Defrost

When defrost occurs in a Hybrid Heat system, the furnace will operate during the defrost cycle. At the end of the defrost cycle, the furnace and heat pump will be de−energized while the fan is energized for 2 minutes allowing the heat exchanger to cool down. If Option 34, Hybrid Heat Furnace Latch is set to Off, at the end of the 2 minute time, the heat pump will be re−energized if a call for heat still exists. If Option 34 is set to On (default), the furnace will remain on until the end of the heating cycle.

Defrost detection is not available if the installer has configured the O/W2/B output to function as a B output. During heat pump heating, a defrost signal shall be considered valid if the compressor output is energized and the defrost signal has been active for less than 15 consecutive minutes. Any defrost signal present for longer than 15 minutes shall be considered invalid.

Heat pump/fan coil and Hybrid Heat systems shall use this input to:

SDetect that defrost is in progress and energize the auxiliary heat to provide homeowner comfort during the defrost cycle

SAllow a defrost cycle to run to completion regardless of the system demand

Three−Minute Minimum on Time

In normal operation, when a stage turns on, it will not turn off for a minimum of 3 minutes. In Hybrid Heat systems, the minimum on time for the furnace is 5 minutes. If the setpoint is changed, this timer is canceled, allowing the equipment to turn off immediately when the demand is removed. The 3 minute minimum on timer applies to all stages of heating and cooling, except Hybrid Heat. A stage will run for a minimum of 3 minutes before the thermostat will be allowed to stage to a lower stage.

56

Image 56
Contents USA Programmable ControlDesigned and Assembled Table of Contents Safety ConsiderationsIntroduction Installation Considerations PowerModels Humidify Equipment and ConnectionsOutdoor Temperature Sensor TSTATCCSEN01−B Dehumidify Equipment and ConnectionsWiring Remote Indoor Temperature SensorTwo−Piece Thermidistat Control Configuration Installation − TP−PRH−A Carton Contents− TP−NRH−A Carton Contents Thermidistat Control LocationInstall Thermidistat Control Unit Damage Hazard Two−Piece Installation Environmental Hazard− Press Tabs to Remove Backplate − Backplate Mounting − Control Module Wiring Guide − Secure Wires to Terminal Strip − Attach Display to Backplate − Equipment Control Module on Equipment − Standoff − Cover on Equipment Control Module Single−Piece Installation − Equipment Control Module − Reattach Display Module Set Thermidistat Control Configuration Page To Enter Configuration Mode Option 01 Equipment Type Configuration Options -SelectionOption 02 Clean Filter Timer Option 03 Fahrenheit/Centigrade Option 04 Fan G On With W/W1Option 07 Zoning Option 08 Auxiliary Heat Lockout TemperatureOption 06 Cooling Lockout Below 55F/13C Option 10 Reversing Valve Option 11 Deadband Setting Between Heat & Cool Option 12 Smart RecoveryOption 13 Room Air Temperature Offset Adjust Option 14 Humidity Display Offset AdjustOption 16 Maximum Cycles Per Hour Option 17 Time Between Equipment StagesOption 18 Backlight Configuration Option 19 Dry Contact Configuration programmable models onlyOption 20 Outdoor Air Temperature Offset Adjustment Option 21 Keypad Lockout programmable models onlyOption 21 Keypad Lockout non−programmable models only Page Option 26 Minimum Cooling Setpoint Option 29 Humidifier Pad Reminder Option 27 Maximum Heating SetpointOption 28 UV Light Reminder Option 30 Programmable Fan programmable models only Option 33 Single or Two−Piece Installation Option 41 Variable Speed Blower Option 34 − Hybrid Heat Furnace LatchOption 40 Humidify Fan Option 42 Variable Speed Super Dehumidification Option 43 Intelligent Heat StagingOption 44 Super Comfort Heat Option 99 Reset to Factory Defaults System START−UP and Checkout Final Settings Energy Star Default SchedulePage Humidification Selections Humidity Control FeaturesHumidification Additional Humidify Comments To Select Humidification programmableTo Select Humidification non−programmable Dehumidification − Auto Humidity Additional Dehumidify Comments Vacation programmable models only Dehumidify Output and Equipment ConnectionsVacation Setpoints Default Values Vacation SetpointsVacation Humidification Vacation DehumidificationTimers Cycle TimerTen−Minute Staging Timer Operational InformationDefrost Three−Minute Minimum on TimeEquipment On Indicators Heat/Cool Setpoints Desired TemperatureHumidify and Dehumidify Indicators Emergency Heat ModeProgrammable Fan programmable models only Dry ContactTemperature Offset After Power Cycle RelaysTroubleshooting Error CodesPage Equipment Configuration Outputs − Equipment Configuration Outputs Wiring Diagrams − Display to Equipment Control Module Connection− FV/FK Fan Coil with 2−Stage Heat Pump − Typical Fan Coil with Heat Pump HUM − FV/FK Fan Coil w/2−Stage Air Conditioner − Typical Fan Coil with Air Conditioner A09169 − FV/FK Fan Coil with 1−Stage Heat Pump − Typical Fan Coil Heating Only HUM − FV/FK Fan Coil with 1−Stage Air Conditioner − Typical Fan Coil Cooling Only A09121 − Single−Stage Furnace with Heat Pump Hybrid Heat COM − Single−Stage Furnace with Single−Speed Air Conditioner A09125 − Single−Stage Furnace Heating Only A09127 − Single−stage Furnace with Air Conditioner and Split Power Thermidistat Control Configuration Record Mode SettingsConfiguration Options Configuration Options Option Fan Humidity Variable Speed Blower Catalog No TP-PRH-4SI