Panasonic CU-KE30NKU, CU-KE36NKU, CS-KE36NKU, CS-KE30NKU Checking Electrical Components

Page 5

 

 

 

Page

9. CHECKING ELECTRICAL COMPONENTS

 

9-1.

Measurement of Insulation Resistance

51

9-2.

Checking Continuity of Fuse on PCB Ass'y

52

10. REFRIGERANT R410A:

 

SPECIAL PRECAUTIONS WHEN SERVICING UNIT

 

10-1.

Characteristics of New Refrigerant R410A

53

10-2.

Checklist before Servicing

54

10-3.

Tools Specifically for R410A

55

10-4.

Tubing Installation Procedures

55

10-5.

In Case of Compressor Malfunction

56

10-6.

In Case Refrigerant is Leaking

58

10-7.

Charging Additional Refrigerant

59

10-8.

Retro-Fitting Existing Systems

59

 

Operating Instructions

 

APPENDIX A

A-1

 

INSTALLAION INSTRUCTIONS

 

APPENDIX B

A-2

5

Image 5
Contents Indoor Model No Product Code No CS-KE30NKU + CU-KE30NKU CS-KE36NKU + CU-KE36NKUOutdoor Model No Product Code No 852 360Safety Precautions Prohibit Table of Contents Checking Electrical Components Operating Range Temperature Indoor Air Intake Temp Outdoor Air Intake TempUnit Specifications SpecificationsIndoor Unit Outdoor Unit208V CS-KE36NKU 21.9 19.9 Indoor Unit CS-KE30NKU Major Component SpecificationsIndoor Unit CB-CS-KE36NKU Indoor Unit CS-KE36NKUOutdoor Unit CU-KE30NKU Outdoor UnitBoard CompressorOutdoor Unit CU-KE36NKU Other Component Specifications Dimensional Data Inchmm 194-00-1 Unit Refrigerant Flow Diagram Refrigerant Flow DiagramIndoor Unit CS-KE30NKU Outdoor Unit CU-KE30NKU Indoor unit Outdoor unitPerformance Data Temperature ChartsHigh pressure performance chart Indoor Unit CS-KE36NKU Outdoor Unit CU-KE36NKU Discharge 9535 8630 Indoor Cooling Capacity Power Supply 230V Single Phase 60Hz Cooling CapacityCS-KE30NKU CU-KE30NKU34,000 BTU/h Outdoor Cooling Capacity Low Ambient30,900 30,870 30,800 30,710 30,590 30,400 30,210 TH Total Heating Capacity BTU/h Power Supply 230V Single Phase 60Hz Heating CapacityHeating Capacity 36,000 BTU/h Air Throw Distance Charts Cooling Electrical Data Electrical CharacteristicsVoltage230V Cooling Heating650 8FA2-5251-12400-1 Electric Wiring DiagramsController 8FA2-5251-15200-0Operation Functions FunctionsEmergency operation Auto cooling/heating operationLamp colors Timer backupOperation Sound Switching Procedure to Noise Reducing ControlNoise Reducing Control Outdoor Unit Maximum Current Value Change Function Maximum Current Value Change ProcedureDescription of function CU-KE36NKUProtective Functions Compressor discharge temperature controlOverload prevention during heating Freeze preventionReverse-Cycle Defrosting Defrost detection and releaseCT Peak current cut-off control Method of Self-Diagnostics Troubleshooting Before Calling for ServicePrecautions before Performing Inspection or Repair Diagnosis Contents Self-diagnostics LampsReplace the circuit board or the fuse NormalReplace the controller Checking the indoor unit Control Check items unit operation Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Alarm Code E05 Serial Communication Error Identification ProcedureOff Blinking Illuminated Before the OperationFrom the previous page a Alarm Code E07/P04/P05/P20/P27 Indoor Fan Motor Trouble Diagnosis of Fan MotorPin 3 Gnd blue Outdoor Fan MotorPin 1 Vcc brown Pin 2 PG whiteNoise malfunction Noise Malfunction and Electromagnetic InterferenceElectromagnetic interference Locations most susceptible to noise Trouble CorrectionChecking Electrical Components Power Supply CordMeasurement of Insulation Resistance Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy Characteristics of New Refrigerant R410A Refrigerant R410A Special Precautions When Servicing UnitWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorAmount in the charging cylinder is less than 20% Configuration and characteristics of cylindersExample To prevent the compositionRecharging Case Refrigerant is LeakingWelding leaking points Charging Additional Refrigerant When Tubes are ExtendedRetro-Fitting Existing Systems Use of Existing UnitsAppendix a Operating Instructions CS-KE36NKU CS-KE30NKUContents FeaturesSafety Precautions Product InformationSafety Instructions Installation LocationElectrical Requirements AvoidUnit Display and Operation Button Names of PartsSymbols Remote Controller DisplayRemote Controller Temperature setting buttons Temp HR. Timer button 1-HOUR OFF TimerMode selector button High Power buttonACL button Using the Remote Controller32 x 13/16 20 mmAutomatic Operation Operation with the Remote ControllerHeating Mode Cooling and DRY ModeAutomatic fan speed Manual fan speedUnoccupied Indication Status High Power ModeSpecial Remarks Operation Indication Setting the Timer1030 pm 710 am 1100 am Present time Using the 1-HOUR OFF TimerTips for Energy Saving When the air conditioner is not running Adjusting the Airflow DirectionCleaning the main unit and Remote Controller How to replace the filterRemoving and remounting the front panel Washing the front panel with waterTrouble Possible Cause Remedy Wired Remote ControllerOperating Range Model No Outdoor Unit Indoor Unit SpecificationsPage 852-6-4190-587-00-0 Contents Installation Instructions Split System Air ConditionerPlease Read Before Starting Accidentally Fins of the outdoor unit. You may get injuredAccessories Supplied with Unit Table Tools Required for Installation not suppliedGeneral Optional Copper Tubing KitAdditional Materials Required for Installation Installation Site SelectionSolid base must not cover the hole of the bottom plate  $/,8,3?,4508-25=  $/,04.3?-8,,D,4+89 Precautions for Installation in a Snowy Area Countermeasures against snow and wind Unit inch $/,-8544+5/90+,9398,30456,4 Required space around the outdoor unit4922054=0/041,9-*04.52,9 27-5/8 11-5/8 Air Intake 25/32 13/32 13-3/8 14-31/32  #04.2,4004922054  9*2,9545/90+,9 4522,8/4/,/,0./5-/,5+55840Obstacles to the front and rear of unit Installation in front-rear rows #04.2,4004922054  9*2,9545/90+,9Trical wiring or conduits are How to Install the Indoor UnitRemove the Rear Panel from the Unit Make a HoleIf Wooden Wall Install the Rear Panel on the WallIf Block, Brick, Concrete or Similar Type Wall Hole DiaHow to replace the grille Removing and Installing the GrilleHow to remove the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringWire Size and Length Wiring Instructions for Inter-unit Connections  For stranded wiring How to connect wiring to the terminal For Indoor UnitFor Outdoor Unit  For solid core wiring or F-cable  Right-side tubing MountingDrain cap Switching drain hose and drain cap Left-side tubing Tubing and wiring to the out Do not supply power toTo unmount indoor unit Frame Fastening MethodWiring Instructions for the Outdoor Unit How to Install the Outdoor UnitRouting the Tubing and Wiring Cover BTo 0.5 mm Adjust so that the amount of tube Flaring Procedure with a Flare ToolRefrigerant Tubing Use of the Flaring MethodFinishing the Installation Connecting Tubing between Indoor and Outdoor UnitsInsulation of Refrigerant Tubing Taping the TubesAir Purging Attempting to turn the valve Be sure to completely insertHex wrench before How to Test Run the Air Conditioner  Pump Down  Basic Functions of the Service ValvesRemote Controller Installation Position  Service Valve ConnectionsAddress Setting of the Remote Controller Address SwitchDC1111-0

CS-KE30NKU, CS-KE36NKU, CU-KE30NKU, CU-KE36NKU specifications

The Panasonic CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU air conditioning units represent the brand's commitment to delivering high-performance cooling solutions backed by innovative technologies. These units cater to both residential and commercial applications, ensuring users experience maximum comfort throughout the year.

One of the standout features of these models is their energy efficiency. Both units are equipped with advanced inverter technology, which allows for variable speed operation. This means they can adjust their power output according to the room's cooling needs, reducing energy consumption and minimizing electric bills while maintaining a consistent temperature. The models boast impressive SEER (Seasonal Energy Efficiency Ratio) ratings, making them environmentally friendly options.

Panasonic's nanoe-G technology is another remarkable feature incorporated into these models. This technology helps to purify the air by generating hydroxyl radicals, which eliminate airborne particles, odors, and harmful bacteria. This results in a healthier indoor environment, conducive to both comfort and well-being. The air purification aspect not only enhances the air quality but also extends the lifespan of the HVAC system by reducing the buildup of dust and contaminants.

In terms of user convenience, both the CU-KE and CS-KE series are equipped with programmable timers, allowing users to set their desired operation schedules. They also come with a remote control for ease of use, enabling adjustments from a distance. The installation process is straightforward, and the sleek design blends seamlessly with various interior aesthetics, making them a suitable choice for any room.

Durability is a key characteristic of Panasonic air conditioning units, and the CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU are designed to withstand varying environmental conditions. Their robust construction ensures reliability and performance over the years. Additionally, both models come with a quiet operation feature that minimizes noise levels, allowing for comfortable use without disturbing daily activities.

In summary, the Panasonic CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU are exceptional air conditioning units that combine energy efficiency, innovative purification technology, user-friendly features, and robust durability. These models are an ideal investment for anyone seeking a reliable and high-performance cooling solution.