Desa VI33PRA Providing Adequate Ventilation, Determining FRESH-AIR Flow for Heater Location

Page 5

AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation Determining Fresh-Air Flow For Heater Location

5

AIR FOR COMBUSTION AND VENTILATION

Continued

PROVIDING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 4 through 6 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11kg per pa-sec-m2) or less with openings gasketed or sealed and

b.weather stripping has been added on openable win- dows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 6.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow for Heater Loca- tion in column 2.

Confined and Unconfined Space

The National Fuel Gas Code ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 3168 cu. ft. (volume of space) x 20 = 63,360 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

 

40,000

 

 

_____________ Btu/Hr

Vent-free heater

+

33,000

Btu/Hr

Total

 

73,000

 

= _____________ Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 63,360 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

For morevisit www..com

110150-01A

Image 5
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualUnvented VENT-FREE GAS Fireplace Insert Safety Information Table of ContentsProduct Identification Log Base AssemblyProduct Features Remote Control AccessoriesLocal Codes UnpackingDetermining FRESH-AIR Flow for Heater Location Providing Adequate VentilationUnusually Tight Construction Confined and Unconfined SpaceVentilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installing Surround KIT GS38 or GS43 InstallationBlower Accessory Check GAS TypeAttaching Left Installing HoodFireplace Insert Installation Into Masonry Fireplace Installation ClearancesInstalling GAS Piping to Fireplace Location Fireplace Insert Installation Into FRAMED-IN EnclosureMantel Clearances for Insert Installation Installation Items NeededPropane/LP Connecting Fireplace Insert to GAS SupplyChecking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Fireplace Insert Gas Connections Installing LogsGhrcta Installing Remote Receiver UnitFor Your Safety Read Before Lighting Installing 9-VOLT BatteriesInstalling 9-Volt Battery Not Included in Receiver Operating Fireplace InsertTo Turn OFF GAS to Appliance Manual Lighting ProcedureShutting Off Heater Shutting Off Burners Only pilot stays litThermostat Control Operation Optional Remote OperationGhrc Series Operation Ghrcta Series OperationInspecting Burners Logs Cleaning MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Observed Problem Possible Cause TroubleshootingMaintenance, Observed Problem Possible Cause Remedy Replacement Parts Wiring DiagramsService Hints SpecificationsRemote Ready Model VI33NRA Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListRemote Ready Model VI33PRA 103877-01 Lighting Instruction Plate 100563-01 Fireplace Insert VI33NRA VI33PRA 101784-01 Magnet Catch 102307-01 Strike Plate WALL-MOUNT Thermostat Switch Receiver and HAND-HELD Remote Control KIT Ghrc SeriesWALL-MOUNT ON/OFF Switch GWMS2 Cleaning KIT CCK110150-01A Warranty Information