TROUBLESHOOTING
Note: Before troubleshooting the system, make sure the gas shutoff valve is ON. The two most common causes of a malfunctioning gas appliance are:
1.Loose wiring connections
2.Construction debris clogging the pilot and/or gas control valve filter
OBSERVED PROBLEM | POSSIBLE CAUSE | REMEDY | ||
Pilot will not light | 1. No gas supply or shutoff | 1. | Check to see if you have gas | |
|
| valve is OFF |
| supply |
| 2. | Air in gas line | 2. | Hold regulator control valve |
|
|
|
| in the PILOT position for 2 to |
|
|
|
| 3 minutes to purge air. If you |
|
|
|
| smell gas stop and wait for a |
|
|
|
| few minutes before trying to |
|
|
|
| light the fireplace |
| 3. | Construction debris clog- | 3. | Remove debris and dirt, in- |
|
| ging pilot orifice |
| spect and clean any other |
| 4. | Low gas pressure |
| possible obstructions |
| 4. | Contact your gas supplier | ||
| 5. | Control valve knob is not on | 5. | Refer to section on pilot |
|
| the PILOT position |
| lighting |
| 6. | Kinked pilot line | 6. | Have a qualified technician |
| 7. | Bad valve |
| replace pilot line |
| 7. | Replace regulator valve (see | ||
| 8. | Vent damper not fully open |
| Accessories, page 31) |
| 8. | Open vent damper until fully | ||
|
|
|
| locked in OPEN position |
|
|
|
|
|
Pilot will not stay lit | 1. | Loose wiring on thermopile |
|
| to regulator valve. No mil- |
|
| livolt current is being sent |
|
| back to regulator |
| 2. | If valve knob and wall switch |
|
| are in the ON position, proba- |
|
| ble defective regulator valve |
| 3. | Vent damper not fully open |
1.Check wiring connections. Refer to wiring diagram shown in Wall Switch Instal- lation, page 11
2.Have a qualified technician replace valve
3.Open vent damper until fully locked in OPEN position
No gas to burner, although wall | 1. | Wall switch wires defective or | 1. | Check electrical connections |
switch and valve are set to the |
| too long | 2. | See Pilot will not stay lit, |
ON position | 2. | Thermopile not generating | ||
|
| sufficient voltage |
| above |
|
|
|
|
|
Frequent pilot outage | 1. | Pilot flame may be too | 1. | Clean and adjust pilot flame |
|
| low, causing safety pilot to |
| for maximum flame impinge- |
|
| “drop out” |
| ment on thermopile |
| 2. | Improper venting or excessive | 2. | Have the vent system inspect- |
|
| blockage |
| ed, including the termination |
|
|
|
| cap. Remove any restriction |
|
|
|
| or obstruction |
www.desatech.com | 23 |