setpoint is adjusted upward by 2% per degree of overcooling. For example, a cooling setpoint of 76_F/24_C and a dehumidify setpoint of 60% is equivalent to a cooling setpoint of 75_F/24_C and a dehumidify setpoint of 62%. This dehumidify setpoint change is internal to the Thermidistat Control and is not shown on the display.
A06599
Fig. 17 − Auto Humidity
3.Dehumidify Off