Haier AD282AMERA, AD482AMEAA, AD362AMERA, AD362AMEAA, AD182AMEAA, AD242AMERA Model, Wiring connection

Page 19

Installation Manual For Indoor Unit

5. Electric wiring

WARNING

DANGER OF BODILY INJURY OR DEATH

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.

(1)Selection of size of power supply and interconnecting wires. Precautions for Electric wiring

Electric wiring work should be conducted only by authorized personnel.

Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires.

Use copper conductor only.

Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)

Item

Model

Circuit

breaker

Power source

Earth leakage breaker

Phase Switch breaker

Overcurrent protector

wire size

Switch

Leak

(minimum)

(A)

rated capacity (A)

(mm2)

breaker(A)

current(mA)

For series 182

1

40

26

2.5

40

30

For series 242

1

40

26

4.0

40

30

For series 282 362

1

40

26

6.0

40

30

For series

3

30

20

2.5

30

30

282 362 482

 

 

 

 

 

 

(2) Wiring connection

Make wiring to supply power to the indoor unit, so that the power for the outdoor unit is supplied by terminals.

For series 182

INDOOR UNIT TERMINAL BLOCK

OUTDOOR UNIT TERMINAL BLOCK

1 2 3 N L

Y/G

 

1

2

3

 

 

Y/G

Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals.

For series 242 282 362

For series 282 362 482

 

INDOOR UNIT

1

2

3

Y/G

 

INDOOR UNIT

1 2 3

 

TERMINAL BLOCK

 

 

 

 

TERMINAL BLOCK

 

 

 

 

 

 

OUTDOOR UNIT

Y/G

N 1 2 3

OUTDOOR UNIT

L N

1

2

3

 

R S T

 

TERMINAL BLOCK

TERMINAL BLOCK

 

 

 

Y/G

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY: 380-400V, 3N~, 50Hz

POWER SUPPLY: 1PH, 220-230V~, 50Hz

Y/G

Y/G

18

Image 19
Contents Please keep this manual carefully and safely Duct Type AIR ConditionerTable of Contents Disposal of the old air conditioner Circuit breaker may be necessary Positive draining Safety PrecautionsNeither stand on the air conditioner nor Outdoor Machine is adaptive in following situationDuct Air outlet Air inlet Parts and FunctionsCooling is not sufficient MalfunctionUnit fails to start Cooling or heating is not sufficientThis is caused by heat expansion or contraction of plastics Case of Auto mode, operation mode is changed automatiFollowings are not malfunction Water flowing sound is heardPoints to observe Care and MaintenanceFor Preparation of HeatingHot Keep For inspection and maintenance Is The Unit Installed CorrectlyInstallation place When you change your address or the installation placeSerious injury are listed Installation Manual For Indoor UnitPreparation of indoor unit 416mmCombination Hanger bolts installation Avoid installation and use at those places listed belowDrain Piping Installation of indoor unitAdjusting to the levelness Tap selection on blower unitDrainage Test ProceduresBlowout duct Installation work for air outlet ductsConnection of suction, exhaust ducts Model Wiring connectionShows resumable fault, shows it is not resumable fault Trouble ShootingRemarks Degree Resumable ifHaier Group