Heat Controller HEV/H manual Antifreeze, Low Water Temperature Cutout Setting DXM2 Control

Page 15

Heat Controller, Inc.

HEV/H SERIES

Installation, Operation & Maintenance

 

 

 

GROUND-LOOP HEAT PUMP APPLICATIONS

pressure is reached. Open the return valve and a pressure surge will be sent through the loop to help purge air pockets from the piping system.

4.Notice the drop in fluid level in the flush cart tank when the return valve is shut off. If air is adequately purged from the system, the level will drop only 1-2 inches (2.5 - 5 cm) in a 10” (25 cm) diameter PVC flush tank (about a half gallon [2.3 liters]), since liquids are incompressible. If the level drops more

than this, flushing should continue since air is still being compressed in the loop fluid. Perform the “dead head” procedure a number of times.

Note: This fluid level drop is your only indication of air in the loop.

Antifreeze may be added before, during or after the flushing procedure. However, depending upon which time is chosen, antifreeze could be wasted when emptying the flush cart tank. See antifreeze section for more details.

Loop static pressure will fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially. Run the unit in either heating or cooling for a number of minutes to condition the loop to a homogenous temperature. This is a good time for tool cleanup, piping insulation, etc. Then, perform final flush and pressurize the loop to a static pressure of 50-75 psi [345-517 kPa] (winter) or 35-40 psi [241-276 kPa] (summer). After pressurization, be sure

to loosen the plug at the end of the Grundfos loop pump motor(s) to allow trapped air to be discharged and to insure the motor housing has been flooded. This is not required for Taco circulators. Insure that the Flow Controller provides adequate flow through the unit by checking pressure drop across the heat exchanger and compare to the pressure drop tables at the back of the manual.

Antifreeze

In areas where minimum entering loop temperatures drop below 40°F [5°C] or where piping will be routed through areas subject to freezing, antifreeze is required. Alcohols and glycols are commonly used as antifreeze; however your local sales manager should be consulted for the antifreeze best suited to your area. Freeze protection should be maintained to 15°F [9°C] below the lowest expected entering loop temperature. For example, if 30°F [-1°C] is the minimum expected entering loop

temperature, the leaving loop temperature would be 25 to 22°F [-4 to -6°C] and freeze protection should be at 15°F [-10°C]. Calculation is as follows:

30°F - 15°F = 15°F [-1°C - 9°C = -10°C].

All alcohols should be premixed and pumped from a reservoir outside of the building when possible or introduced under the water level to prevent fumes.

Calculate the total volume of fluid in the piping system. Then use the percentage by volume shown in Table

1 for the amount of antifreeze needed. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specific gravity.

Low Water Temperature Cutout Setting

DXM2 Control

When antifreeze is selected, the FP1 jumper (JW3) should be clipped to select the low temperature (an- tifreeze 13°F [-10.6°C]) set point and avoid nuisance faults (see “Low Water Temperature Cutout Selection” in this manual). NOTE: Low water temperature operation requires extended range equipment.

Table 1: Approximate Fluid Volume (gal.) per 100' of Pipe

Fluid Volume (gal [L]/100’ Pipe)

Pipe

Size

Volume (gal) [L]

 

 

 

 

1”

4.1 [15.5]

 

 

 

Copper

1.25”

6.4 [24.2]

 

 

 

 

2.5”

9.2 [34.8]

 

 

 

Rubber Hose

1”

3.9 [14.8]

 

 

 

 

3/4” IPS SDR11

2.8 [10.6]

 

 

 

 

1” IPS SDR11

4.5 [17.0]

 

 

 

 

1.25” IPS SDR11

8.0 [30.3]

 

 

 

 

Polyethylene

1.5” IPS SDR11

10.9

[41.3]

 

 

 

2” IPS SDR11

18.0

[68.1]

 

 

 

 

 

1.25” IPS SCH40

8.3 [31.4]

 

 

 

 

 

1.5” IPS SCH40

10.9

[41.3]

 

 

 

 

 

2” IPS SCH40

17.0

[64.4]

 

 

 

 

Unit Heat Exchanger

Typical

1.0

[3.8]

 

 

 

 

Flush Cart Tank

10” Dia x 3ft

10 [37.9]

[254mm x 0.9m]

 

 

 

 

 

 

 

Table 2: Antifreeze Percentages by Volume

Type

Minimum Temperature for Freeze Protection

 

10°F [-12.2°C]

15°F [-9.4°C]

20°F [-6.7°C]

25°F [-3.9°C]

 

 

 

 

 

Methanol

25%

21%

16%

10%

100% USP food grade Propylene Glycol

38%

30%

22%

15%

 

 

 

 

 

15

Image 15
Contents Residential Packaged Geothermal Heat Pump Table of Contents Unit Nomenclature Configuration Supply AIR OptionsSafety General Information Vertical Upflow Physical DataHE Vertical Upflow Dimensional Data Return Connection Standard Deluxe Filter Frame Vertical Unit Location Vertical InstallationCondensate Piping for Vertical Units Sound Attenuation for Vertical UnitsVertical Installation Horizontal Unit LocationMounting Horizontal Units Typical Closed Loop Horizontal Unit Installation Horizontal InstallationField Conversion of AIR Discharge Field Conversion of Air DischargeSide to Back Discharge Conversion GROUND-LOOP Heat Pump Applications Water Connection InstallationAntifreeze Low Water Temperature Cutout Setting DXM2 ControlGROUND-WATER Heat Pump Applications Open Loop Ground Water SystemsWater Quality Standards Flow Regulation Water Coil Low Temperature Limit SettingExpansion Tank and Pump Water Control ValveWater Quality Standards Water Quality StandardsHOT Water Generator Typical HWG InstallationInstallation Initial Start-Up Water Tank PreparationHWG Water Piping Water Tank RefillGeneral Line Voltage Wiring Electrical Line VoltageElectrical Line Voltage Volt Operation Electrical Power WiringPower Connection HWG WiringElectrical LOW Voltage Wiring Low Water Temperature Cutout SelectionThermostat Connections Accessory Connections Taco ValveThermostat Thermostat Installation Electrical Thermostat WiringECM Blower Control ECM Blower Performance Data Table Blower Performance DataWiring Diagram Unit Operation DXM2 ControlsP11 DXM2 Layout and ConnectionsUnit Commissioning and Operating Conditions Operating LimitsCommissioning Conditions Unit Starting and Operating Conditions Unit Start-up Procedure Unit START-UP and Operating ConditionsUnit and System Checkout Unit START-UP Procedure Unit START-UP ProcedureHE Coax Water Pressure Drop Unit Operating ConditionsHE Series Typical Unit Operating Pressures and Temperatures Unit Operating Conditions Preventive Maintenance Troubleshooting Start DXM2 Process Flow ChartFault Htg Clg Possible Cause Solution Functional TroubleshootingIFC Fault Code 410A Troubleshooting FormHEV/H Series 97B0016N11

HEV/H specifications

The Heat Controller HEV/H series represents a significant advancement in heating technology, designed to provide efficient and effective climate control for both residential and commercial spaces. This innovative range of heat pumps combines cutting-edge features with user-friendly functionality to offer a reliable solution for modern heating needs.

One of the standout features of the HEV/H series is its advanced inverter technology. This system allows the heat pump to adjust its output based on the specific heating requirements of the environment. By varying the compressor's speed, the HEV/H maintains a consistent temperature while significantly reducing energy consumption. This not only lowers utility bills but also reduces environmental impact, making it a more sustainable option compared to traditional heating methods.

The HEV/H series is equipped with a high-efficiency heat exchanger, which maximizes heat transfer and enhances overall performance. This component ensures that the system can operate effectively even in colder climates, providing reliable heating throughout the winter months. Additionally, the unit’s low noise operation is designed to maintain a peaceful environment, making it suitable for bedrooms, offices, and other noise-sensitive areas.

Another notable characteristic of the HEV/H series is its smart control features. Integrated with Wi-Fi connectivity, users can conveniently manage their heating settings remotely via a smartphone app. This feature allows for customized scheduling and temperature control, ensuring optimal comfort and convenience. Users can also receive real-time notifications on energy consumption and system performance, enhancing user engagement and control.

The HEV/H series also emphasizes durability and longevity. Constructed with high-quality materials, the units are designed to withstand the rigors of daily use while requiring minimal maintenance. The incorporation of advanced filtration systems helps to improve indoor air quality by capturing dust and allergens, which is especially beneficial for individuals with allergies or respiratory issues.

In summary, the Heat Controller HEV/H series exemplifies modern heating technology with its combination of efficiency, control, and user-friendly features. Its inverter technology, high-efficiency heat exchangers, smart connectivity, and durable construction make it an outstanding choice for anyone seeking to enhance their indoor climate while being conscious of energy usage and environmental impact. Whether for a home or business, the HEV/H series is poised to deliver exceptional heating solutions tailored to diverse needs.