Varec 4532 manual Technical data at a glance

Page 61

4532

Technical data

 

 

12 Technical data

Technical data at a glance:

Application

Application

The 4532 ATC performs precise liquid and gas phase average temperature measurement in bulk storage tank applications.

Standard 2" flange installation

Overall 18.5m temperature measurement range

Function and system design

Measuring principle

Temperature measurement

Up to 6 elements spaced evenly over the length of the flexible tube.

Pt100, Class A elements

Input

Measured variable

Temperature measurement

 

Temperature conversion range: -20 ~ +100°C

 

 

Measuring range

-20 ~ +100°C (-4 ~ 212°F)

 

 

Output

 

 

 

Output signal

• HART protocol (multi drop HART loop connection)

 

 

Signal on alarm

Error information can be accessed via the following interfaces and

 

transmitted digital protocol (refer to the operation manuals on

 

following instruments)

 

• Tank Side monitor 4590 TSM

 

• 6000 Series Servo Tank Gauge

 

 

Auxiliary energy

 

 

 

Load HART

Minimum load for HART communication: 250 W

 

 

Cable entry

see technical document

 

 

Supply voltage

16 ~ 30VDC (on multi drop HART loop)

 

 

Current consumption

Less than 6mA

 

 

Performance characteristics

 

 

Reference operating

• temperature = +25 °C (77 °F) ±5 °C (9 °F)

conditions

• pressure = 1013 mbar abs. (14.7 psia) ±20 mbar (0.3 psi)

 

• relative humidity (air) = 65 % ± 20%

 

 

Maximum measured

Typical statements for reference conditions, include linearity,

error

repeatability, and hysteresis:

 

• Linearity:

 

• Temperature: ±0.15°C (0.27°F) + number of element deviation

 

(based on IEC class A standard)

 

 

Varec, Inc.

51

Image 61
Contents Installation Page Copyright Disclaimer of Warranties Safety Precaution Definitions Safety Precautions Average Temperature/Water Bottom Sensor and Converter Contents Operation and Description of Instrument Function Index Varec, Inc Contents Introduction Installation and operation overviewIntroduction Software historyHart System functional diagramSafety instructions Wiring Power supplyGrounding ReturnDirect voltage Safety instructions Device designation Nameplate IdentificationScope of delivery CE marks, declaration of conformity Design, dimensions InstallationUnpacking Recommended procedure Incorrect procedure Flexible tubeSpecial conditions for safe use Installation InstructionsInstallation Mounting instruction MountingTop anchor method Mounting on a fixed roof tankTensioning wire mounting Thermo well application Thermo well methodFlexible tube is stabilized by an anchor weight Anchor weight methodAnchor weight mounting Mounting on a floating roof tank Thermo well method 10Guide ring and anchor weight application Guide ring and anchor weight methodMounting Terminal Connection 1 4532 ATC terminal Wiring3 4590 TSM i.s. terminal 2 6000 Series Servo Tank Gauge terminal4532 ATC Grounding Wiring Operating Device set up 4590 TSMLocal Hart connection As a Varec tank gauging instrument As a standalone generic Hart instrumentDevice set up 6000 Series Servo Tank Gauge 4532 ATC specific parameter set up on the 4590 TSM2 4532 ATC configuration on 6000 Series Servo Tank Gauge Preparation of 6000 Series Servo Tank GaugeGVH447 Reference Zero GVH480 DiagnosticGVH449 Reference GVH450~459 Temp No.1~10Operating Operation and Description of Instrument Function Temperature measurement Primary values VH00 ~ VH09Hart Device designation Device DataElement Temperature 2 VH20 ~ VH29 Element Temperature 1 VH10 ~ VH15Advanced VH28 Lower Limit SpotVH29 Upper Limit VH46 Hysteresis Width Item type read and write Default 10mmVH49 Liquid Offset VH48 Gas OffsetVH53 Element Point Item type select Default WB Adjustment and Operation Power VH60 ~ VH69VH55 Element Volume Item type read and write Range 1 ~ WB primary and Advanced temp VH50 ~ VH59VH71 Zero Adjust Temperature Adjustment VH70 ~ VH79VH72 Adjust Span VH69 Ref VoltageVH74 Position VH73 TemperatureVH75 Resistance VH76 Resistance AdjVH79 Protect Code Error code VH80 Present ErrorVH81 Temperature Unit VH83 No. of Preambles VH82 Element NumberVH84 Distance Unit VH85 Kind of IntervalVH88 Short Error Device setting 2 VH90~VH99VH89 Open Error VH90 Device ID Number Item type read and write DefaultVH94 Polling Address VH92 Error Dis. SelVH95 Manufacture ID VH96 Software VersionExterior cleaning MaintenanceRepairs Repairs to Ex-approved devicesGVH ReplacementSystem error messages Troubleshooting1Spare Parts Spare partsAnchor weight Tall profile AccessoriesAnchor weight Low profile 3Wire hook dimension Wire hook, Top anchorTechnical data at a glance Technical dataTechnical data Process connection SUS304 Order StructureOrder Structure Declaration of Contamination Form Declaration of ContaminationDeclaration of Contamination Form Index Index 4532 Your official representative Your offical representative