INSTALLATION MANUAL FOR INDOOR UNIT

NOTICE

All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to your local distributor.

WARNING

BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAI- LURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.

(1) Preparation of indoor unit

Before or during the installation of the unit, assemble necessary optional panel etc. depending on the specific type.

(2)Select places for installation satisfying following conditions and at the same time obtain the consent on the part of your client user.

(a) Places where chilled or heated air circulates freely.

When the installation height exceeds 3m warmed air stays close to the ceiling. In such cases, suggest our client users to install air circulators.

(b)Places where perfect drainage can be prepared and sufficient drainage.

(c)Places free from air disturbances to the suction port and blowout hole of the indoor unit, places where the fire alarm may not malfunction or short-circuit.

(d)Places with the environmental dew-point temperature is lower than 28 C and the relative humidity is less than 80%.

(When installing at a place under a high humidity environment, pay sufficient attention to the prevention of dewing such as thermal insulation of the unit. )

(e)Ceiling height shall have the following height.

Installation space

Combination with silent panel

366mm

100 or

 

100 or

more

more

more

 

50 or more

 

1000 or

 

 

Obstacle

Unit: mm

(3)Avoid installation and use at those places listed below.

(a)Places exposed to oil splashes or steam (e.g. kitchens and machine plants).

Installation and use at such places incur deteriorations in the performance or corrosion with the heat exchanger or damage in molded synthetic resin parts.

(b)Places where corrosive gas (such as sulfurous acid gas) or inflammable gas (thinner, gasoline, etc) in generated or remains. Installation and use at such places cause corrosion in the heat exchanger and damage in molded synthetic resin parts.

(c)Places adjacent to equipment generating electromagnetic waves or high-frequency waves such as in hospitals.

Generated noise may cause malfunctioning of the controller.

16

Image 17
Contents Operation & Installation Manual Table of Contents Disposal of the old air conditioner Make sure the system is grounded Safety PrecautionsDo not wash the air conditioner with water Machine is adaptive in following situation Applicable ambient temperature rangeParts and Functions Unit fails to start MalfunctionCooling or heating is not sufficient Cooling is not sufficientFollowings are not malfunction Points to observe Care and MaintenanceCleaning Defrosting operation in the heating mode When heating is startedWhen the room thermostat is actuated Atmospheric temperature and warming capacityInstallation place Installation Manual for Outdoor UnitOpen space requirement around the unit Installation where the area with strong windsInstallation Outline piping Precautions for refrigerant pipingPiping size Piping connectionInstallation Manual for Outdoor Unit Installation Manual for Indoor Unit Preparation of indoor unit Avoid installation and use at those places listed belowPreparation for suspending the unit 225New cement panel Install the hoisting screwWood structure Steel structure Original cement panelSuspending of indoor unit RequirementsConfirm drainage Material of connection pipe and thermal insulationPermitted length and fall of connection pipe Connection of refrigerant pipeElectric wiring Installation Manual for Electric WiringPay attention not to damage PC board Wire. And the two ends of the shieldInstallation check and test run Configuration of power supplyCheck and Test RUN Set of the air sending of the fan motor