Carrier TP-NRH-A, TP-PRH-A installation instructions Auto Humidity

Page 51

setpoint is adjusted upward by 2% per degree of overcooling. For example, a cooling setpoint of 76_F/24_C and a dehumidify setpoint of 60% is equivalent to a cooling setpoint of 75_F/24_C and a dehumidify setpoint of 62%. This dehumidify setpoint change is internal to the Thermidistat Control and is not shown on the display.

A06599

Fig. 17 − Auto Humidity

3.Dehumidify Off

Dehumidification can be turned off completely. This can be done without changing existing setpoints.

51

Image 51
Contents Programmable Control Designed and AssembledUSA Safety Considerations Table of ContentsIntroduction Power Installation ConsiderationsHumidify Equipment and Connections ModelsDehumidify Equipment and Connections Outdoor Temperature Sensor TSTATCCSEN01−BRemote Indoor Temperature Sensor Two−Piece Thermidistat Control ConfigurationWiring − TP−PRH−A Carton Contents InstallationThermidistat Control Location − TP−NRH−A Carton ContentsInstall Thermidistat Control Unit Damage Hazard Environmental Hazard Two−Piece Installation− Press Tabs to Remove Backplate − Backplate Mounting − Control Module Wiring Guide − Secure Wires to Terminal Strip − Attach Display to Backplate − Equipment Control Module on Equipment − Standoff − Cover on Equipment Control Module Single−Piece Installation − Equipment Control Module − Reattach Display Module Set Thermidistat Control Configuration Page To Enter Configuration Mode Configuration Options -Selection Option 02 Clean Filter TimerOption 01 Equipment Type Option 04 Fan G On With W/W1 Option 03 Fahrenheit/CentigradeOption 08 Auxiliary Heat Lockout Temperature Option 06 Cooling Lockout Below 55F/13COption 07 Zoning Option 10 Reversing Valve Option 14 Humidity Display Offset Adjust Option 11 Deadband Setting Between Heat & CoolOption 12 Smart Recovery Option 13 Room Air Temperature Offset AdjustOption 17 Time Between Equipment Stages Option 16 Maximum Cycles Per HourOption 19 Dry Contact Configuration programmable models only Option 18 Backlight ConfigurationOption 21 Keypad Lockout programmable models only Option 20 Outdoor Air Temperature Offset AdjustmentOption 21 Keypad Lockout non−programmable models only Page Option 26 Minimum Cooling Setpoint Option 27 Maximum Heating Setpoint Option 28 UV Light ReminderOption 29 Humidifier Pad Reminder Option 30 Programmable Fan programmable models only Option 33 Single or Two−Piece Installation Option 34 − Hybrid Heat Furnace Latch Option 40 Humidify FanOption 41 Variable Speed Blower Option 43 Intelligent Heat Staging Option 42 Variable Speed Super DehumidificationOption 44 Super Comfort Heat Option 99 Reset to Factory Defaults System START−UP and Checkout Energy Star Default Schedule Final SettingsPage Humidity Control Features HumidificationHumidification Selections To Select Humidification programmable To Select Humidification non−programmableAdditional Humidify Comments Dehumidification − Auto Humidity Additional Dehumidify Comments Dehumidify Output and Equipment Connections Vacation programmable models onlyVacation Dehumidification Vacation Setpoints Default ValuesVacation Setpoints Vacation HumidificationOperational Information TimersCycle Timer Ten−Minute Staging TimerThree−Minute Minimum on Time DefrostEmergency Heat Mode Equipment On IndicatorsHeat/Cool Setpoints Desired Temperature Humidify and Dehumidify IndicatorsDry Contact Programmable Fan programmable models onlyRelays Temperature Offset After Power CycleError Codes TroubleshootingPage Equipment Configuration Outputs − Equipment Configuration Outputs − Display to Equipment Control Module Connection Wiring Diagrams− FV/FK Fan Coil with 2−Stage Heat Pump − Typical Fan Coil with Heat Pump HUM − FV/FK Fan Coil w/2−Stage Air Conditioner − Typical Fan Coil with Air Conditioner A09169 − FV/FK Fan Coil with 1−Stage Heat Pump − Typical Fan Coil Heating Only HUM − FV/FK Fan Coil with 1−Stage Air Conditioner − Typical Fan Coil Cooling Only A09121 − Single−Stage Furnace with Heat Pump Hybrid Heat COM − Single−Stage Furnace with Single−Speed Air Conditioner A09125 − Single−Stage Furnace Heating Only A09127 − Single−stage Furnace with Air Conditioner and Split Power Mode Settings Thermidistat Control Configuration RecordConfiguration Options Configuration Options Option Fan Humidity Variable Speed Blower Catalog No TP-PRH-4SI