Scott 4.5, 3, 2.2 manual Control Console

Page 21

MANUAL

ALARM BUTTON (RED INDICATOR)

WITHDRAW BUTTON (BLUE INDICATOR)

RED SIGNAL

LIGHT

GREEN SIGNAL LIGHT

WITHDRAW

MANUAL

RESET

BUTTON (YELLOW INDICATOR)

PUSH 2X

TO RESET

ALARM

CONSOLE

DISPLAY

FIGURE 5

THE CONTROL CONSOLE

OPERATIONAL INSPECTION of your respirator. If, during the inspec- tion any malfunction of the respirator or the SEMS PDA Portable Unit is noted, remove the respirator from service and tag for repair by au- thorized personnel.

1.While performing the visual inspection of the respirator inspect all SEMS PDA Portable Unit enclosures, lenses, and wire conduits for cracks, wear or other damage. If damage is noted, remove respirator from service and tag respirator for repair by qualified personnel.

2.Check the operation of the SEMS PDA distress alarm in accor- dance with the REGULAR OPERATIONAL INSPECTION section of this instruction for the SEMS PDA distress alarm installed on your SCBA.

3.With an operating Base Station, verify that the SEMS PDA Por- table Unit initializes and logs-in to the Base Station. When testing the SEMS PDA alarms, verify that the Portable Unit and Base Station are communicating with each other properly.

4.Verify that the batteries are properly installed and that there is no “BATT” indication on the display.

5.Send an “EVAC’ signal to the SEMS PDA Portable Unit and check the response. Verify that both the ALL-CALL and the Selective Evacuation signals are properly received by the Portable Unit.

6.When testing the “LOW AIR” alarm operation, verify that the proper

signal is transmitted to the Base Station.

On a regular basis established by your respiratory protection program, each SEMS Base Station must be inspected and tested for proper operation. Each of the functions defined in the USE OF THE SEMS BASE STATION section of this instruction must be checked and veri- fied to be operating properly. If any malfunction is found, remove the Base Station from service and tag for repair by authorized personnel.

WARNING

FOLLOW REGULAR OPERATIONAL INSPEC- TION PROCEDURE EXACTLY. IF THE SEMS PORTABLE UNIT OR BASE STATION DOES NOT OPERATE AS DESCRIBED OR IF ANY OTHER OPERATIONAL MALFUNCTION IS NOTED, DO NOT USE THE RESPIRATOR. USE OF A MALFUNCTIONING RESPIRATOR M AY R E S U LT I N S E R I O U S I N J U RY O R DEATH.

21

Image 21
Contents Sems Description Base Station Sensor ModulePage Detecting and Avoiding Radio Frequency Interference Keep Radio Antennas AT Least SIX 6 Inches from These AreasRFI Warning Areas Radio Frequency Interference RFI FCC NoticeIntrinsically Safe Listing ProgrammingBasic Functions of the Sems Equipment Portable Unit Operation of the Sems PDA Distress AlarmFull Alarm PRE AlarmTurning OFF the Sems PDA Distress Alarm Manual AlarmBattery Test Other Operational Features END of Service Time IndicatorUSE of the Sems PDA Portable Unit Evacuation Base Station USE of the Sems Base StationPage Event LOG Screen Event LOGSample Event LOG Regular Operational Inspection Regular Operational Inspection On Next Inspection of Sems PDA Distress AlarmInspection of Sems PDA Portable Unit Control Console Battery Replacement Sems PDA Distress Alarm Portable UnitBattery Cover Battery Compartment and Cover Seal Battery Replacement on NextCheck Your Work Control Console Battery Battery Orientation AS Shown Battery Compartments on Base StationMaintenance Does When the Sems PDA IT Indicates That Distress Alarm isSound Levels Performance SpecificationsRev a 6/03