Carrier TP-PRH-A Option 16 Maximum Cycles Per Hour, Option 17 Time Between Equipment Stages

Page 32

Control to automatically change between heating mode and cooling mode when sufficient demand for heating or cooling exists.

On — Auto mode is available. OF — Auto mode is not available. Default is On.

Option 16 — Maximum Cycles Per Hour

This selection limits the number of cycles per hour that the Thermidistat Control allows the system to operate. Selections are 2, 4, 6.

2 — The heating and cooling outputs will be energized no more than 2 times per hour. When an output is energized, it will not be energized again for 30 minutes.

4 — The heating and cooling outputs will be energized no more than 4 times per hour. When an output is energized, it will not be energized again for 15 minutes.

6 — The heating and cooling outputs will be energized no more than 6 times per hour. When an output is energized, it will not be energized again for 10 minutes.

Default is 4.

Option 17 — Time Between Equipment Stages

This selection is only available for heat pump systems. This determines the minimum number of minutes of equipment operation on the highest compressor stage before allowing the transition to auxiliary heat. Available selections are 10, 15, 20, and 25. The time between stages of any individual piece of equipment, such as low speed and high speed compressor or fan coil stages, will be fixed at

10minutes. Default is 15.

32

Image 32
Contents USA Programmable ControlDesigned and Assembled Table of Contents Safety ConsiderationsIntroduction Installation Considerations PowerModels Humidify Equipment and ConnectionsOutdoor Temperature Sensor TSTATCCSEN01−B Dehumidify Equipment and ConnectionsWiring Remote Indoor Temperature SensorTwo−Piece Thermidistat Control Configuration Installation − TP−PRH−A Carton Contents− TP−NRH−A Carton Contents Thermidistat Control LocationInstall Thermidistat Control Unit Damage Hazard Two−Piece Installation Environmental Hazard− Press Tabs to Remove Backplate − Backplate Mounting − Control Module Wiring Guide − Secure Wires to Terminal Strip − Attach Display to Backplate − Equipment Control Module on Equipment − Standoff − Cover on Equipment Control Module Single−Piece Installation − Equipment Control Module − Reattach Display Module Set Thermidistat Control Configuration Page To Enter Configuration Mode Option 01 Equipment Type Configuration Options -SelectionOption 02 Clean Filter Timer Option 03 Fahrenheit/Centigrade Option 04 Fan G On With W/W1Option 07 Zoning Option 08 Auxiliary Heat Lockout TemperatureOption 06 Cooling Lockout Below 55F/13C Option 10 Reversing Valve Option 11 Deadband Setting Between Heat & Cool Option 12 Smart RecoveryOption 13 Room Air Temperature Offset Adjust Option 14 Humidity Display Offset AdjustOption 16 Maximum Cycles Per Hour Option 17 Time Between Equipment StagesOption 18 Backlight Configuration Option 19 Dry Contact Configuration programmable models onlyOption 20 Outdoor Air Temperature Offset Adjustment Option 21 Keypad Lockout programmable models onlyOption 21 Keypad Lockout non−programmable models only Page Option 26 Minimum Cooling Setpoint Option 29 Humidifier Pad Reminder Option 27 Maximum Heating SetpointOption 28 UV Light Reminder Option 30 Programmable Fan programmable models only Option 33 Single or Two−Piece Installation Option 41 Variable Speed Blower Option 34 − Hybrid Heat Furnace LatchOption 40 Humidify Fan Option 42 Variable Speed Super Dehumidification Option 43 Intelligent Heat StagingOption 44 Super Comfort Heat Option 99 Reset to Factory Defaults System START−UP and Checkout Final Settings Energy Star Default SchedulePage Humidification Selections Humidity Control FeaturesHumidification Additional Humidify Comments To Select Humidification programmableTo Select Humidification non−programmable Dehumidification − Auto Humidity Additional Dehumidify Comments Vacation programmable models only Dehumidify Output and Equipment ConnectionsVacation Setpoints Default Values Vacation SetpointsVacation Humidification Vacation DehumidificationTimers Cycle TimerTen−Minute Staging Timer Operational InformationDefrost Three−Minute Minimum on TimeEquipment On Indicators Heat/Cool Setpoints Desired TemperatureHumidify and Dehumidify Indicators Emergency Heat ModeProgrammable Fan programmable models only Dry ContactTemperature Offset After Power Cycle RelaysTroubleshooting Error CodesPage Equipment Configuration Outputs − Equipment Configuration Outputs Wiring Diagrams − Display to Equipment Control Module Connection− FV/FK Fan Coil with 2−Stage Heat Pump − Typical Fan Coil with Heat Pump HUM − FV/FK Fan Coil w/2−Stage Air Conditioner − Typical Fan Coil with Air Conditioner A09169 − FV/FK Fan Coil with 1−Stage Heat Pump − Typical Fan Coil Heating Only HUM − FV/FK Fan Coil with 1−Stage Air Conditioner − Typical Fan Coil Cooling Only A09121 − Single−Stage Furnace with Heat Pump Hybrid Heat COM − Single−Stage Furnace with Single−Speed Air Conditioner A09125 − Single−Stage Furnace Heating Only A09127 − Single−stage Furnace with Air Conditioner and Split Power Thermidistat Control Configuration Record Mode SettingsConfiguration Options Configuration Options Option Fan Humidity Variable Speed Blower Catalog No TP-PRH-4SI