Haier AD142AMBIA Original cement panel, Steel structure, Suspending of indoor unit, Requirements

Page 20

INSTALLATION MANUAL FOR INDOOR UNIT

Original cement panel

Use the in hole hinge, in hole plug or in hole screw.

Steel structure

Suspending bolt

 

Directly use angle steel or new angle

 

steel for support.

 

Suspending of indoor unit

Angle steel for support

Hoisting screw

Fix the cap of hoisting screw on and suspend them on the T groove of the hoisting part of the unit.

Use gradienter to keep the level degree of the unit within 5mm.

!Notice

In order to normally drain water, the drain hose should be mated according to the installation manual. In order to avoid dew-forming, thermal insulation treatment should be done.

Improper connection pipe may cause water enter indoor.

Requirements:

The indoor side drain hose should be thermal insulated.

The parts connected with indoor unit should be thermal insulated. Improper thermal insulation may cause dew-forming phenomenon.

The drain hose should be downwards slant (over 1/100) and there should be no S-shaped bend.

Otherwise, abnormal sound may occur.

The horizontal length of the drain hose should be less than 20m. If the connection pipe is too long, the supporting frame should be set every 1.5~2m to prevent pipe from rise and fall. For the centralized connection pipe, please perform work as the following Figure shown. Pay attention not to exerting external force to the connection part of the drain hose.

1m~1.5m

Supporting frame

Downward slant over 1/100

Thermal insulation material (user self-provided)

As large as possible (about 10cm)

VP30

Downward slant over 1/100

S-shaped bend

Wall

Outside

Slant

Drain hose

(user self-provided)

19

Image 20
Contents Operation & Installation Manual Table of Contents Disposal of the old air conditioner Safety Precautions Make sure the system is groundedDo not wash the air conditioner with water Applicable ambient temperature range Machine is adaptive in following situationParts and Functions Malfunction Unit fails to startCooling or heating is not sufficient Cooling is not sufficientFollowings are not malfunction Points to observe Care and MaintenanceCleaning When heating is started Defrosting operation in the heating modeWhen the room thermostat is actuated Atmospheric temperature and warming capacityInstallation Manual for Outdoor Unit Installation placeOpen space requirement around the unit Installation where the area with strong windsInstallation Precautions for refrigerant piping Outline pipingPiping size Piping connectionInstallation Manual for Outdoor Unit Installation Manual for Indoor Unit Avoid installation and use at those places listed below Preparation of indoor unit225 Preparation for suspending the unitNew cement panel Install the hoisting screwWood structure Original cement panel Steel structureSuspending of indoor unit RequirementsMaterial of connection pipe and thermal insulation Confirm drainagePermitted length and fall of connection pipe Connection of refrigerant pipeInstallation Manual for Electric Wiring Electric wiringWire. And the two ends of the shield Pay attention not to damage PC boardConfiguration of power supply Installation check and test runCheck and Test RUN Set of the air sending of the fan motor