Haier AD362AMEAA, AD482AMEAA, AD362AMERA Installation work for air outlet ducts, Blowout duct

Page 18

Installation Manual For Indoor Unit

(7) Installation work for air outlet ducts

Air conditioner main unit

Ceiling surface

BSpecial blowout (Option)

Heat

inlet duct

 

 

insulation

(optional or

 

Suction panel

 

marketat item)

 

 

 

(Silent panel)

A Blowout duct

C

special inlet (option)

(Optional or marketed item)

 

 

 

(with air filter)

Hole for check

Calculate the draft and external static pressure and select the length, shape and blowout.

ABlowout duct

2-spot, 3-spot and 4-spot with 200 type duct are the standard specifications. Determine the number of spots based on following table.

Note (1) Shield the central blowout hole for 2-spot.

(2) Shield the blowout hole around the center for 3-spot.

Limit the difference in length between spots at less than 2:1. Reduce the length of duct as much as possible.

Reduce the number of bends as much as possible. (Corner R should be as larger as possible.)

Bad example

Bad example

Good example

Use a band. etc. to connect the main unit and the blowout duct flange.

Conduct the duct installation work before finishing the ceiling.

(8) Connection of suction, exhaust ducts

State seeing from top of unit

 

Exhaust hole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Side fresh air inlet

Rear fresh air inlet

Fig.1

Fig.2

(a) Duct connection position i) Fresh air inlet

Inlet can be selected from the side or rear faces depending on the working conditions. Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted. (Side inlet cannot be used.)

ii)Exhaust (Make sure to use also the suction.) Use the side exhaust port.

17

Image 18
Contents Duct Type AIR Conditioner Please keep this manual carefully and safelyTable of Contents Disposal of the old air conditioner Safety Precautions Circuit breaker may be necessary Positive drainingNeither stand on the air conditioner nor Machine is adaptive in following situation OutdoorParts and Functions Duct Air outlet Air inletCooling or heating is not sufficient MalfunctionUnit fails to start Cooling is not sufficientWater flowing sound is heard Case of Auto mode, operation mode is changed automatiFollowings are not malfunction This is caused by heat expansion or contraction of plasticsCare and Maintenance Points to observeFor Preparation of HeatingHot Keep When you change your address or the installation place Is The Unit Installed CorrectlyInstallation place For inspection and maintenanceInstallation Manual For Indoor Unit Serious injury are listed416mm Preparation of indoor unitCombination Avoid installation and use at those places listed below Hanger bolts installationTap selection on blower unit Installation of indoor unitAdjusting to the levelness Drain PipingProcedures Drainage TestInstallation work for air outlet ducts Blowout ductConnection of suction, exhaust ducts Wiring connection ModelTrouble Shooting Shows resumable fault, shows it is not resumable faultRemarks Resumable if DegreeHaier Group