Carrier TP-NRH-A, TP-PRH-A Configuration Options -Selection, Option 01 Equipment Type

Page 27

flashing is changed by using the UP/DOWN buttons. All changes made are saved at the time of selection and will be saved in the event of the 3 minute time−out or when installer exits from configuration menu.

Configuration Options —Selection

Option 01 — Equipment Type

Range: H2, A2, HP, AC, hh, h2, H, C

H2 — operates a two−speed heat pump with a fan coil HP — operates a single−speed heat pump with a fan coil A2 — operates a two−speed AC with a fan coil or furnace AC — operates a single−speed AC with a fan coil or furnace

hh— operates a single−speed heat pump with a furnace

h2 — operates a two−speed heat pump with a furnace

H— operates a heat−only system. Furnace or fan coil only; no outdoor unit.

C— operates a cool only−system. Outdoor AC unit with an indoor fan coil with no strip heaters.

Default is H2.

Option 02 — Clean Filter Timer

Select hours of blower operation (heating, cooling, or fan) before CHECK FILTER icon is displayed. With OF selected, icon will never come on, disabling this feature. Time selection can range from 800 to 7200 hr by selecting numbers 1 through 9. (Time is 800 X number selected.) Default is 4 (3200 hr).

Recommended selections are disposable filter−800 to 2400 hr, media filter−2400 to 3200 hr, or electronic air cleaner−1600 to 2400 hr of blower operation. For higher efficiency filter, please consult filter’s Installation Instruction for details.

27

Image 27
Contents Programmable Control Designed and AssembledUSA Safety Considerations Table of ContentsIntroduction Power Installation ConsiderationsHumidify Equipment and Connections ModelsDehumidify Equipment and Connections Outdoor Temperature Sensor TSTATCCSEN01−BRemote Indoor Temperature Sensor Two−Piece Thermidistat Control ConfigurationWiring − TP−PRH−A Carton Contents InstallationThermidistat Control Location − TP−NRH−A Carton ContentsInstall Thermidistat Control Unit Damage Hazard Environmental Hazard Two−Piece Installation− Press Tabs to Remove Backplate − Backplate Mounting − Control Module Wiring Guide − Secure Wires to Terminal Strip − Attach Display to Backplate − Equipment Control Module on Equipment − Standoff − Cover on Equipment Control Module Single−Piece Installation − Equipment Control Module − Reattach Display Module Set Thermidistat Control Configuration Page To Enter Configuration Mode Configuration Options -Selection Option 02 Clean Filter TimerOption 01 Equipment Type Option 04 Fan G On With W/W1 Option 03 Fahrenheit/CentigradeOption 08 Auxiliary Heat Lockout Temperature Option 06 Cooling Lockout Below 55F/13COption 07 Zoning Option 10 Reversing Valve Option 14 Humidity Display Offset Adjust Option 11 Deadband Setting Between Heat & CoolOption 12 Smart Recovery Option 13 Room Air Temperature Offset AdjustOption 17 Time Between Equipment Stages Option 16 Maximum Cycles Per HourOption 19 Dry Contact Configuration programmable models only Option 18 Backlight ConfigurationOption 21 Keypad Lockout programmable models only Option 20 Outdoor Air Temperature Offset AdjustmentOption 21 Keypad Lockout non−programmable models only Page Option 26 Minimum Cooling Setpoint Option 27 Maximum Heating Setpoint Option 28 UV Light ReminderOption 29 Humidifier Pad Reminder Option 30 Programmable Fan programmable models only Option 33 Single or Two−Piece Installation Option 34 − Hybrid Heat Furnace Latch Option 40 Humidify FanOption 41 Variable Speed Blower Option 43 Intelligent Heat Staging Option 42 Variable Speed Super DehumidificationOption 44 Super Comfort Heat Option 99 Reset to Factory Defaults System START−UP and Checkout Energy Star Default Schedule Final SettingsPage Humidity Control Features HumidificationHumidification Selections To Select Humidification programmable To Select Humidification non−programmableAdditional Humidify Comments Dehumidification − Auto Humidity Additional Dehumidify Comments Dehumidify Output and Equipment Connections Vacation programmable models onlyVacation Dehumidification Vacation Setpoints Default ValuesVacation Setpoints Vacation HumidificationOperational Information TimersCycle Timer Ten−Minute Staging TimerThree−Minute Minimum on Time DefrostEmergency Heat Mode Equipment On IndicatorsHeat/Cool Setpoints Desired Temperature Humidify and Dehumidify IndicatorsDry Contact Programmable Fan programmable models onlyRelays Temperature Offset After Power CycleError Codes TroubleshootingPage Equipment Configuration Outputs − Equipment Configuration Outputs − Display to Equipment Control Module Connection Wiring Diagrams− FV/FK Fan Coil with 2−Stage Heat Pump − Typical Fan Coil with Heat Pump HUM − FV/FK Fan Coil w/2−Stage Air Conditioner − Typical Fan Coil with Air Conditioner A09169 − FV/FK Fan Coil with 1−Stage Heat Pump − Typical Fan Coil Heating Only HUM − FV/FK Fan Coil with 1−Stage Air Conditioner − Typical Fan Coil Cooling Only A09121 − Single−Stage Furnace with Heat Pump Hybrid Heat COM − Single−Stage Furnace with Single−Speed Air Conditioner A09125 − Single−Stage Furnace Heating Only A09127 − Single−stage Furnace with Air Conditioner and Split Power Mode Settings Thermidistat Control Configuration RecordConfiguration Options Configuration Options Option Fan Humidity Variable Speed Blower Catalog No TP-PRH-4SI