TROUBLESHOOTING
Note: Before troubleshooting the system, make sure the gas shutoff valve is ON. The two most common causes of a malfunctioning gas appliance are:
1.Loose wiring connections
2.Construction debris clogging the pilot and/or gas control valve filter
OBSERVED PROBLEM | POSSIBLE CAUSE | REMEDY | ||
Pilot will not light  | 1. No gas supply or shutoff  | 1.  | Check to see if you have gas  | |
  | 
  | valve is OFF | 
  | supply | 
  | 2.  | Air in gas line | 2.  | Hold regulator control valve  | 
  | 
  | 
  | 
  | in the PILOT position for 2 to  | 
  | 
  | 
  | 
  | 3 minutes to purge air. If you  | 
  | 
  | 
  | 
  | smell gas stop and wait for a  | 
  | 
  | 
  | 
  | few minutes before trying to  | 
  | 
  | 
  | 
  | light the fireplace  | 
  | 3.  | Construction debris clog-  | 3.  | Remove debris and dirt, in-  | 
  | 
  | ging pilot orifice  | 
  | spect and clean any other  | 
  | 4.  | Low gas pressure  | 
  | possible obstructions  | 
  | 4.  | Contact your gas supplier  | ||
  | 5.  | Control valve knob is not on  | 5.  | Refer to section on pilot  | 
  | 
  | the PILOT position  | 
  | lighting  | 
  | 6.  | Kinked pilot line  | 6.  | Have a qualified technician  | 
  | 7.  | Bad valve  | 
  | replace pilot line  | 
  | 7.  | Replace regulator valve (see  | ||
  | 8.  | Vent damper not fully open  | 
  | Accessories, page 31) | 
  | 8.  | Open vent damper until fully  | ||
  | 
  | 
  | 
  | locked in OPEN position  | 
  | 
  | 
  | 
  | 
  | 
Pilot will not stay lit  | 1.  | Loose wiring on thermopile  | 
  | 
  | to regulator valve. No mil-  | 
  | 
  | livolt current is being sent  | 
  | 
  | back to regulator | 
  | 2.  | If valve knob and wall switch  | 
  | 
  | are in the ON position, proba-  | 
  | 
  | ble defective regulator valve  | 
  | 3.  | Vent damper not fully open  | 
1.Check wiring connections. Refer to wiring diagram shown in Wall Switch Instal- lation, page 11
2.Have a qualified technician replace valve
3.Open vent damper until fully locked in OPEN position
No gas to burner, although wall  | 1.  | Wall switch wires defective or  | 1.  | Check electrical connections  | 
switch and valve are set to the  | 
  | too long  | 2.  | See Pilot will not stay lit, | 
ON position  | 2.  | Thermopile not generating  | ||
  | 
  | sufficient voltage  | 
  | above  | 
  | 
  | 
  | 
  | 
  | 
Frequent pilot outage  | 1.  | Pilot flame may be too  | 1.  | Clean and adjust pilot flame  | 
  | 
  | low, causing safety pilot to  | 
  | for maximum flame impinge-  | 
  | 
  | “drop out”  | 
  | ment on thermopile  | 
  | 2.  | Improper venting or excessive  | 2.  | Have the vent system inspect-  | 
  | 
  | blockage  | 
  | ed, including the termination  | 
  | 
  | 
  | 
  | cap. Remove any restriction  | 
  | 
  | 
  | 
  | or obstruction  | 
www.desatech.com  | 23  |