4532 | Operation and Description of Instrument Function |
|
|
VH80: Present Error
Item type: read only
Display of current error message. One of the following codes will be indicated:
Error code
•0: No error presence
•1: Common line open
•2: undetermined
•3: #1 element open
•4: #1 element short
•5: #2 element open
•6: #2 element short
•7: #3 element open
•8: #3 element short
•9: #4 element open
•10: #4 element short
•11: #5 element open
•12: #5 element short
•13: #6 element open
•14: #6 element short
•23: #0 element over range
•24: Memory defect (ROM)
•29: Element exposed (liquid level below #1 element position)
•30: undetermined
•31: undetermined
•41: Memory defect (RAM)
•42: Memory defect (EEROM)
VH81 Temperature Unit
Item type: select
Default: °C
Selection: C, F, K
Selection of temperature display unit. Based on universal HART setting, °C(HART code: 32), °F(HART code: 33) and °K(HART code: 35) are available.
Note! Selection of temperature display unit only applies to reply data from 4532 ATC. Data transmission from host gauge (4590 TSM or 6000 Series Servo Tank Gauge) to 4532 ATC must be performed by °C unit only (terminology of HART command 133)
Varec, Inc. | 41 |