Page 17

5) SOOTING

Make sure log placement is

in the correct location.

Make sure there is sufficient

air supply.

Check air shutter on the venturi tube for proper primary air adjustment.

SEE PAGE 16.

Make sure orifice matches

that on the rating plate.

Make sure outlet (manifold)

pressure is correct.

Make sure the unit has been

derated for high altitude

applications. (if required)

Check to make sure that the

vent is drafting properly.

Correct to manufactures

specifications.

Correct if necessary.

Outside air supply may be

required on B-vented

models.

Increase primary air.

Open air shutter.

Correct if necessary.

Use a manometer to check

the gas pressure.

SEE PAGE 5 FIGURE 7.

Correct if necessary.

Correct if necessary.

 

 

 

 

 

 

Sherwood Industries Ltd.

ENVIRO

PAGE 15

 

 

 

 

 

 

Image 17
Contents GAS Fireplace Suggested Tools List for Servicing Table of ContentsSee page 2 Figure 1PILOT will not Light No Spark Ignition System175mm See page 4 Figure Piezo Ignitor OK but Pilot will Still not LightTo remove pilot injector Exploded View S.I.T Pilot AssemblySupply Pressures 50% Turn Down Natural GAS Propane GAS Proper Voltage These Readings should be Constant with no FluctuationChecking Thermocouple forPilot will not Stay LIT T Eurosit Modulating 630 Series See page 6 Figure Main Burners will not LightSee page 8 Figure Main Burners will not Light CON’T See Main Burners will not Stay LITVented Models Enviro Sample Direct Vent Chimney Installations ALL Models Enviro Sooting Enviro Vented Models Flame LiftingDo not GO TOO FAR or Unit will Soot See page 5 Figure EnviroDirect Vent Models Blower Diagnosis ALL Models Natural GAS Propane GAS DRILL# Size Orifice Sizing ChartStep by Step Service Instructions Cleaning the Appliance Glossary