Option 18 — Backlight Configuration

When OF (off), the backlight will be lit for 10 seconds after a button is pressed. After 10 seconds of no button presses, the backlight turns off. When On, the backlight will normally be on and dim in appearance. The backlight brightness becomes brighter when a button is pressed. After 10 seconds of no button presses, the backlight will return to the dimmer level until another button press occurs. The range of brightness is 1 through 5 with 5 being full brightness.

Default is 3.

Option 19 — Dry Contact Configuration (programmable models only)

There are 3 available selections, OF, 1 and 2. OF — The dry contact is always de−energized.

1 — The dry contact will be energized for the specified number of minutes per hour. This selection is programmable by period. When this selection is changed from OF to 1, the period icons are shown and the minute segments of the clock display are shown. The triangle icon next to the WAKE period will be on and a value between 0 and 60 will be shown in the minutes display. See Operational Information and Wiring Diagrams for further explanation of dry contact configuration and use. To change the period or minutes, press the soft key below the period or minutes and then use the UP/DOWN buttons to change to the desired value.

2 — The dry contact will operate as a DH relay. This relay is reverse logic. When the humidity level is above the dehumidify setpoint, the dry contact D1−D2 will be opened. When the humidity level is below the dehumidify setpoint, D1−D2 will be closed. There is a +/− 2% hysteresis around the dehumidify setpoint to prevent rapid on/off cycling of the DH output. When configured for dehumidification, the Rc terminal must be connected to one of the dry contact terminals. This provides power to energize the dehumidify terminal on the

33

Image 33
Contents Programmable Control Designed and AssembledUSA Safety Considerations Table of ContentsIntroduction Power Installation ConsiderationsHumidify Equipment and Connections ModelsDehumidify Equipment and Connections Outdoor Temperature Sensor TSTATCCSEN01−BRemote Indoor Temperature Sensor Two−Piece Thermidistat Control ConfigurationWiring − TP−PRH−A Carton Contents InstallationThermidistat Control Location − TP−NRH−A Carton ContentsInstall Thermidistat Control Unit Damage Hazard Environmental Hazard Two−Piece Installation− Press Tabs to Remove Backplate − Backplate Mounting − Control Module Wiring Guide − Secure Wires to Terminal Strip − Attach Display to Backplate − Equipment Control Module on Equipment − Standoff − Cover on Equipment Control Module Single−Piece Installation − Equipment Control Module − Reattach Display Module Set Thermidistat Control Configuration Page To Enter Configuration Mode Configuration Options -Selection Option 02 Clean Filter TimerOption 01 Equipment Type Option 04 Fan G On With W/W1 Option 03 Fahrenheit/CentigradeOption 08 Auxiliary Heat Lockout Temperature Option 06 Cooling Lockout Below 55F/13COption 07 Zoning Option 10 Reversing Valve Option 12 Smart Recovery Option 11 Deadband Setting Between Heat & CoolOption 13 Room Air Temperature Offset Adjust Option 14 Humidity Display Offset AdjustOption 17 Time Between Equipment Stages Option 16 Maximum Cycles Per HourOption 19 Dry Contact Configuration programmable models only Option 18 Backlight ConfigurationOption 21 Keypad Lockout programmable models only Option 20 Outdoor Air Temperature Offset AdjustmentOption 21 Keypad Lockout non−programmable models only Page Option 26 Minimum Cooling Setpoint Option 27 Maximum Heating Setpoint Option 28 UV Light ReminderOption 29 Humidifier Pad Reminder Option 30 Programmable Fan programmable models only Option 33 Single or Two−Piece Installation Option 34 − Hybrid Heat Furnace Latch Option 40 Humidify FanOption 41 Variable Speed Blower Option 43 Intelligent Heat Staging Option 42 Variable Speed Super DehumidificationOption 44 Super Comfort Heat Option 99 Reset to Factory Defaults System START−UP and Checkout Energy Star Default Schedule Final SettingsPage Humidity Control Features HumidificationHumidification Selections To Select Humidification programmable To Select Humidification non−programmableAdditional Humidify Comments Dehumidification − Auto Humidity Additional Dehumidify Comments Dehumidify Output and Equipment Connections Vacation programmable models onlyVacation Setpoints Vacation Setpoints Default ValuesVacation Humidification Vacation DehumidificationCycle Timer TimersTen−Minute Staging Timer Operational InformationThree−Minute Minimum on Time DefrostHeat/Cool Setpoints Desired Temperature Equipment On IndicatorsHumidify and Dehumidify Indicators Emergency Heat ModeDry Contact Programmable Fan programmable models onlyRelays Temperature Offset After Power CycleError Codes TroubleshootingPage Equipment Configuration Outputs − Equipment Configuration Outputs − Display to Equipment Control Module Connection Wiring Diagrams− FV/FK Fan Coil with 2−Stage Heat Pump − Typical Fan Coil with Heat Pump HUM − FV/FK Fan Coil w/2−Stage Air Conditioner − Typical Fan Coil with Air Conditioner A09169 − FV/FK Fan Coil with 1−Stage Heat Pump − Typical Fan Coil Heating Only HUM − FV/FK Fan Coil with 1−Stage Air Conditioner − Typical Fan Coil Cooling Only A09121 − Single−Stage Furnace with Heat Pump Hybrid Heat COM − Single−Stage Furnace with Single−Speed Air Conditioner A09125 − Single−Stage Furnace Heating Only A09127 − Single−stage Furnace with Air Conditioner and Split Power Mode Settings Thermidistat Control Configuration RecordConfiguration Options Configuration Options Option Fan Humidity Variable Speed Blower Catalog No TP-PRH-4SI