Omega DP26-RTD manual S3 Jumper Functions

Page 22

3.2 MAIN BOARD POWER JUMPERS (Continued)

S2 jumpers are for sensor break indications:

*S2A jumper is not used

*S2B jumper is for positive sensor break on input 1 (i.e. heating)

*S2C jumper is for positive sensor break on input 2 (i.e. heating)

*S2D is not used

S3 jumpers are used for the following (refer to Table 3-1):

*To enable or disable the front panel push-buttons

*To allow for an extremely low resistance load for analog output

*To disable the MENU button

*To perform calibration procedure

Test pins TP1 - TP11 are for testing purposes. Do not use as reading errors may result.

Table 3-1 S3 Jumper Functions

Jumper Description

S3-A Install to enable front panel push-buttons.

Remove to disable all front panel push-buttons

S3-B Removed. Install for factory calibration only.

S3-C Normally removed. Install for analog voltage output when load is less than 1 Kohm impedance. Care should be taken when installing this jumper.

S3-D Removed. Not used.

S3-E If installed without S3-B, the MENU button locks out.

While in run mode, if you press the MENU button, the display shows “LOCK".

14

Image 22
Contents User’s Guide Servicing North America Standard Procedures PrefacePage Iii Table of Contents Selecting Output Configuration OT.CF List of Figures Introduction UnpackingSafety Considerations EMC ConsiderationsAbout the Meter Standard FeaturesDescription Available Accessories Add-On OptionsFront of the Meter Shows the location of each part of the front of the meterMeter Buttons Setpts ButtonReset Button Front Panel Lockout Push Button Lockout Jumper LockoutConnector label ac Powered and dc Powered detail Back of the MeterBack of the Meter Connector Description Disassembly Disconnect the power supply before proceedingGetting Started Main Board Power JumpersRATING/PRODUCT Label Main Board Jumper Positions S3 Jumper Functions Mounting the Meter PlcsConnecting Sensor Input Through 3-7 illustrate how to connect you power sensorsConnecting Main Power Main Power Connections ac powered unitMain Power Connections dc powered unit Analog and Relay Output Connections11 Analog Output Connections Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Menu /DEV Reset DescriptionDisplay /DEV Setpoint Configuration Displays SetpointSpecifications Signal InputInput Power Information Analog Output if applicable Side View TOP View Factory Preset Values Menu Item Factory Preset ValuesCE Approvals Information WARRANTY/DISCLAIMER OMEGA…Of Course