Carrier TP-PRH-A, TP-NRH-A installation instructions Backplate Mounting

Page 14

2.Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be leveled for proper operation) and mark wall through 4 mounting holes. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors. See Fig. 6.

A07165

Fig. 6 − Backplate Mounting

3.Drill four 3/16−in. mounting holes in wall where marked. Thermidistat Control may be mounted to a standard junction box, if desired. Hole pattern on Thermidistat Control mounting base matches junction box mounting holes.

4.Secure rear plastic mounting base to wall with 4 screws and anchors provided. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors. Make sure all wires extend through hole in mounting base.

5.Adjust length and routing of each wire to reach proper connector block and terminal on mounting base with 1/4−in. (6 mm) extra wire.

14

Image 14
Contents USA Programmable ControlDesigned and Assembled Table of Contents Safety ConsiderationsIntroduction Installation Considerations PowerModels Humidify Equipment and ConnectionsOutdoor Temperature Sensor TSTATCCSEN01−B Dehumidify Equipment and ConnectionsWiring Remote Indoor Temperature SensorTwo−Piece Thermidistat Control Configuration Installation − TP−PRH−A Carton Contents− TP−NRH−A Carton Contents Thermidistat Control LocationInstall Thermidistat Control Unit Damage Hazard Two−Piece Installation Environmental Hazard− Press Tabs to Remove Backplate − Backplate Mounting − Control Module Wiring Guide − Secure Wires to Terminal Strip − Attach Display to Backplate − Equipment Control Module on Equipment − Standoff − Cover on Equipment Control Module Single−Piece Installation − Equipment Control Module − Reattach Display Module Set Thermidistat Control Configuration Page To Enter Configuration Mode Option 01 Equipment Type Configuration Options -SelectionOption 02 Clean Filter Timer Option 03 Fahrenheit/Centigrade Option 04 Fan G On With W/W1Option 07 Zoning Option 08 Auxiliary Heat Lockout TemperatureOption 06 Cooling Lockout Below 55F/13C Option 10 Reversing Valve Option 13 Room Air Temperature Offset Adjust Option 11 Deadband Setting Between Heat & CoolOption 12 Smart Recovery Option 14 Humidity Display Offset AdjustOption 16 Maximum Cycles Per Hour Option 17 Time Between Equipment StagesOption 18 Backlight Configuration Option 19 Dry Contact Configuration programmable models onlyOption 20 Outdoor Air Temperature Offset Adjustment Option 21 Keypad Lockout programmable models onlyOption 21 Keypad Lockout non−programmable models only Page Option 26 Minimum Cooling Setpoint Option 29 Humidifier Pad Reminder Option 27 Maximum Heating SetpointOption 28 UV Light Reminder Option 30 Programmable Fan programmable models only Option 33 Single or Two−Piece Installation Option 41 Variable Speed Blower Option 34 − Hybrid Heat Furnace LatchOption 40 Humidify Fan Option 42 Variable Speed Super Dehumidification Option 43 Intelligent Heat StagingOption 44 Super Comfort Heat Option 99 Reset to Factory Defaults System START−UP and Checkout Final Settings Energy Star Default SchedulePage Humidification Selections Humidity Control FeaturesHumidification Additional Humidify Comments To Select Humidification programmableTo Select Humidification non−programmable Dehumidification − Auto Humidity Additional Dehumidify Comments Vacation programmable models only Dehumidify Output and Equipment ConnectionsVacation Humidification Vacation Setpoints Default ValuesVacation Setpoints Vacation DehumidificationTen−Minute Staging Timer TimersCycle Timer Operational InformationDefrost Three−Minute Minimum on TimeHumidify and Dehumidify Indicators Equipment On IndicatorsHeat/Cool Setpoints Desired Temperature Emergency Heat ModeProgrammable Fan programmable models only Dry ContactTemperature Offset After Power Cycle RelaysTroubleshooting Error CodesPage Equipment Configuration Outputs − Equipment Configuration Outputs Wiring Diagrams − Display to Equipment Control Module Connection− FV/FK Fan Coil with 2−Stage Heat Pump − Typical Fan Coil with Heat Pump HUM − FV/FK Fan Coil w/2−Stage Air Conditioner − Typical Fan Coil with Air Conditioner A09169 − FV/FK Fan Coil with 1−Stage Heat Pump − Typical Fan Coil Heating Only HUM − FV/FK Fan Coil with 1−Stage Air Conditioner − Typical Fan Coil Cooling Only A09121 − Single−Stage Furnace with Heat Pump Hybrid Heat COM − Single−Stage Furnace with Single−Speed Air Conditioner A09125 − Single−Stage Furnace Heating Only A09127 − Single−stage Furnace with Air Conditioner and Split Power Thermidistat Control Configuration Record Mode SettingsConfiguration Options Configuration Options Option Fan Humidity Variable Speed Blower Catalog No TP-PRH-4SI