Heat Controller HEV/H manual Water Quality Standards

Page 18

Installation, Operation & Maintenance

HEV/H SERIES

Heat Controller, Inc.

 

 

 

WATER QUALITY STANDARDS

Table 3: Water Quality Standards

Water Quality Parameter

HX

Material

Closed

Recirculating

Open Loop and Recirculating Well

Scaling Potential - Primary Measurement

Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below

pH/Calcium Hardness Method

All

-

pH < 7.5 and Ca Hardness <100ppm

Index Limits for Probable Scaling Situations - (Operation outside these limits is not recommended)

Scaling indexes should be calculated at 66°C for direct use and HWG applications, and at 32°C for indirect HX use. A monitoring plan should be implemented.

Ryznar Stability Index

Langelier Saturation Index

All

All

-

-

6.0 - 7.5

If >7.5 minimize steel pipe use.

-0.5 to +0.5

If <-0.5 minimize steel pipe use. Based upon 66°C HWG and Direct well, 29°C Indirect Well HX

Iron Fouling

Iron Fe 2+ (Ferrous) (Bacterial Iron potential)

Iron Fouling

All

All

-

-

<0.2 ppm (Ferrous)

If Fe2+ (ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.

<0.5 ppm of Oxygen

Above this level deposition will occur .

Corrosion Prevention

pH

Hydrogen Sulfide (H2S)

Ammonia ion as hydroxide, chloride, nitrate and sulfate compounds

Maximum

Chloride Levels

All

All

All

Copper

Cupronickel

304SS

316SS

Titanium

6 - 8.5

Monitor/treat as

needed

-

-

-

-

-

-

-

6 - 8.5

Minimize steel pipe below 7 and no open tanks with pH <8

<0.5 ppm

At H2S>0.2 ppm, avoid use of copper and copper nickel piping or HX's. Rotten egg smell appears at 0.5 ppm level.

Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.

<0.5 ppm

Maximum Allowable at maximum water temperature.

10C

24C

38 C

<20ppm

NR

NR

<150 ppm

NR

NR

<400 ppm

<250 ppm

<150 ppm

<1000 ppm

<550 ppm

< 375 ppm

>1000 ppm

>550 ppm

>375 ppm

Erosion and Clogging

Particulate Size and

Erosion

All

<10 ppm of particles and a maximum velocity of 1.8 m/s Filtered for maximum 841 micron [0.84 mm, 20 mesh] size.

<10 ppm (<1 ppm "sandfree” for reinjection) of particles and a maximum velocity of 1.8 m/s. Filtered for maximum 841 micron 0.84 mm,

20 mesh] size. Any particulate that is not removed can potentially clog components.

The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. When water properties are outside of those requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger.

Notes:

‡&ORVHG5HFLUFXODWLQJV\VWHPLVLGHQWLILHGE\Dclosed pressurized piping system.

‡5HFLUFXODWLQJRSHQZHOOVVKRXOGREVHUYHWKHRSHQUHFLUFXODWLQJGHVLJQFRQVLGHUDWLRQV

‡15Application not recommended.

‡1RGHVLJQ0D[LPXP

Rev.: 3/22/2012

18

Image 18
Contents Residential Packaged Geothermal Heat Pump Table of Contents Configuration Supply AIR Options Unit NomenclatureSafety General Information Physical Data Vertical UpflowHE Vertical Upflow Dimensional Data Return Connection Standard Deluxe Filter Frame Vertical Installation Vertical Unit LocationSound Attenuation for Vertical Units Condensate Piping for Vertical UnitsVertical Installation Horizontal Unit LocationMounting Horizontal Units Horizontal Installation Typical Closed Loop Horizontal Unit InstallationField Conversion of AIR Discharge Field Conversion of Air DischargeSide to Back Discharge Conversion Water Connection Installation GROUND-LOOP Heat Pump ApplicationsLow Water Temperature Cutout Setting DXM2 Control AntifreezeGROUND-WATER Heat Pump Applications Open Loop Ground Water SystemsWater Quality Standards Water Control Valve Water Coil Low Temperature Limit SettingExpansion Tank and Pump Flow RegulationWater Quality Standards Water Quality StandardsTypical HWG Installation HOT Water GeneratorInstallation Water Tank Refill Water Tank PreparationHWG Water Piping Initial Start-UpGeneral Line Voltage Wiring Electrical Line VoltageElectrical Line Voltage HWG Wiring Electrical Power WiringPower Connection Volt OperationElectrical LOW Voltage Wiring Low Water Temperature Cutout SelectionThermostat Connections Accessory Connections Taco ValveThermostat Electrical Thermostat Wiring Thermostat InstallationECM Blower Control Blower Performance Data ECM Blower Performance Data TableWiring Diagram DXM2 Controls Unit OperationDXM2 Layout and Connections P11Unit Commissioning and Operating Conditions Operating LimitsCommissioning Conditions Unit Starting and Operating Conditions Unit Start-up Procedure Unit START-UP and Operating ConditionsUnit and System Checkout Unit START-UP Procedure Unit START-UP ProcedureUnit Operating Conditions HE Coax Water Pressure DropHE Series Typical Unit Operating Pressures and Temperatures Unit Operating Conditions Preventive Maintenance Troubleshooting DXM2 Process Flow Chart StartFunctional Troubleshooting Fault Htg Clg Possible Cause SolutionIFC Fault Code Troubleshooting Form 410AHEV/H Series 97B0016N11

HEV/H specifications

The Heat Controller HEV/H series represents a significant advancement in heating technology, designed to provide efficient and effective climate control for both residential and commercial spaces. This innovative range of heat pumps combines cutting-edge features with user-friendly functionality to offer a reliable solution for modern heating needs.

One of the standout features of the HEV/H series is its advanced inverter technology. This system allows the heat pump to adjust its output based on the specific heating requirements of the environment. By varying the compressor's speed, the HEV/H maintains a consistent temperature while significantly reducing energy consumption. This not only lowers utility bills but also reduces environmental impact, making it a more sustainable option compared to traditional heating methods.

The HEV/H series is equipped with a high-efficiency heat exchanger, which maximizes heat transfer and enhances overall performance. This component ensures that the system can operate effectively even in colder climates, providing reliable heating throughout the winter months. Additionally, the unit’s low noise operation is designed to maintain a peaceful environment, making it suitable for bedrooms, offices, and other noise-sensitive areas.

Another notable characteristic of the HEV/H series is its smart control features. Integrated with Wi-Fi connectivity, users can conveniently manage their heating settings remotely via a smartphone app. This feature allows for customized scheduling and temperature control, ensuring optimal comfort and convenience. Users can also receive real-time notifications on energy consumption and system performance, enhancing user engagement and control.

The HEV/H series also emphasizes durability and longevity. Constructed with high-quality materials, the units are designed to withstand the rigors of daily use while requiring minimal maintenance. The incorporation of advanced filtration systems helps to improve indoor air quality by capturing dust and allergens, which is especially beneficial for individuals with allergies or respiratory issues.

In summary, the Heat Controller HEV/H series exemplifies modern heating technology with its combination of efficiency, control, and user-friendly features. Its inverter technology, high-efficiency heat exchangers, smart connectivity, and durable construction make it an outstanding choice for anyone seeking to enhance their indoor climate while being conscious of energy usage and environmental impact. Whether for a home or business, the HEV/H series is poised to deliver exceptional heating solutions tailored to diverse needs.