Haier AD142AMBIA Machine is adaptive in following situation, Applicable ambient temperature range

Page 6

SAFETY PRECAUTIONS

The machine is adaptive in following situation

1. Applicable ambient temperature range:

 

 

 

Rated

Maximum

Minimum

 

Indoor

DB C

27

32

18

Cooling

WB C

19

23

14

 

outdoor

DB C

35

43

-5

 

 

WB C

24

26

--

 

 

Heating

Indoor

DB C

20

27

15

 

WB C

14.5

--

--

 

 

 

outdoor

DB C

7

24

-7

 

WB C

6

18

--

 

 

2.If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.

3.If the fuse on PC board is broken please change it with the type of T3.15A /250VAC.

4.The wiring method should be in line with the local wiring standard.

5.Use copper wire only. The connecting cable should be H05RN-F 4G 0.75mm2. The power cable should be H07RN-F 3G 2.5mm2. All the cables shall have got the European allthentication certificate.

6.The power supply connects from the outdoor side.

7.The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should be no less 3mm.

8.The indoor unit installation height is at least 2.5m.

Note:

Part of the power supply of the air conditioner are not prepared because of the requirement of the dealer, the power supply should be provided for oneself.

5

Image 6
Contents Operation & Installation Manual Table of Contents Disposal of the old air conditioner Safety Precautions Make sure the system is groundedDo not wash the air conditioner with water Applicable ambient temperature range Machine is adaptive in following situationParts and Functions Cooling or heating is not sufficient MalfunctionUnit fails to start Cooling is not sufficientFollowings are not malfunction Care and Maintenance CleaningPoints to observe When the room thermostat is actuated When heating is startedDefrosting operation in the heating mode Atmospheric temperature and warming capacityInstallation Manual for Outdoor Unit Installation placeInstallation where the area with strong winds InstallationOpen space requirement around the unit Piping size Precautions for refrigerant pipingOutline piping Piping connectionInstallation Manual for Outdoor Unit Installation Manual for Indoor Unit Avoid installation and use at those places listed below Preparation of indoor unit225 Preparation for suspending the unitInstall the hoisting screw Wood structureNew cement panel Suspending of indoor unit Original cement panelSteel structure RequirementsPermitted length and fall of connection pipe Material of connection pipe and thermal insulationConfirm drainage Connection of refrigerant pipeInstallation Manual for Electric Wiring Electric wiringWire. And the two ends of the shield Pay attention not to damage PC boardCheck and Test RUN Configuration of power supplyInstallation check and test run Set of the air sending of the fan motor