max. 2.59 kPa |
|
|
|
6 | Regency |