Panasonic CS-KE36NKU, CU-KE36NKU, CU-KE30NKU Using the 1-HOUR OFF Timer, Tips for Energy Saving

Page 74

4. How to set daily ON/OFF repeat timer

(Example) To start operation at 7:10 am. and stop the air conditioner at 11:00 am.

10:30 pm.

7:10 am.

11:00 am.

Present time

ON

OFF

 

 

 

 

 

 

 

 

 

 

Operation

Indication

 

 

1. Set the timer ON/OFF times

The present time 10:30 pm. and

as shown in 2-1, 2, 3 and 3-1,

are displayed.

2, 3.

 

 

 

NOTE

The ON/OFF combination timer uses the current time as the reference, and it is activated starting from whichever set time comes first.

With the ON/OFF combination timer, the settings are repeated every day.

You can check the timer ON/OFF times after you have set them by pressing the ON TIME and OFF TIME setting buttons.

To cancel a timer program

Press the CANCEL button.

When either an ON or OFF timer is to be canceled, press the button corresponding to the timer whose program is to be canceled, and then press the CANCEL button.

NOTE

The airflow direction, fan speed and temperature setting can be changed after a timer program has been set even when the unit is stopped. Even when operation is stopped during an ON timer program, the unit will start operating when the set time is reached provided that the program is not canceled.

When the ON timer and OFF timer are set to the same time, the timer operates as if it is turned off.

USING THE 1-HOUR OFF TIMER

1. 1-Hour OFF Timer

This function causes the unit to operate for one hour and then stop, regardless of whether the unit is on or off when this button is pressed.

The indicator in the display indicates that this function is operating.

Setting procedure:

Regardless of whether the unit is operating or stopped, press the 1 HR. TIMER button.

appears in the display.

Cancellation procedure:

Press the ON/OFF operation button to turn the unit off, wait for the unit to stop operating, and then press the ON/OFF operation button again.

The 1-Hour Timer function is now cancelled and the unit operates normally.

NOTE

If, while the 1-Hour Timer function is operating, the 1HR. TIMER button is pressed once to cancel the function and then again, the unit continues to operate for one hour from that point in time and then stops.

It is not possible to use the OFF Timer and 1-Hour OFF Timer together. Whichever function is set last takes precedence. If the 1 HR. TIMER button is pressed while the TIMER OFF function operates, the OFF Timer is cancelled and the unit will stop operating one hour later.

2.Operation together with the daily ON/OFF repeat timer

The 1-Hour OFF Timer setting is given priority over the DAILY ON/ OFF REPEAT setting.

TIPS FOR ENERGY SAVING

Avoid

Do not block neither the air intake nor the air outlet. It may cause less performance, and may leads to malfunctions.

Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls and ceiling of the room are warmed by the sun, it will take longer to cool the room.

Do

Always try to keep the air filter clean. (Refer to “CARE AND CLEANING”.) A clogged filter will impair the performance of the unit.

To prevent conditioned air from escaping, keep windows, doors and any other openings closed.

14

Image 74
Contents Outdoor Model No Product Code No CS-KE30NKU + CU-KE30NKU CS-KE36NKU + CU-KE36NKUIndoor Model No Product Code No 852 360Safety Precautions Prohibit Table of Contents Checking Electrical Components Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeIndoor Unit SpecificationsUnit Specifications Outdoor Unit208V CS-KE36NKU 21.9 19.9 Indoor Unit CS-KE30NKU Major Component SpecificationsIndoor Unit Indoor Unit CS-KE36NKU CB-CS-KE36NKUBoard Outdoor UnitOutdoor Unit CU-KE30NKU CompressorOutdoor Unit CU-KE36NKU Other Component Specifications Dimensional Data Inchmm 194-00-1 Unit Indoor Unit CS-KE30NKU Outdoor Unit CU-KE30NKU Refrigerant Flow DiagramRefrigerant Flow Diagram Indoor unit Outdoor unitTemperature Charts Performance DataHigh pressure performance chart Indoor Unit CS-KE36NKU Outdoor Unit CU-KE36NKU Discharge 9535 8630 Indoor CS-KE30NKU Power Supply 230V Single Phase 60Hz Cooling CapacityCooling Capacity CU-KE30NKU34,000 BTU/h Cooling Capacity Low Ambient Outdoor30,900 30,870 30,800 30,710 30,590 30,400 30,210 TH Total Heating Capacity BTU/h Power Supply 230V Single Phase 60Hz Heating CapacityHeating Capacity 36,000 BTU/h Air Throw Distance Charts Cooling Voltage230V Cooling Electrical CharacteristicsElectrical Data Heating650 Electric Wiring Diagrams 8FA2-5251-12400-18FA2-5251-15200-0 ControllerEmergency operation FunctionsOperation Functions Auto cooling/heating operationTimer backup Lamp colorsOperation Sound Switching Procedure to Noise Reducing ControlNoise Reducing Control Outdoor Unit Description of function Maximum Current Value Change ProcedureMaximum Current Value Change Function CU-KE36NKUOverload prevention during heating Compressor discharge temperature controlProtective Functions Freeze preventionReverse-Cycle Defrosting Defrost detection and releaseCT Peak current cut-off control Method of Self-Diagnostics Troubleshooting Before Calling for ServicePrecautions before Performing Inspection or Repair Self-diagnostics Lamps Diagnosis ContentsReplace the circuit board or the fuse NormalReplace the controller Checking the indoor unit Control Check items unit operation Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Off Blinking Illuminated Serial Communication Error Identification ProcedureAlarm Code E05 Before the OperationFrom the previous page a Alarm Code E07/P04/P05/P20/P27 Trouble Diagnosis of Fan Motor Indoor Fan MotorPin 1 Vcc brown Outdoor Fan MotorPin 3 Gnd blue Pin 2 PG whiteElectromagnetic interference Noise Malfunction and Electromagnetic InterferenceNoise malfunction Locations most susceptible to noise Trouble CorrectionMeasurement of Insulation Resistance Power Supply CordChecking Electrical Components Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy What is New Refrigerant R410A? Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A CharacteristicsChecklist before Servicing Tubing Installation Procedures Tools Specifically for R410AProcedure for Replacing Compressor Case of Compressor MalfunctionExample Configuration and characteristics of cylindersAmount in the charging cylinder is less than 20% To prevent the compositionRecharging Case Refrigerant is LeakingWelding leaking points Retro-Fitting Existing Systems When Tubes are ExtendedCharging Additional Refrigerant Use of Existing UnitsAppendix a Operating Instructions CS-KE30NKU CS-KE36NKUSafety Precautions FeaturesContents Product InformationElectrical Requirements Installation LocationSafety Instructions AvoidNames of Parts Unit Display and Operation ButtonRemote Controller Display SymbolsRemote Controller Mode selector button HR. Timer button 1-HOUR OFF TimerTemperature setting buttons Temp High Power button32 x 13/16 Using the Remote ControllerACL button 20 mmOperation with the Remote Controller Automatic OperationAutomatic fan speed Cooling and DRY ModeHeating Mode Manual fan speedHigh Power Mode Unoccupied Indication StatusSpecial Remarks Setting the Timer Operation Indication1030 pm 710 am 1100 am Present time Using the 1-HOUR OFF TimerTips for Energy Saving Adjusting the Airflow Direction When the air conditioner is not runningRemoving and remounting the front panel How to replace the filterCleaning the main unit and Remote Controller Washing the front panel with waterTrouble Possible Cause Remedy Wired Remote ControllerOperating Range Specifications Model No Outdoor Unit Indoor UnitPage 852-6-4190-587-00-0 Installation Instructions Split System Air Conditioner ContentsPlease Read Before Starting Fins of the outdoor unit. You may get injured AccidentallyGeneral Tools Required for Installation not suppliedAccessories Supplied with Unit Table Optional Copper Tubing KitInstallation Site Selection Additional Materials Required for InstallationSolid base must not cover the hole of the bottom plate  $/,8,3?,4508-25=  $/,04.3?-8,,D,4+89 Precautions for Installation in a Snowy Area Countermeasures against snow and wind Unit inch $/,-8544+5/90+,9398,30456,4 Required space around the outdoor unit4922054=0/041,9-*04.52,9 27-5/8 11-5/8 Air Intake 25/32 13/32 13-3/8 14-31/32 4522,8/4/,/,0./5-/,5+55840  #04.2,4004922054  9*2,9545/90+,9 #04.2,4004922054 Installation in front-rear rowsObstacles to the front and rear of unit  9*2,9545/90+,9Remove the Rear Panel from the Unit How to Install the Indoor UnitTrical wiring or conduits are Make a HoleIf Block, Brick, Concrete or Similar Type Wall Install the Rear Panel on the WallIf Wooden Wall Hole DiaHow to replace the grille Removing and Installing the GrilleHow to remove the grille Wiring Instructions General precautions on wiring Shape the Indoor Side TubingWire Size and Length Wiring Instructions for Inter-unit Connections  For stranded wiring How to connect wiring to the terminal For Indoor UnitFor Outdoor Unit  For solid core wiring or F-cable Mounting  Right-side tubingDrain cap Switching drain hose and drain cap Left-side tubing To unmount indoor unit Do not supply power toTubing and wiring to the out Frame Fastening MethodRouting the Tubing and Wiring How to Install the Outdoor UnitWiring Instructions for the Outdoor Unit Cover BRefrigerant Tubing Flaring Procedure with a Flare ToolTo 0.5 mm Adjust so that the amount of tube Use of the Flaring MethodInsulation of Refrigerant Tubing Connecting Tubing between Indoor and Outdoor UnitsFinishing the Installation Taping the TubesAir Purging Attempting to turn the valve Be sure to completely insertHex wrench before How to Test Run the Air Conditioner  Basic Functions of the Service Valves  Pump Down Service Valve Connections Remote Controller Installation PositionAddress Switch Address Setting of the Remote ControllerDC1111-0

CS-KE30NKU, CS-KE36NKU, CU-KE30NKU, CU-KE36NKU specifications

The Panasonic CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU air conditioning units represent the brand's commitment to delivering high-performance cooling solutions backed by innovative technologies. These units cater to both residential and commercial applications, ensuring users experience maximum comfort throughout the year.

One of the standout features of these models is their energy efficiency. Both units are equipped with advanced inverter technology, which allows for variable speed operation. This means they can adjust their power output according to the room's cooling needs, reducing energy consumption and minimizing electric bills while maintaining a consistent temperature. The models boast impressive SEER (Seasonal Energy Efficiency Ratio) ratings, making them environmentally friendly options.

Panasonic's nanoe-G technology is another remarkable feature incorporated into these models. This technology helps to purify the air by generating hydroxyl radicals, which eliminate airborne particles, odors, and harmful bacteria. This results in a healthier indoor environment, conducive to both comfort and well-being. The air purification aspect not only enhances the air quality but also extends the lifespan of the HVAC system by reducing the buildup of dust and contaminants.

In terms of user convenience, both the CU-KE and CS-KE series are equipped with programmable timers, allowing users to set their desired operation schedules. They also come with a remote control for ease of use, enabling adjustments from a distance. The installation process is straightforward, and the sleek design blends seamlessly with various interior aesthetics, making them a suitable choice for any room.

Durability is a key characteristic of Panasonic air conditioning units, and the CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU are designed to withstand varying environmental conditions. Their robust construction ensures reliability and performance over the years. Additionally, both models come with a quiet operation feature that minimizes noise levels, allowing for comfortable use without disturbing daily activities.

In summary, the Panasonic CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU are exceptional air conditioning units that combine energy efficiency, innovative purification technology, user-friendly features, and robust durability. These models are an ideal investment for anyone seeking a reliable and high-performance cooling solution.