Installation Manual For Indoor Unit
(3)Avoid installation and use at those places listed below.
(a)Places exposed to oil splashes or steam (e.g. kitchens and machine plants).
Installation and use at such places incur deteriorations in the performance or corrosion with the heat exchanger or damage in molded synthetic resin parts.
(b)Places where corrosive gas (such as sulfurous acid gas) or inflammable gas (thinner, gasoline, etc) in generated or remains. Installation and use at such places cause corrosion in the heat exchanger and damage in molded synthetic resin parts.
(c)Places adjacent to equipment generating electromagnetic waves or
Generated noise may cause malfunctioning of the controller.
(4)Preparation for suspending the unit
(a)Size of hole at ceiling and position of hanging bolts <Combination with silent panel>
|
| (Pipe co- nnection side) |
57 | A | 137 |
(Hanging bolt position)
B
(Ceiling hole size)
C
(Panel dimensions)
75 | bolt(Hangingposition) 690 | hole(Ceilingsize) 750 dimensions)(Panel |
70 |
|
|
545 |
|
|
| 30 | dimensions) |
30 |
| panel~ |
| (Ceiling wrap | |
|
|
(Ceiling ~ panel wrap dimensions)
|
|
| Unit: mm | |
|
|
|
| |
Dimensions | A | B | C | |
Model | ||||
|
|
| ||
For series 182 242 282 362 | 1000 | 1194 | 1254 | |
|
|
|
| |
For series 482 | 1406 | 1600 | 1660 | |
|
|
|
|
(b) Hanger bolts installation
Use care of the piping direction when the unit is installed.
Insert | |
|
Concrete
Hanging bolt M10
14