INSTALLATION

Continued

Grate

Pan and Ember

0.5"

Material

0.5"

 

Burner Pan

Figure 24 - Pan and Ember Material

Clearances

LOG PLACEMENT FOR M36, M36P, VM36 AND VM36P MODELS

1.Place small front right log (log 1) on right front of grate as shown in Figure 25.

2.Place large back log (log 2) onto grate mak- ing sure notches rest over grate as shown in Figure 25.

3.Place log 3 into notch on log 2, resting the front end on top of log 1 (see Figure 26).

4.Place the upper end of log 4 into the notch on log 2 as shown in Figure 26. Rest the lower end of log 4 onto the middle grate finger as shown in Figure 27.

5.Place the upper end of log 5 into notch on the left of log 2 (see Figure 27). Rest the lower end of log 5 on the grate as shown in Figure 28.

6.Insert the lower end of log 6 between the first two grate fingers as shown in Figure 28 and position the upper end of log 6 into the notched area on the front of log 2 as shown in Figure 28.

As an option to enhance the look of the hearth, you may place the lava rock provided around the front and sides of the burner.

Log 2

Notch

Log 1

NOTICE: Do not put lava rock inside the burner pan or around the air mixer fitting. Placing lava rock inside the burner pan or blocking the openings of the pro- pane/LP air-mixer could cause performance problems.

Log 4

Log 3 Log 2

Notches

Log 1

Figure 26 - Installing Logs 3 and 4

 

Log 5

Log 6

Notch

 

Log 4

Notch

Figure 27 - Installing Logs 5 and 6

Figure 25 - Installing Logs 1 and 2

Figure 28 - Logs Installed for M36, M36P, VM36 and VM36P Models

108795-01N

www.desatech.com

15

Image 15
Contents PROPANE/LP GAS Natural GASTable of Contents High traffic areas Windy or drafty areas Safety InformationModification of the appliance or any of the components UnpackingIntroduction Before YOU BeginSelecting Location Possible Locations for Installing ApplianceOrifice Size Product SpecificationsM42B,H, VM42B,H 10.5 in. WC 2.66 kPaDetails PRE-INSTALLATION PreparationClearances Mantel Clearances and WallFraming Rough Opening for Installing WallVent Piping Starter Collar Transition Pipe Vent Collar Venting InstallationInstalling Transition Pipe and Starter Collar flue connection must be made using listedRoof Pitch Typical B-Vent ConfigurationInstallation Wall Switch InstallationChecking for Proper Venting Receiver Plastic Mounting Clips Mounting Bracket Optional Wireless HAND-HELD Remote Control Installation Installing Receiver Volt Battery Clip Terminal Wires ReceiverInstalling 9-Volt Battery in Hand-Held Remote Control Unit GAS Line HOOK-UPM36PB,H M42PB,H Ember and PAN Material Placement Log LOG Placement for M36, M36P, VM36 and VM36P ModelsGrate Pan and Ember Material Burner Pan Log Notch Log 3 Log NotchesLog Notch Log 2B LOG Placement for M42, M42P, VM42 and VM42P ModelsNotch Log Log 2A Log 2B Log NotchesInstalling Optional Glass Door Accessory Combustion AIR KIT Model AK4 OptionalAppliance Enclosure Partially Opened Door Opening Vent DamperSpring Clip Screw Side FrontFor Your Safety Read Before Lighting Operating FireplaceLighting Instructions Optional HAND-HELD Remote Operation Pilot AssemblyInspecting Burners To Turn OFF GAS To ApplianceLogs Cleaning MaintenanceBurner Flame Pattern Pilot and BurnerReplacement Parts Wiring DiagramService Hints Technical ServiceObserved Problem Possible Cause Remedy TroubleshootingGas/air mixture caused Connected, replace ignitorElectrode at pilot spark at If pilot lights, an improperGas leak. See Warning Models Illustrated Parts BreakdownDescription QTY Parts ListM36B,H, M36PB,H, VM36B,H and VM36PB,H Brick Liners for ModelsLogsets for Models M42B,H, M42PB,H, VM42B,H and VM42PB,H Accessories Warranty Information Keep this WarrantyLimited Warranty VENT-FREE Firebox