Panasonic CU-KE30NKU, CU-KE36NKU service manual CS-KE30NKU, CS-KE36NKU

Page 61

Operating Instructions

Split System Air Conditioner

Model No.

 

Indoor Units

Outdoor Units

CS-KE30NKU

CU-KE30NKU

CS-KE36NKU

CU-KE36NKU

This air conditioner uses the refrigerant R410A.

Before operating the unit, read these operating instructions thoroughly and keep them for future reference.

Panasonic Corporation

1006 Kadoma, Kadoma City, Osaka, Japan

85264181221002

CV6233187112

Image 61
Contents Indoor Model No Product Code No CS-KE30NKU + CU-KE30NKU CS-KE36NKU + CU-KE36NKUOutdoor Model No Product Code No 852 360Safety Precautions Prohibit Table of Contents Checking Electrical Components Operating Range Temperature Indoor Air Intake Temp Outdoor Air Intake TempUnit Specifications SpecificationsIndoor Unit Outdoor Unit208V CS-KE36NKU 21.9 19.9 Indoor Unit Major Component SpecificationsIndoor Unit CS-KE30NKU CB-CS-KE36NKU Indoor Unit CS-KE36NKUOutdoor Unit CU-KE30NKU Outdoor UnitBoard CompressorOutdoor Unit CU-KE36NKU Other Component Specifications Dimensional Data Inchmm 194-00-1 Unit Refrigerant Flow Diagram Refrigerant Flow DiagramIndoor Unit CS-KE30NKU Outdoor Unit CU-KE30NKU Indoor unit Outdoor unitPerformance Data Temperature ChartsHigh pressure performance chart Indoor Unit CS-KE36NKU Outdoor Unit CU-KE36NKU Discharge 9535 8630 Indoor Cooling Capacity Power Supply 230V Single Phase 60Hz Cooling CapacityCS-KE30NKU CU-KE30NKU34,000 BTU/h Outdoor Cooling Capacity Low Ambient30,900 30,870 30,800 30,710 30,590 30,400 30,210 Heating Capacity Power Supply 230V Single Phase 60Hz Heating CapacityTH Total Heating Capacity BTU/h 36,000 BTU/h Air Throw Distance Charts Cooling Electrical Data Electrical CharacteristicsVoltage230V Cooling Heating650 8FA2-5251-12400-1 Electric Wiring DiagramsController 8FA2-5251-15200-0Operation Functions FunctionsEmergency operation Auto cooling/heating operationLamp colors Timer backupNoise Reducing Control Outdoor Unit Switching Procedure to Noise Reducing ControlOperation Sound Maximum Current Value Change Function Maximum Current Value Change ProcedureDescription of function CU-KE36NKUProtective Functions Compressor discharge temperature controlOverload prevention during heating Freeze preventionCT Peak current cut-off control Defrost detection and releaseReverse-Cycle Defrosting Precautions before Performing Inspection or Repair Troubleshooting Before Calling for ServiceMethod of Self-Diagnostics Diagnosis Contents Self-diagnostics LampsReplace the controller NormalReplace the circuit board or the fuse Checking the Indoor and Outdoor Units Using the TEST/T-RUN terminalsChecking the indoor unit Control Check items unit operation Alarm Code E05 Serial Communication Error Identification ProcedureOff Blinking Illuminated Before the OperationFrom the previous page a Alarm Code E07/P04/P05/P20/P27 Indoor Fan Motor Trouble Diagnosis of Fan MotorPin 3 Gnd blue Outdoor Fan MotorPin 1 Vcc brown Pin 2 PG whiteNoise malfunction Noise Malfunction and Electromagnetic InterferenceElectromagnetic interference Locations most susceptible to noise Trouble CorrectionChecking Electrical Components Power Supply CordMeasurement of Insulation Resistance Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy Characteristics of New Refrigerant R410A Refrigerant R410A Special Precautions When Servicing UnitWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorAmount in the charging cylinder is less than 20% Configuration and characteristics of cylindersExample To prevent the compositionWelding leaking points Case Refrigerant is LeakingRecharging Charging Additional Refrigerant When Tubes are ExtendedRetro-Fitting Existing Systems Use of Existing UnitsAppendix a Operating Instructions CS-KE36NKU CS-KE30NKUContents FeaturesSafety Precautions Product InformationSafety Instructions Installation LocationElectrical Requirements AvoidUnit Display and Operation Button Names of PartsSymbols Remote Controller DisplayRemote Controller Temperature setting buttons Temp HR. Timer button 1-HOUR OFF TimerMode selector button High Power buttonACL button Using the Remote Controller32 x 13/16 20 mmAutomatic Operation Operation with the Remote ControllerHeating Mode Cooling and DRY ModeAutomatic fan speed Manual fan speedUnoccupied Indication Status High Power ModeSpecial Remarks Operation Indication Setting the TimerTips for Energy Saving Using the 1-HOUR OFF Timer1030 pm 710 am 1100 am Present time When the air conditioner is not running Adjusting the Airflow DirectionCleaning the main unit and Remote Controller How to replace the filterRemoving and remounting the front panel Washing the front panel with waterOperating Range Wired Remote ControllerTrouble Possible Cause Remedy Model No Outdoor Unit Indoor Unit SpecificationsPage 852-6-4190-587-00-0 Contents Installation Instructions Split System Air ConditionerPlease Read Before Starting Accidentally Fins of the outdoor unit. You may get injuredAccessories Supplied with Unit Table Tools Required for Installation not suppliedGeneral Optional Copper Tubing KitAdditional Materials Required for Installation Installation Site SelectionSolid base must not cover the hole of the bottom plate  Countermeasures against snow and wind Precautions for Installation in a Snowy Area $/,8,3?,4508-25=  $/,04.3?-8,,D,4+89 Unit inch 4922054=0/041,9-*04.52,9 Required space around the outdoor unit$/,-8544+5/90+,9398,30456,4 27-5/8 11-5/8 Air Intake 25/32 13/32 13-3/8 14-31/32  #04.2,4004922054  9*2,9545/90+,9 4522,8/4/,/,0./5-/,5+55840Obstacles to the front and rear of unit Installation in front-rear rows #04.2,4004922054  9*2,9545/90+,9Trical wiring or conduits are How to Install the Indoor UnitRemove the Rear Panel from the Unit Make a HoleIf Wooden Wall Install the Rear Panel on the WallIf Block, Brick, Concrete or Similar Type Wall Hole DiaHow to remove the grille Removing and Installing the GrilleHow to replace the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringWire Size and Length Wiring Instructions for Inter-unit Connections For Outdoor Unit  For solid core wiring or F-cable How to connect wiring to the terminal For Indoor Unit For stranded wiring  Right-side tubing Mounting Left-side tubing Switching drain hose and drain capDrain cap Tubing and wiring to the out Do not supply power toTo unmount indoor unit Frame Fastening MethodWiring Instructions for the Outdoor Unit How to Install the Outdoor UnitRouting the Tubing and Wiring Cover BTo 0.5 mm Adjust so that the amount of tube Flaring Procedure with a Flare ToolRefrigerant Tubing Use of the Flaring MethodFinishing the Installation Connecting Tubing between Indoor and Outdoor UnitsInsulation of Refrigerant Tubing Taping the TubesAir Purging Hex wrench before Be sure to completely insertAttempting to turn the valve How to Test Run the Air Conditioner  Pump Down  Basic Functions of the Service ValvesRemote Controller Installation Position  Service Valve ConnectionsAddress Setting of the Remote Controller Address SwitchDC1111-0

CS-KE30NKU, CS-KE36NKU, CU-KE30NKU, CU-KE36NKU specifications

The Panasonic CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU air conditioning units represent the brand's commitment to delivering high-performance cooling solutions backed by innovative technologies. These units cater to both residential and commercial applications, ensuring users experience maximum comfort throughout the year.

One of the standout features of these models is their energy efficiency. Both units are equipped with advanced inverter technology, which allows for variable speed operation. This means they can adjust their power output according to the room's cooling needs, reducing energy consumption and minimizing electric bills while maintaining a consistent temperature. The models boast impressive SEER (Seasonal Energy Efficiency Ratio) ratings, making them environmentally friendly options.

Panasonic's nanoe-G technology is another remarkable feature incorporated into these models. This technology helps to purify the air by generating hydroxyl radicals, which eliminate airborne particles, odors, and harmful bacteria. This results in a healthier indoor environment, conducive to both comfort and well-being. The air purification aspect not only enhances the air quality but also extends the lifespan of the HVAC system by reducing the buildup of dust and contaminants.

In terms of user convenience, both the CU-KE and CS-KE series are equipped with programmable timers, allowing users to set their desired operation schedules. They also come with a remote control for ease of use, enabling adjustments from a distance. The installation process is straightforward, and the sleek design blends seamlessly with various interior aesthetics, making them a suitable choice for any room.

Durability is a key characteristic of Panasonic air conditioning units, and the CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU are designed to withstand varying environmental conditions. Their robust construction ensures reliability and performance over the years. Additionally, both models come with a quiet operation feature that minimizes noise levels, allowing for comfortable use without disturbing daily activities.

In summary, the Panasonic CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU are exceptional air conditioning units that combine energy efficiency, innovative purification technology, user-friendly features, and robust durability. These models are an ideal investment for anyone seeking a reliable and high-performance cooling solution.