To Select Dehumidification (programmable − between NORMAL, COOL TO, and OFF)

Press the soft key below the dehumidify icon button to bring up dehumidify selections. Dehumidify options are only available when in Cooling mode. When system is in AUTO mode, dehumidify options are available if the last system operation was a call for cooling.

To Select Dehumidification (non−programmable − between NORMAL, COOL TO, and OFF)

Press the features button three times. The first press displays the outdoor air temperature, the second press displays the humidify options and the third press will display the current dehumidify selections.

The mode button is used to cycle through the dehumidify selections.

Additional Dehumidify Comments

Dehumidification can be enhanced (with some efficiency loss) by turning blower off immediately at the end of each cooling cycle (eliminating normal 90 sec blower off delay). Where maximum humidity removal is desired, this should be done. Fan coils have the capability of removing this off delay. On FK or FV Fan Coils, set delay tap to 0/0. On standard fan coils, a jumper can be cut to disable off delay. Refer to fan coil Installation Instructions for details. If FAN is set for continuous operation (fan On icon displayed), G output is turned off for 5 minutes at the end of each cooling cycle as long as dehumidify demand exists.

Like humidify, dehumidify actions are initiated when humidity is 1% above setpoint and are terminated when humidity drops to 1% below setpoint. This prevents unnecessary toggling of dehumidify actions when humidity is near setpoint.

52

Image 52
Contents Designed and Assembled Programmable ControlUSA Table of Contents Safety ConsiderationsIntroduction Installation Considerations PowerModels Humidify Equipment and ConnectionsOutdoor Temperature Sensor TSTATCCSEN01−B Dehumidify Equipment and ConnectionsTwo−Piece Thermidistat Control Configuration Remote Indoor Temperature SensorWiring Installation − TP−PRH−A Carton Contents− TP−NRH−A Carton Contents Thermidistat Control LocationInstall Thermidistat Control Unit Damage Hazard Two−Piece Installation Environmental Hazard− Press Tabs to Remove Backplate − Backplate Mounting − Control Module Wiring Guide − Secure Wires to Terminal Strip − Attach Display to Backplate − Equipment Control Module on Equipment − Standoff − Cover on Equipment Control Module Single−Piece Installation − Equipment Control Module − Reattach Display Module Set Thermidistat Control Configuration Page To Enter Configuration Mode Option 02 Clean Filter Timer Configuration Options -SelectionOption 01 Equipment Type Option 03 Fahrenheit/Centigrade Option 04 Fan G On With W/W1Option 06 Cooling Lockout Below 55F/13C Option 08 Auxiliary Heat Lockout TemperatureOption 07 Zoning Option 10 Reversing Valve Option 11 Deadband Setting Between Heat & Cool Option 12 Smart RecoveryOption 13 Room Air Temperature Offset Adjust Option 14 Humidity Display Offset AdjustOption 16 Maximum Cycles Per Hour Option 17 Time Between Equipment StagesOption 18 Backlight Configuration Option 19 Dry Contact Configuration programmable models onlyOption 20 Outdoor Air Temperature Offset Adjustment Option 21 Keypad Lockout programmable models onlyOption 21 Keypad Lockout non−programmable models only Page Option 26 Minimum Cooling Setpoint Option 28 UV Light Reminder Option 27 Maximum Heating SetpointOption 29 Humidifier Pad Reminder Option 30 Programmable Fan programmable models only Option 33 Single or Two−Piece Installation Option 40 Humidify Fan Option 34 − Hybrid Heat Furnace LatchOption 41 Variable Speed Blower Option 42 Variable Speed Super Dehumidification Option 43 Intelligent Heat StagingOption 44 Super Comfort Heat Option 99 Reset to Factory Defaults System START−UP and Checkout Final Settings Energy Star Default SchedulePage Humidification Humidity Control FeaturesHumidification Selections To Select Humidification non−programmable To Select Humidification programmableAdditional Humidify Comments Dehumidification − Auto Humidity Additional Dehumidify Comments Vacation programmable models only Dehumidify Output and Equipment ConnectionsVacation Setpoints Default Values Vacation SetpointsVacation Humidification Vacation DehumidificationTimers Cycle TimerTen−Minute Staging Timer Operational InformationDefrost Three−Minute Minimum on TimeEquipment On Indicators Heat/Cool Setpoints Desired TemperatureHumidify and Dehumidify Indicators Emergency Heat ModeProgrammable Fan programmable models only Dry ContactTemperature Offset After Power Cycle RelaysTroubleshooting Error CodesPage Equipment Configuration Outputs − Equipment Configuration Outputs Wiring Diagrams − Display to Equipment Control Module Connection− FV/FK Fan Coil with 2−Stage Heat Pump − Typical Fan Coil with Heat Pump HUM − FV/FK Fan Coil w/2−Stage Air Conditioner − Typical Fan Coil with Air Conditioner A09169 − FV/FK Fan Coil with 1−Stage Heat Pump − Typical Fan Coil Heating Only HUM − FV/FK Fan Coil with 1−Stage Air Conditioner − Typical Fan Coil Cooling Only A09121 − Single−Stage Furnace with Heat Pump Hybrid Heat COM − Single−Stage Furnace with Single−Speed Air Conditioner A09125 − Single−Stage Furnace Heating Only A09127 − Single−stage Furnace with Air Conditioner and Split Power Thermidistat Control Configuration Record Mode SettingsConfiguration Options Configuration Options Option Fan Humidity Variable Speed Blower Catalog No TP-PRH-4SI