Haier AU142AFBIA, AD142AMBIA Open space requirement around the unit, Installation

Page 13

INSTALLATION MANUAL FOR OUTDOOR UNIT

<Heat Pump model/Cooling Only model >

WARNING

BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE. BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.

1. Accessories

Edging

"Edging" for protection of electric wires from an opening edge.

2. Selection of the place of installation

Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or user.

Place where air circulates.

Place free from heat radiation from other heat sources.

Place where drain water may be discharged.

Place where noise and hot air may not disturb the neighborhood.

Place where there is not heavy snowfall in the winter time.

Place where obstacles do not exist near the air inlet and air outlet .

Place where the air outlet may not be exposed to a strong wind.

Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit.

Mount guide-louvers to place where short-circuit is a possibility.

When installing several units, secure sufficient suction space to avoid short circuiting.

(1) Open space requirement around the unit

Unit: mm

L2

Air inlet

Air inlet L3

500

(Servicing

space)

Air outlet

L1

Distance

Case

I

II

III

 

L1

 

open

open

500

 

 

 

 

 

L2

 

300

0

open

 

 

 

 

 

L3

 

150

300

150

 

 

 

 

 

(2) Installation where the area with strong winds.

Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction.

3. Installation of outdoor unit

NO

(1) Installation

Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .

(a) Concrete foundation

Unit

Anchor bolt

Concrete foundation

To fix by bolts

Note (1) Give enough room for the concrete foundation to fix by anchor bolts.

Foundation anchor

Unit

Concrete foundation

Anchor bolt

Note (1) Place the concrete foundation deep enough.

Install the unit so that the angle of inclination must be less than 3 degrees. 12

Image 13
Contents Operation & Installation Manual Table of Contents Disposal of the old air conditioner Make sure the system is grounded Safety PrecautionsDo not wash the air conditioner with water Machine is adaptive in following situation Applicable ambient temperature rangeParts and Functions Unit fails to start MalfunctionCooling or heating is not sufficient Cooling is not sufficientFollowings are not malfunction Cleaning Care and MaintenancePoints to observe Defrosting operation in the heating mode When heating is startedWhen the room thermostat is actuated Atmospheric temperature and warming capacityInstallation place Installation Manual for Outdoor UnitInstallation Installation where the area with strong windsOpen space requirement around the unit Outline piping Precautions for refrigerant pipingPiping size Piping connectionInstallation Manual for Outdoor Unit Installation Manual for Indoor Unit Preparation of indoor unit Avoid installation and use at those places listed belowPreparation for suspending the unit 225Wood structure Install the hoisting screwNew cement panel Steel structure Original cement panelSuspending of indoor unit RequirementsConfirm drainage Material of connection pipe and thermal insulationPermitted length and fall of connection pipe Connection of refrigerant pipeElectric wiring Installation Manual for Electric WiringPay attention not to damage PC board Wire. And the two ends of the shieldInstallation check and test run Configuration of power supplyCheck and Test RUN Set of the air sending of the fan motor